ABB Emax 2 Ekip signalling and programmable status
Signalling module, programmable status and datalogger settings of the ABB Emax 2 circuit breaker.
The ABB Emax 2 with an Ekip Touch trip unit is an air circuit breaker for main low voltage switchboards that can drive signalling relays and logic of its own. This Modbus RTU template reads the relay, input, programmable status and datalogger settings and lets you change them from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 221, read and write
- Brand
- ABB
- Key readings
- Relay functions · Relay delays · Input functions · Programmable status triggers · Datalogger triggers
- Available commands
- Relay function and delay · Input function and delay · Programmable status triggers · Datalogger stop delay
- Compatible models
- Ekip Touch · Ekip Hi-Touch · Ekip G Touch · ABB SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 with Ekip Com Modbus RTU, trip unit firmware 3.xx
- Last updated
Registers (221)
221 read, 221 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Relay 4K configuration | Read and write | 1500 | FC03 / FC06 | uint16 | |
| Relay 4K.1 Function | Read and write | 1501 | FC03 / FC06 | uint16 | |
| Relay 4K.1 Delay | s | Read and write | 1502 | FC03 / FC06 | uint16 |
| Relay 4K.2 Function | Read and write | 1503 | FC03 / FC06 | uint16 | |
| Relay 4K.2 Delay | s | Read and write | 1504 | FC03 / FC06 | uint16 |
| Relay 4K.3 Function | Read and write | ||||
| Relay 4K.3 Delay | s | Read and write | |||
| Relay 4K.4 Function | Read and write | ||||
| Relay 4K.4 Delay | s | Read and write | |||
| Input 4K configuration | Read and write | ||||
| Input 4K.1 delay | s | Read and write | |||
| Input 4K.2 Delay | s | Read and write | |||
| Input 4K.3 Delay | s | Read and write | |||
| Input 4K.4 Delay | s | Read and write | |||
| Relays 2K-1, 2K-2 Configuration | Read and write | ||||
| Relay 2K-1.1 Function | Read and write | ||||
| Relay 2K-1.1 Delay | s | Read and write | |||
| Relay 2K-1.2 Function | Read and write | ||||
| Relay 2K-1.2 Delay | s | Read and write | |||
| Relay 2K-2.1 Function | Read and write | ||||
| Relay 2K-2.1 Delay | s | Read and write | |||
| Relay 2K-2.2 Function | Read and write | ||||
| Relay 2K-2.2 Delay | s | Read and write | |||
| Relay 2K-3.1 Function | Read and write | ||||
| Relay 2K-3.1 Delay | s | Read and write | |||
| Relay 2K-3.2 Function | Read and write | ||||
| Relay 2K-3.2 Delay | s | Read and write | |||
| Relays 2K-3 Configuration | Read and write | ||||
| Trigger Opcode 1 Programmable Status A | Read and write | ||||
| Trigger Opcode 2 Programmable Status A | Read and write | ||||
| Trigger Opcode 3 Programmable Status A | Read and write | ||||
| Trigger Opcode 1 Programmable Status B | Read and write | ||||
| Trigger Opcode 2 Programmable Status B | Read and write | ||||
| Trigger Opcode 3 Programmable Status B | Read and write | ||||
| Trigger Opcode 1 Programmable Status C | Read and write | ||||
| Trigger Opcode 2 Programmable Status C | Read and write | ||||
| Trigger Opcode 3 Programmable Status C | Read and write | ||||
| Trigger Opcode 1 Programmable Status D | Read and write | ||||
| Trigger Opcode 2 Programmable Status D | Read and write | ||||
| Trigger Opcode 3 Programmable Status D | Read and write | ||||
| Delay On Programmable Status A | s | Read and write | |||
| Delay Off Programmable Status A | s | Read and write | |||
| Delay On Programmable Status B | s | Read and write | |||
| Delay Off Programmable Status B | s | Read and write | |||
| Delay On Programmable Status C | s | Read and write | |||
| Delay Off Programmable Status C | s | Read and write | |||
| Delay On Programmable Status D | s | Read and write | |||
| Delay Off Programmable Status D | s | Read and write | |||
| Dataloggers Configuration | Read and write | ||||
| Dataloggers Frequency | Read and write | ||||
