ABB ABB Emax 2 Ekip signalling and programmable status Modbus RTU template

ABB Emax 2 Ekip signalling and programmable status

Signalling module, programmable status and datalogger settings of the ABB Emax 2 circuit breaker.

The ABB Emax 2 with an Ekip Touch trip unit is an air circuit breaker for main low voltage switchboards that can drive signalling relays and logic of its own. This Modbus RTU template reads the relay, input, programmable status and datalogger settings and lets you change them from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
221, read and write
Brand
ABB
Key readings
Relay functions · Relay delays · Input functions · Programmable status triggers · Datalogger triggers
Available commands
Relay function and delay · Input function and delay · Programmable status triggers · Datalogger stop delay
Compatible models
Ekip Touch · Ekip Hi-Touch · Ekip G Touch · ABB SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 with Ekip Com Modbus RTU, trip unit firmware 3.xx
Last updated

Registers (221)

221 read, 221 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Relay 4K configurationRead and write1500FC03 / FC06uint16
Relay 4K.1 FunctionRead and write1501FC03 / FC06uint16
Relay 4K.1 DelaysRead and write1502FC03 / FC06uint16
Relay 4K.2 FunctionRead and write1503FC03 / FC06uint16
Relay 4K.2 DelaysRead and write1504FC03 / FC06uint16
Relay 4K.3 FunctionRead and write
Relay 4K.3 DelaysRead and write
Relay 4K.4 FunctionRead and write
Relay 4K.4 DelaysRead and write
Input 4K configurationRead and write
Input 4K.1 delaysRead and write
Input 4K.2 DelaysRead and write
Input 4K.3 DelaysRead and write
Input 4K.4 DelaysRead and write
Relays 2K-1, 2K-2 ConfigurationRead and write
Relay 2K-1.1 FunctionRead and write
Relay 2K-1.1 DelaysRead and write
Relay 2K-1.2 FunctionRead and write
Relay 2K-1.2 DelaysRead and write
Relay 2K-2.1 FunctionRead and write
Relay 2K-2.1 DelaysRead and write
Relay 2K-2.2 FunctionRead and write
Relay 2K-2.2 DelaysRead and write
Relay 2K-3.1 FunctionRead and write
Relay 2K-3.1 DelaysRead and write
Relay 2K-3.2 FunctionRead and write
Relay 2K-3.2 DelaysRead and write
Relays 2K-3 ConfigurationRead and write
Trigger Opcode 1 Programmable Status ARead and write
Trigger Opcode 2 Programmable Status ARead and write
Trigger Opcode 3 Programmable Status ARead and write
Trigger Opcode 1 Programmable Status BRead and write
Trigger Opcode 2 Programmable Status BRead and write
Trigger Opcode 3 Programmable Status BRead and write
Trigger Opcode 1 Programmable Status CRead and write
Trigger Opcode 2 Programmable Status CRead and write
Trigger Opcode 3 Programmable Status CRead and write
Trigger Opcode 1 Programmable Status DRead and write
Trigger Opcode 2 Programmable Status DRead and write
Trigger Opcode 3 Programmable Status DRead and write
Delay On Programmable Status AsRead and write
Delay Off Programmable Status AsRead and write
Delay On Programmable Status BsRead and write
Delay Off Programmable Status BsRead and write
Delay On Programmable Status CsRead and write
Delay Off Programmable Status CsRead and write
Delay On Programmable Status DsRead and write
Delay Off Programmable Status DsRead and write
Dataloggers ConfigurationRead and write
Dataloggers FrequencyRead and write
DLog 1 Trigger Opcode 1Read and write
DLog 1 Trigger Opcode 2Read and write
DLog 1 Trigger Opcode 3Read and write
DLog 1 Stop DelaysRead and write
DLog 2 Trigger Opcode 1Read and write
DLog 2 Trigger Opcode 2Read and write
DLog 2 Trigger Opcode 3Read and write
DLog 2 Stop DelaysRead and write
Relays 10K Configuration ARead and write
Relays 10K Configuration BRead and write
Relays 10K Configuration CRead and write
Relays 10K Configuration DRead and write
Relays 10K Configuration ERead and write
Relays 10K Configuration FRead and write
Relays 10K Configuration GRead and write
Relays 10K Configuration HRead and write
Relay 10K-1.1 FunctionRead and write
Relay 10K-1.1 DelaysRead and write
Relay 10K-1.2 FunctionRead and write
Relay 10K-1.2 DelaysRead and write
Relay 10K-1.3 FunctionRead and write
Relay 10K-1.3 DelaysRead and write
Relay 10K-1.4 FunctionRead and write
Relay 10K-1.4 DelaysRead and write
Relay 10K-1.5 FunctionRead and write
Relay 10K-1.5 DelaysRead and write
Relay 10K-1.6 FunctionRead and write
Relay 10K-1.6 DelaysRead and write
Relay 10K-1.7 FunctionRead and write
Relay 10K-1.7 DelaysRead and write
Relay 10K-1.8 FunctionRead and write
Relay 10K-1.8 DelaysRead and write
Relay 10K-1.9 FunctionRead and write
Relay 10K-1.9 DelaysRead and write
Relay 10K-1.10 FunctionRead and write
Relay 10K-1.10 DelaysRead and write
Relay 10K-2.1 FunctionRead and write
Relay 10K-2.1 DelaysRead and write
Relay 10K-2.2 FunctionRead and write
Relay 10K-2.2 DelaysRead and write
Relay 10K-2.3 FunctionRead and write
Relay 10K-2.3 DelaysRead and write
Relay 10K-2.4 FunctionRead and write
Relay 10K-2.4 DelaysRead and write
Relay 10K-2.5 FunctionRead and write
Relay 10K-2.5 DelaysRead and write
Relay 10K-2.6 FunctionRead and write
Relay 10K-2.6 DelaysRead and write
Relay 10K-2.7 FunctionRead and write
Relay 10K-2.7 DelaysRead and write
Relay 10K-2.8 FunctionRead and write
Relay 10K-2.8 DelaysRead and write
Relay 10K-2.9 FunctionRead and write
Relay 10K-2.9 DelaysRead and write
Relay 10K-2.10 FunctionRead and write
Relay 10K-2.10 DelaysRead and write
Relay 10K-3.1 FunctionRead and write
Relay 10K-3.1 DelaysRead and write
Relay 10K-3.2 FunctionRead and write
Relay 10K-3.2 DelaysRead and write
