Atrea DUPLEX RD5

Heat recovery ventilation unit with remote performance, mode and temperature control.

The Atrea DUPLEX with RD5 control is a heat recovery ventilation unit that supplies fresh air and extracts used air in homes, schools and offices. This Modbus TCP template reads air temperatures, air flows, mode and all alarms, and lets you set the required performance, operating mode and temperature from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
117, read and write
Brand
Atrea
Key readings
Supply air temperature · Outdoor air temperature · Indoor air temperature · Supply and exhaust flow · Desired mode · Alarms and warnings
Available commands
Required performance · Desired mode · Required temperature · Required zone · Season
Compatible models
DUPLEX units with RD5 control · DUPLEX EC5 · DUPLEX ECV5 · DUPLEX Multi · DUPLEX Pro
Last updated

Registers (117)

117 read, 13 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Outdoor Air Temperature°CRead
Supply Air Temperature°CRead
Exhaust Air Temperature°CRead
Waste Air Temperature°CRead
Indoor Air Temperature°CRead
Current Supply Flowm³/hRead
Current Exhaust Flowm³/hRead
Required Supply Flowm³/hRead
Required Exhaust Flowm³/hRead
Required Fresh Air Flowm³/hRead
Current Fresh Air Flowm³/hRead
Fan M1 SignalmVRead
Fan M2 SignalmVRead
Heater RegulationRead
Heat Pump ControlRead
Water Heater PumpRead
Water Heating ValveRead
Heat Pump Heating SignalRead
Heat Pump Cooling SignalRead
Required Performance CurrentRead
Desired Mode CurrentRead
Required Temperature Current°CRead
Required Zone CurrentRead
Current SeasonRead
Required PerformanceRead and write
Desired ModeRead and write
Required Temperature°CRead and write
Required ZoneRead and write
Season SettingRead and write
Performance Control SourceRead and write
Mode Control SourceRead and write
Temperature Control SourceRead and write
Zone Control SourceRead and write
T-ODA SourceRead and write
T-ODA From BMS°CRead and write
T-IDA SourceRead and write
T-IDA From BMS°CRead and write
Mode Condition C10508Read
Mode Condition C10509Read
Fan Control MethodRead
Unit OrientationRead
Heater TypeRead
Cooler TypeRead
Temperature Control TypeRead
Circulation Damper FittedRead
Clock YearRead
Clock MonthRead
Clock DayRead
Clock HourRead
Clock MinuteRead
Clock SecondRead
Unit OverheatingRead
Unset OrientationRead
Heater Type Not SetRead
Frost Protection 2Read
STP Contact ActiveRead
DP1 Pressure Gauge FailureRead
DP2 Pressure Gauge FailureRead
TU1 Sensor FailureRead
TU2 Sensor FailureRead
TEa Sensor FailureRead
TEb Sensor FailureRead
TA2 Sensor FailureRead
RD-IO Communication FailureRead
Unbalanced FlowRead
Frost Protection 1Read
Interior Sensor FailureRead
Recuperator FrostRead
Recuperator DefrostingRead
High TariffRead
Insufficient FlowRead
Insufficient Primary HeatingRead
Clogged FilterRead
AI Input IN1 FailureRead
AI Input IN2 FailureRead
AI Input INk1/1 FailureRead
AI Input INk2/1 FailureRead
AI Input INk3/1 FailureRead
AI Input INk4/1 FailureRead
AI Input INk1/2 FailureRead
AI Input INk2/2 FailureRead
AI Input INk3/2 FailureRead
AI Input INk4/2 FailureRead
Unit Not OperationalRead
Missing Configuration FileRead
Insufficient PreheatingRead
Unauthorised Heater CombinationRead
DP3 Pressure Gauge FailureRead
External Pressure Gauge FailureRead
RD5-K/1 Module FailureRead
RD5-K/2 Module FailureRead
CH DefrostingRead
TRk1 Sensor Failure Module 1Read
TRk2 Sensor Failure Module 1Read
TRk3 Sensor Failure Module 1Read
TRk4 Sensor Failure Module 1Read
TRk5 Sensor Failure Module 1Read
TRk1 Sensor Failure Module 2Read
TRk2 Sensor Failure Module 2Read
TRk3 Sensor Failure Module 2Read
TRk4 Sensor Failure Module 2Read
TRk5 Sensor Failure Module 2Read
Update In ProgressRead
Unauthorised Cooling ConfigurationRead
Safe Mode ActiveRead
Capillary Frost ProtectionRead
Frost Protection ConfigurationRead
Incomplete Learning UnitsRead
T-ODA Sensor FailureRead
T-ETA/T-IDA Sensor FailureRead
Cooling Not AvailableRead
Heating Not AvailableRead
Evaporation ActiveRead
Increased Performance During FloodingRead
Unauthorised Flow SettingsRead
Filter Change IntervalRead
Filter Test ConfigurationRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show supply, outdoor and indoor air temperature of every ventilation unit on one dashboard.
  • Send an email when the Clogged Filter warning or any alarm becomes active.
  • Track supply and exhaust air flow over time to spot unbalanced ventilation.
  • Lower the required performance of a school ventilation unit outside opening hours with a scheduled automation.
  • Switch the desired mode or required temperature remotely without visiting the site.

Installation

  1. Connect the Ethernet port of the RD5 control to the network of the ModbusCloud Gateway, or directly to its LAN port.

  2. In the service settings of the unit, set 3.15.1 Modbus TCP to on. Modbus is off at the factory.

  3. In ModbusCloud, add a Modbus TCP device with the IP address of the unit, port 502 and unit ID 1, and import the Atrea DUPLEX RD5 template.

  4. Check that Outdoor Air Temperature and Supply Air Temperature show plausible values.

  5. For control from ModbusCloud, set the control source registers to manual (0) so the weekly program does not overwrite your values.

Things to watch for

The unit does not answer on port 502. What should I check?

Modbus TCP is off at the factory; enable 3.15.1 Modbus TCP in the service settings. Check that the IP address of the unit is reachable from the network of the ModbusCloud Gateway and that no firewall blocks port 502. The unit answers on any unit ID except 0.

Some readings fail or come back late.

The RD5 control needs at least 5 seconds between batches of requests. Keep the reading interval at its default or longer, and avoid reading the unit from several systems at the same time.

Why does a written mode or temperature not stay?

If the unit follows its weekly program, the program overwrites manual values. Set the matching control source register to 0 (manual), or write 2 after the new value for a temporary change. Some modes also need equipment such as a circulation damper.

What should I watch out for when writing to the unit?

Write only the control values: performance, mode, temperature, zone and season. The configuration registers for fan control, orientation, heater and cooler must not be changed. Outdoor or indoor temperatures sent from another system must be refreshed within 90 seconds, otherwise the unit reports a sensor fault.

More TCP templates