| DLog 1 Trigger Opcode 1 | Read and write | ||||
| DLog 1 Trigger Opcode 2 | Read and write | ||||
| DLog 1 Trigger Opcode 3 | Read and write | ||||
| DLog 1 Stop Delay | s | Read and write | |||
| DLog 2 Trigger Opcode 1 | Read and write | ||||
| DLog 2 Trigger Opcode 2 | Read and write | ||||
| DLog 2 Trigger Opcode 3 | Read and write | ||||
| DLog 2 Stop Delay | s | Read and write | |||
| Relays 10K Configuration A | Read and write | ||||
| Relays 10K Configuration B | Read and write | ||||
| Relays 10K Configuration C | Read and write | ||||
| Relays 10K Configuration D | Read and write | ||||
| Relays 10K Configuration E | Read and write | ||||
| Relays 10K Configuration F | Read and write | ||||
| Relays 10K Configuration G | Read and write | ||||
| Relays 10K Configuration H | Read and write | ||||
| Relay 10K-1.1 Function | Read and write | ||||
| Relay 10K-1.1 Delay | s | Read and write | |||
| Relay 10K-1.2 Function | Read and write | ||||
| Relay 10K-1.2 Delay | s | Read and write | |||
| Relay 10K-1.3 Function | Read and write | ||||
| Relay 10K-1.3 Delay | s | Read and write | |||
| Relay 10K-1.4 Function | Read and write | ||||
| Relay 10K-1.4 Delay | s | Read and write | |||
| Relay 10K-1.5 Function | Read and write | ||||
| Relay 10K-1.5 Delay | s | Read and write | |||
| Relay 10K-1.6 Function | Read and write | ||||
| Relay 10K-1.6 Delay | s | Read and write | |||
| Relay 10K-1.7 Function | Read and write | ||||
| Relay 10K-1.7 Delay | s | Read and write | |||
| Relay 10K-1.8 Function | Read and write | ||||
| Relay 10K-1.8 Delay | s | Read and write | |||
| Relay 10K-1.9 Function | Read and write | ||||
| Relay 10K-1.9 Delay | s | Read and write | |||
| Relay 10K-1.10 Function | Read and write | ||||
| Relay 10K-1.10 Delay | s | Read and write | |||
| Relay 10K-2.1 Function | Read and write | ||||
| Relay 10K-2.1 Delay | s | Read and write | |||
| Relay 10K-2.2 Function | Read and write | ||||
| Relay 10K-2.2 Delay | s | Read and write | |||
| Relay 10K-2.3 Function | Read and write | ||||
| Relay 10K-2.3 Delay | s | Read and write | |||
| Relay 10K-2.4 Function | Read and write | ||||
| Relay 10K-2.4 Delay | s | Read and write | |||
| Relay 10K-2.5 Function | Read and write | ||||
| Relay 10K-2.5 Delay | s | Read and write | |||
| Relay 10K-2.6 Function | Read and write | ||||
| Relay 10K-2.6 Delay | s | Read and write | |||
| Relay 10K-2.7 Function | Read and write | ||||
| Relay 10K-2.7 Delay | s | Read and write | |||
| Relay 10K-2.8 Function | Read and write | ||||
| Relay 10K-2.8 Delay | s | Read and write | |||
| Relay 10K-2.9 Function | Read and write | ||||
| Relay 10K-2.9 Delay | s | Read and write | |||
| Relay 10K-2.10 Function | Read and write | ||||
| Relay 10K-2.10 Delay | s | Read and write | |||
| Relay 10K-3.1 Function | Read and write | ||||
| Relay 10K-3.1 Delay | s | Read and write | |||
| Relay 10K-3.2 Function | Read and write | ||||
| Relay 10K-3.2 Delay | s | Read and write | |||
| Relay 10K-3.3 Function | Read and write | ||||
| Relay 10K-3.3 Delay | s | Read and write | |||
| Relay 10K-3.4 Function | Read and write | ||||
| Relay 10K-3.4 Delay | s | Read and write | |||
| Relay 10K-3.5 Function | Read and write | ||||
| Relay 10K-3.5 Delay | s | Read and write | |||
| Relay 10K-3.6 Function | Read and write | ||||
| Relay 10K-3.6 Delay | s | Read and write | |||
| Relay 10K-3.7 Function | Read and write | ||||
| Relay 10K-3.7 Delay | s | Read and write | |||
| Relay 10K-3.8 Function | Read and write | ||||
| Relay 10K-3.8 Delay | s | Read and write | |||
| Relay 10K-3.9 Function | Read and write | ||||
| Relay 10K-3.9 Delay | s | Read and write | |||
| Relay 10K-3.10 Function | Read and write | ||||
| Relay 10K-3.10 Delay | s | Read and write | |||
| External Trip Function | Read and write | ||||