Relay 10K-3.3 FunctionRead and write
Relay 10K-3.3 DelaysRead and write
Relay 10K-3.4 FunctionRead and write
Relay 10K-3.4 DelaysRead and write
Relay 10K-3.5 FunctionRead and write
Relay 10K-3.5 DelaysRead and write
Relay 10K-3.6 FunctionRead and write
Relay 10K-3.6 DelaysRead and write
Relay 10K-3.7 FunctionRead and write
Relay 10K-3.7 DelaysRead and write
Relay 10K-3.8 FunctionRead and write
Relay 10K-3.8 DelaysRead and write
Relay 10K-3.9 FunctionRead and write
Relay 10K-3.9 DelaysRead and write
Relay 10K-3.10 FunctionRead and write
Relay 10K-3.10 DelaysRead and write
External Trip FunctionRead and write
External Trip DelaysRead and write
Trip Reset FunctionRead and write
Trip Reset DelaysRead and write
Set B FunctionRead and write
Set B DelaysRead and write
LocalRemote FunctionRead and write
LocalRemote DelaysRead and write
Reset Signalling Module FunctionRead and write
Reset Signalling Module DelaysRead and write
Energy Reset FunctionRead and write
Energy Reset DelaysRead and write
YO FunctionRead and write
YO DelaysRead and write
YC FunctionRead and write
YC DelaysRead and write
2I FunctionRead and write
2I Delay ONsRead and write
restartDlog1 FunctionRead and write
restartDlog1 DelaysRead and write
restartDlog2 FunctionRead and write
restartDlog2 DelaysRead and write
2I Delay OFFsRead and write
Trigger Opcode 1 Programmable Status ERead and write
Trigger Opcode 2 Programmable Status ERead and write
Trigger Opcode 3 Programmable Status ERead and write
Delay On Programmable Status EsRead and write
Delay Off Programmable Status EsRead and write
Trigger Opcode 1 Programmable Status FRead and write
Trigger Opcode 2 Programmable Status FRead and write
Trigger Opcode 3 Programmable Status FRead and write
Delay On Programmable Status FsRead and write
Delay Off Programmable Status FsRead and write
Trigger Opcode 1 Programmable Status GRead and write
Trigger Opcode 2 Programmable Status GRead and write
Trigger Opcode 3 Programmable Status GRead and write
Delay On Programmable Status GsRead and write
Delay Off Programmable Status GsRead and write
Trigger Opcode 1 Programmable Status HRead and write
Trigger Opcode 2 Programmable Status HRead and write
Trigger Opcode 3 Programmable Status HRead and write
Delay On Programmable Status HsRead and write
Delay Off Programmable Status HsRead and write
Trigger Opcode 1 Programmable Status IRead and write
Trigger Opcode 2 Programmable Status IRead and write
Trigger Opcode 3 Programmable Status IRead and write
Delay On Programmable Status IsRead and write
Delay Off Programmable Status IsRead and write
Trigger Opcode 1 Programmable Status LRead and write
Trigger Opcode 2 Programmable Status LRead and write
Trigger Opcode 3 Programmable Status LRead and write
Delay On Programmable Status LsRead and write
Delay Off Programmable Status LsRead and write
Trigger Opcode 1 Programmable Status MRead and write
Trigger Opcode 2 Programmable Status MRead and write
Trigger Opcode 3 Programmable Status MRead and write
Delay On Programmable Status MsRead and write
Delay Off Programmable Status MsRead and write
Trigger Opcode 1 Programmable Status NRead and write
Trigger Opcode 2 Programmable Status NRead and write
Trigger Opcode 3 Programmable Status NRead and write
Delay On Programmable Status NsRead and write
Delay Off Programmable Status NsRead and write
Trigger Opcode 1 Programmable Status ORead and write
Trigger Opcode 2 Programmable Status ORead and write
Trigger Opcode 3 Programmable Status ORead and write
Delay On Programmable Status OsRead and write
Delay Off Programmable Status OsRead and write
Trigger Opcode 1 Programmable Status PRead and write
Trigger Opcode 2 Programmable Status PRead and write
Trigger Opcode 3 Programmable Status PRead and write
Delay On Programmable Status PsRead and write
Delay Off Programmable Status PsRead and write
Trigger Opcode 1 Programmable Status QRead and write
Trigger Opcode 2 Programmable Status QRead and write
Trigger Opcode 3 Programmable Status QRead and write
Delay On Programmable Status QsRead and write
Delay Off Programmable Status QsRead and write
Trigger Opcode 1 Programmable Status RRead and write
Trigger Opcode 2 Programmable Status RRead and write
Trigger Opcode 3 Programmable Status RRead and write
Delay On Programmable Status RsRead and write
Delay Off Programmable Status RsRead and write
Programmable Status 2 Register 1770Read and write
Programmable Status 2 Register 1771Read and write
Programmable Status 2 Register 1772Read and write
Programmable Status 2 Register 1773Read and write
Trigger Opcode 1 Function S inputRead and write
Trigger Opcode 1 Function S2 inputRead and write
Trigger Opcode 1 Function G inputRead and write
Trigger Opcode 1 Function Gext inputRead and write
Trigger Opcode 1 Function DFw inputRead and write
Trigger Opcode 1 Function DBw inputRead and write
Trigger Opcode 1 Function S/DFw outputRead and write
Trigger Opcode 1 Function G/DBw outputRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Compare the relay functions of several Emax 2 breakers to find a switchboard that is set up differently.
  • Check after commissioning that every signalling relay has the function and delay that the design asks for.
  • Change the delay of a signalling relay remotely when it switches too early on short events.
  • Keep a history of the programmable status settings so you can see when someone changed them.
  • Set an alarm when a datalogger trigger or relay function changes, as a check on unplanned changes.

