Danfoss Danfoss VLT AQUA Drive FC 202 Option Modules Modbus RTU template

Danfoss VLT AQUA Drive FC 202 Option Modules

Option card parameters of the VLT AQUA Drive FC 202, as an addition to the drive template.

The Danfoss VLT AQUA Drive FC 202 takes option cards for fieldbus, extra I/O, cascade control of several pumps, a bypass and temperature sensors. This Modbus RTU template holds the parameters of those cards, so you can read their status and change their settings from ModbusCloud next to the drive template.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
308, read and write
Brand
Danfoss
Key readings
Cascade pump status · Cascade reference and capacity · Bypass status and running hours · Fieldbus warning and error counters · Ethernet link status
Available commands
Cascade controller settings · Staging and destaging limits · Extra analog and digital I/O · Temperature input limits · Fieldbus settings
Compatible models
VLT AQUA Drive FC 202
Last updated

Registers (308)

308 read, 229 write

NameUnitAccessAddress (Hidden until you confirm your email)Function (hidden)Type (hidden)
SetpointRead
Actual ValueRead
PCD Write ConfigurationRead and write
PCD Read ConfigurationRead and write
Node AddressRead and write
Drive Unit System NumberRead and write
Telegram SelectionRead and write
Parameters for SignalsRead
Parameter EditRead and write
Process ControlRead and write
Safe AddressRead and write
Fault Message CounterRead
Fault CodeRead
Fault NumberRead
Fault Situation CounterRead and write
PROFIBUS Warning WordRead
Actual Baud RateRead
Device IdentificationRead
Profile NumberRead
Control Word 1Read
Status Word 1Read
Programming Set-upRead and write
PROFIBUS Save Data ValueRead and write
PROFIBUSDriveResetRead and write
Defined Parameters (1)Read
Defined Parameters (2)Read
Defined Parameters (3)Read
Defined Parameters (4)Read
Defined Parameters (5)Read
Defined Parameters (6)Read
Changed Parameters (1)Read
Changed Parameters (2)Read
Changed Parameters (4)Read
Changed Parameters (5)Read
PROFIBUS Revision CounterRead
CAN ProtocolRead and write
Baud Rate SelectRead and write
MAC IDRead and write
Readout Transmit Error CounterRead
Readout Receive Error CounterRead
Readout Bus Off CounterRead
Process Data Type SelectionRead and write
Process Data Config Write 10-11Read and write
Process Data Config Read 10-12Read and write
Warning ParameterRead
Net Reference 10-14Read and write
Net Control 10-15Read and write
COS Filter 1Read and write
COS Filter 2Read and write
COS Filter 3Read and write
COS Filter 4Read and write
Array IndexRead and write
Store Data ValueRead and write
Devicenet RevisionRead
DeviceNet Product CodeRead and write
Devicenet F ParametersRead
IP AddressRead and write
Subnet MaskRead and write
Default GatewayRead and write
DHCP ServerRead and write
Lease ExpiresRead
Name ServersRead and write
Domain NameRead and write
Physical AddressRead and write
Link StatusRead
Link DurationRead
Auto NegotiationRead and write
Link SpeedRead and write
Link DuplexRead and write
Supervisor MACRead and write
Supervisor IP Addr.Read and write
Control InstanceRead and write
Process Data Config Write 12-21Read and write
Process Data Config Read 12-22Read and write
Primary MasterRead and write
Store Data ValuesRead and write
Store AlwaysRead and write
Net Reference 12-31Read and write
Net Control 12-32Read and write
CIP RevisionRead
CIP Product CodeRead and write
EDS ParameterRead
COS Inhibit TimerRead and write
COS FilterRead and write
Status ParameterRead
Slave Message CountRead
Slave Exception Message CountRead