| External Trip Delay | s | Read and write | |||
| Trip Reset Function | Read and write | ||||
| Trip Reset Delay | s | Read and write | |||
| Set B Function | Read and write | ||||
| Set B Delay | s | Read and write | |||
| LocalRemote Function | Read and write | ||||
| LocalRemote Delay | s | Read and write | |||
| Reset Signalling Module Function | Read and write | ||||
| Reset Signalling Module Delay | s | Read and write | |||
| Energy Reset Function | Read and write | ||||
| Energy Reset Delay | s | Read and write | |||
| YO Function | Read and write | ||||
| YO Delay | s | Read and write | |||
| YC Function | Read and write | ||||
| YC Delay | s | Read and write | |||
| 2I Function | Read and write | ||||
| 2I Delay ON | s | Read and write | |||
| restartDlog1 Function | Read and write | ||||
| restartDlog1 Delay | s | Read and write | |||
| restartDlog2 Function | Read and write | ||||
| restartDlog2 Delay | s | Read and write | |||
| 2I Delay OFF | s | Read and write | |||
| Trigger Opcode 1 Programmable Status E | Read and write | ||||
| Trigger Opcode 2 Programmable Status E | Read and write | ||||
| Trigger Opcode 3 Programmable Status E | Read and write | ||||
| Delay On Programmable Status E | s | Read and write | |||
| Delay Off Programmable Status E | s | Read and write | |||
| Trigger Opcode 1 Programmable Status F | Read and write | ||||
| Trigger Opcode 2 Programmable Status F | Read and write | ||||
| Trigger Opcode 3 Programmable Status F | Read and write | ||||
| Delay On Programmable Status F | s | Read and write | |||
| Delay Off Programmable Status F | s | Read and write | |||
| Trigger Opcode 1 Programmable Status G | Read and write | ||||
| Trigger Opcode 2 Programmable Status G | Read and write | ||||
| Trigger Opcode 3 Programmable Status G | Read and write | ||||
| Delay On Programmable Status G | s | Read and write | |||
| Delay Off Programmable Status G | s | Read and write | |||
| Trigger Opcode 1 Programmable Status H | Read and write | ||||
| Trigger Opcode 2 Programmable Status H | Read and write | ||||
| Trigger Opcode 3 Programmable Status H | Read and write | ||||
| Delay On Programmable Status H | s | Read and write | |||
| Delay Off Programmable Status H | s | Read and write | |||
| Trigger Opcode 1 Programmable Status I | Read and write | ||||
| Trigger Opcode 2 Programmable Status I | Read and write | ||||
| Trigger Opcode 3 Programmable Status I | Read and write | ||||
| Delay On Programmable Status I | s | Read and write | |||
| Delay Off Programmable Status I | s | Read and write | |||
| Trigger Opcode 1 Programmable Status L | Read and write | ||||
| Trigger Opcode 2 Programmable Status L | Read and write | ||||
| Trigger Opcode 3 Programmable Status L | Read and write | ||||
| Delay On Programmable Status L | s | Read and write | |||
| Delay Off Programmable Status L | s | Read and write | |||
| Trigger Opcode 1 Programmable Status M | Read and write | ||||
| Trigger Opcode 2 Programmable Status M | Read and write | ||||
| Trigger Opcode 3 Programmable Status M | Read and write | ||||
| Delay On Programmable Status M | s | Read and write | |||
| Delay Off Programmable Status M | s | Read and write | |||
| Trigger Opcode 1 Programmable Status N | Read and write | ||||
| Trigger Opcode 2 Programmable Status N | Read and write | ||||
| Trigger Opcode 3 Programmable Status N | Read and write | ||||
| Delay On Programmable Status N | s | Read and write | |||
| Delay Off Programmable Status N | s | Read and write | |||
| Trigger Opcode 1 Programmable Status O | Read and write | ||||
| Trigger Opcode 2 Programmable Status O | Read and write | ||||
| Trigger Opcode 3 Programmable Status O | Read and write | ||||
| Delay On Programmable Status O | s | Read and write | |||
| Delay Off Programmable Status O | s | Read and write | |||