Installation

  1. Fit the Ekip Com Modbus RTU module in the Emax 2 terminal box and give the trip unit and module auxiliary supply.

  2. Wire the RS485 pair of the module to RS485 A and B of the ModbusCloud Gateway and terminate the bus with 120 ohm at both ends.

  3. Read address, baud rate and parity on the Ekip Touch display (default 247, 19200, even parity).

  4. In ModbusCloud, add a Modbus device with the same settings, or use the device of the core Emax 2 template, and import this template.

  5. Check that the relay functions match what the Ekip Touch display shows for the fitted signalling modules.

Things to watch for

Can I write these settings from ModbusCloud?

Yes, the registers are read and write. Read the current value first and write only one setting at a time. A wrong relay function or trigger can switch outputs that control other equipment, so agree changes with whoever is responsible for the switchboard.

What do the function and trigger codes mean?

They are codes from the signalling and event tables of the Emax 2 trip unit. Look them up in the ABB tables or set the function once on the Ekip Touch display and read back the code that appears.

Why do some relay settings stay at zero?

Settings of a signalling module only mean something when that module is fitted. Without an Ekip Signalling 10K, for example, its relay functions stay at their default value.

The module does not answer at all. What should I check?

Check the auxiliary supply of the Ekip Com module and that address, baud rate and parity match the Gateway (default 247, 19200, even). Swap A and B if needed and terminate the bus at both ends.