Danfoss Danfoss Optyma iCO2 Gateway Modbus RTU template

Danfoss Optyma iCO2 Gateway

CO2 condensing unit gateway: pressures, temperatures, valve openings and alarms.

The Danfoss Optyma iCO2 is a CO2 condensing unit for cold rooms and display cases, and its gateway makes the unit readable over Modbus RTU. This template reads pressures, temperatures, valve openings, fan speed, compressor capacity and alarms, and lets you write the main switch and suction setpoint from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
58, read and write
Brand
Danfoss
Key readings
High pressure · Receiver pressure · Suction pressure · Gas cooler outlet temperature · Discharge temperature · Compressor capacity · Alarms
Available commands
Main switch · Suction setpoint · Night offset · Day and night times
Compatible models
OP-MPAM005 · OP-MPAM015 · Danfoss Optyma iCO2 CO2 condensing units 4.6 kW MT and 20 kW MT / 10 kW LT with the iCO2 gateway, SW 1.0x
Last updated

Registers (58)

58 read, 7 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Main SwitchRead and write
Night ConditionRead
Operation ConditionRead
Suction Setpoint Ts Ref°CRead and write
Reference°CRead
Night OffsetKRead and write
Fan Speed%Read
Day Start HourhRead and write
Night Start HourhRead and write
Clock HourshRead and write
Clock MinutesminRead and write
CDU Software VersionRead
High Pressure PcbarRead
DI1 StatusRead
SuperheatKRead
DI2 StatusRead
Compressor Capacity%Read
Alarm RelayRead
Gas Cooler Outlet Temperature°CRead
Receiver Outlet Temperature°CRead
Receiver PressurebarRead
Receiver Temperature Trec°CRead
Condensing Temperature Tc°CRead
Suction Pressure PobarRead
Evaporating Temperature To°CRead
Ambient Temperature°CRead
Discharge Temperature°CRead
Suction Temperature°CRead
Dynamic LP Off°CRead
Dynamic LP On°CRead
Gateway Firmware VersionRead
Gateway Firmware Version (Danfoss format)Read
High Pressure Valve Opening%Read
Receiver Pressure Valve Opening%Read
Summary AlarmRead
Control StateRead
Gas Cooler Out Sensor ErrorRead
Ambient Sensor ErrorRead
Discharge Sensor ErrorRead
Suction Temperature Sensor ErrorRead
Suction Pressure Sensor ErrorRead
Receiver Out Sensor ErrorRead
Receiver Pressure Sensor ErrorRead
Low Pressure AlarmRead
High Pressure AlarmRead
Gas Cooler Fan AlarmRead
Standby Mode AlarmRead
Gas Cooler Pressure Sensor ErrorRead
High Receiver Pressure AlarmRead
Max Discharge Temperature AlarmRead
Safety AlarmRead
Drive Alarm H23Read
Drive Alarm H24Read
Drive Alarm H25Read
Drive Alarm H26Read
Drive Alarm H28Read
Drive Alarm H29Read
MMILDS Communication ErrorRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show high pressure, receiver pressure and gas cooler outlet temperature of every CO2 unit on one dashboard.
  • Get an email when the high pressure, high receiver pressure or max discharge temperature alarm turns on.
  • Follow the high pressure valve opening and fan speed through a hot summer to see when the gas cooler reaches its limit.
  • Switch a unit to standby with the main switch during maintenance on the cold room.
  • Adjust the suction setpoint or night offset from ModbusCloud when the cold room use changes.

Installation

  1. Wire the RS485 terminals of the iCO2 gateway to the RS485 port of the ModbusCloud Gateway, with a 120 ohm resistor at both ends of the bus.

  2. Set a unique slave address with parameter o03 on the MMILDS display and set the bus to 19200 baud, 8 data bits, even parity, 1 stop bit.

  3. In ModbusCloud, add a Modbus device (RTU) with that address and import this template.

  4. Check that high pressure, suction pressure and ambient temperature show plausible values.

  5. Set alarm rules on the alarm registers you want to be told about, such as high pressure and high receiver pressure.

Things to watch for

The gateway does not answer on the bus. What should I check?

Use even parity and 1 stop bit, and check the address set with o03 on the MMILDS display. The gateway switches between 19200 and 38400 baud by itself. Swap A and B if it still does not answer.

Why do pressures and temperatures look ten times too high?

Values with one decimal are sent multiplied by 10, so 127 means 12.7. The template applies that scale. Fan speed, compressor capacity and valve openings are whole percentages.

How do I get notified of a unit fault?

Each alarm, such as high pressure, low pressure, high receiver pressure, gas cooler fan or a sensor error, has its own register that reads 1 while active. The summary alarm reads 1 when any alarm is present. Put an alarm rule on the ones that matter.

Is it safe to write the main switch and suction setpoint?

Main switch 0 puts the unit in standby, so write it only when you mean to stop refrigeration; 2 starts vacuum mode for service. Keep the suction setpoint within -20 to 10 °C and agree changes with whoever is responsible for the cold room.