| Trigger Opcode 1 Programmable Status P | Read and write | ||||
| Trigger Opcode 2 Programmable Status P | Read and write | ||||
| Trigger Opcode 3 Programmable Status P | Read and write | ||||
| Delay On Programmable Status P | s | Read and write | |||
| Delay Off Programmable Status P | s | Read and write | |||
| Trigger Opcode 1 Programmable Status Q | Read and write | ||||
| Trigger Opcode 2 Programmable Status Q | Read and write | ||||
| Trigger Opcode 3 Programmable Status Q | Read and write | ||||
| Delay On Programmable Status Q | s | Read and write | |||
| Delay Off Programmable Status Q | s | Read and write | |||
| Trigger Opcode 1 Programmable Status R | Read and write | ||||
| Trigger Opcode 2 Programmable Status R | Read and write | ||||
| Trigger Opcode 3 Programmable Status R | Read and write | ||||
| Delay On Programmable Status R | s | Read and write | |||
| Delay Off Programmable Status R | s | Read and write | |||
| Programmable Status 2 Register 1770 | Read and write | ||||
| Programmable Status 2 Register 1771 | Read and write | ||||
| Programmable Status 2 Register 1772 | Read and write | ||||
| Programmable Status 2 Register 1773 | Read and write | ||||
| Trigger Opcode 1 Function S input | Read and write | ||||
| Trigger Opcode 1 Function S2 input | Read and write | ||||
| Trigger Opcode 1 Function G input | Read and write | ||||
| Trigger Opcode 1 Function Gext input | Read and write | ||||
| Trigger Opcode 1 Function DFw input | Read and write | ||||
| Trigger Opcode 1 Function DBw input | Read and write | ||||
| Trigger Opcode 1 Function S/DFw output | Read and write | ||||
| Trigger Opcode 1 Function G/DBw output | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Compare the relay functions of several Emax 2 breakers to find a switchboard that is set up differently.
- Check after commissioning that every signalling relay has the function and delay that the design asks for.
- Change the delay of a signalling relay remotely when it switches too early on short events.
- Keep a history of the programmable status settings so you can see when someone changed them.
- Set an alarm when a datalogger trigger or relay function changes, as a check on unplanned changes.
Installation
Fit the Ekip Com Modbus RTU module in the Emax 2 terminal box and give the trip unit and module auxiliary supply.
Wire the RS485 pair of the module to RS485 A and B of the ModbusCloud Gateway and terminate the bus with 120 ohm at both ends.
Read address, baud rate and parity on the Ekip Touch display (default 247, 19200, even parity).
In ModbusCloud, add a Modbus device with the same settings, or use the device of the core Emax 2 template, and import this template.
Check that the relay functions match what the Ekip Touch display shows for the fitted signalling modules.
Things to watch for
Can I write these settings from ModbusCloud?
Yes, the registers are read and write. Read the current value first and write only one setting at a time. A wrong relay function or trigger can switch outputs that control other equipment, so agree changes with whoever is responsible for the switchboard.
What do the function and trigger codes mean?
They are codes from the signalling and event tables of the Emax 2 trip unit. Look them up in the ABB tables or set the function once on the Ekip Touch display and read back the code that appears.
Why do some relay settings stay at zero?
Settings of a signalling module only mean something when that module is fitted. Without an Ekip Signalling 10K, for example, its relay functions stay at their default value.
The module does not answer at all. What should I check?
Check the auxiliary supply of the Ekip Com module and that address, baud rate and parity match the Gateway (default 247, 19200, even). Swap A and B if needed and terminate the bus at both ends.
Want to see how it works?