Ethernet Extended StatusRead and write
BACnet StatusRead
BACnet DatalinkRead and write
BACnet UDP PortRead and write
BBMD IP AddressRead and write
BBMD PortRead and write
BBMD Reg. IntervalsRead and write
Device ID Conflict DetectionminRead and write
Message CounterRead
FTP ServerRead and write
HTTP ServerRead and write
SMTP ServiceRead and write
SNMP AgentRead and write
Address Conflict DetectionRead and write
ACD Last ConflictRead and write
NTP Host ServerRead and write
SNTP Time SyncminRead and write
Transparent Socket Channel PortRead and write
Cable DiagnosticsRead and write
MDI-XRead and write
IGMP SnoopingRead and write
Cable Error LengthRead and write
Port ConfigRead and write
QoS PriorityRead and write
Interface CountersRead
Media CountersRead
Terminal X42/1 ModeRead and write
Terminal X42/3 ModeRead and write
Terminal X42/5 ModeRead and write
Terminal X42/1 Low VoltageVRead and write
Terminal X42/1 High VoltageVRead and write
Term. X42/1 Low Ref./Feedb. ValueRead and write
Term. X42/1 High Ref./Feedb. ValueRead and write
Term. X42/1 Filter Time ConstantsRead and write
Term. X42/1 Live ZeroRead and write
Terminal X42/3 Low VoltageVRead and write
Terminal X42/3 High VoltageVRead and write
Term. X42/3 Low Ref./Feedb. ValueRead and write
Term. X42/3 High Ref./Feedb. ValueRead and write
Term. X42/3 Filter Time ConstantsRead and write
Term. X42/3 Live ZeroRead and write
Terminal X42/5 Low VoltageVRead and write
Terminal X42/5 High VoltageVRead and write
Term. X42/5 Low Ref./Feedb. ValueRead and write
Term. X42/5 High Ref./Feedb. ValueRead and write
Term. X42/5 Filter Time ConstantsRead and write
Term. X42/5 Live ZeroRead and write
Terminal X42/7 OutputRead and write
Terminal X42/7 Min. Scale%Read and write
Terminal X42/7 Max. Scale%Read and write
Terminal X42/7 Bus Control%Read and write
Terminal X42/7 Timeout Preset%Read and write
Terminal X42/9 OutputRead and write
Terminal X42/9 Min. Scale%Read and write
Terminal X42/9 Max. Scale%Read and write
Terminal X42/9 Bus Control%Read and write
Terminal X42/9 Timeout Preset%Read and write
Terminal X42/11 OutputRead and write
Terminal X42/11 Min. Scale%Read and write
Terminal X42/11 Max. Scale%Read and write
Terminal X42/11 Bus Control%Read and write
Terminal X42/11 Timeout Preset%Read and write
Pump StatusRead
Manual Pump ControlRead and write
Current Runtime HourshRead
Pump Total Lifetime HourshRead and write
Cascade ControllerRead and write
Number of DrivesRead and write
Number of PumpsRead and write
Max Number of Pumps RunningRead and write
Pump CapacityRead and write
Runtime BalancingRead and write
Motor StartersRead and write
Spin Time for Unused PumpsRead and write
Reset Current Runtime HoursRead and write
Normal Operating Range%Read and write
Override Limit%Read and write
Staging DelaysRead and write
Destaging DelaysRead and write
Override Hold TimesRead and write
Min Speed Destage DelayRead and write
Auto Tune Staging SpeedsRead and write
Stage On Speed [RPM]rpmRead and write
Stage On Speed [Hz]HzRead and write
Stage Off Speed [RPM]rpmRead and write
Stage Off Speed [Hz]HzRead and write
Auto Tune Staging SettingsRead and write
Ramp Down DelaysRead and write
Ramp Up DelaysRead and write
Staging Threshold%Read and write
Destaging Threshold%Read and write
Staging Speed [RPM]rpmRead
Staging Speed [Hz]HzRead
Destaging Speed [RPM]rpmRead
Destaging Speed [Hz]HzRead
Staging PrincipleRead and write
Automatic AlternationRead and write
Alternation EventRead and write
Alternation Time IntervalminRead and write
Alternation Time ValueminRead
Alternation At Time of DayRead and write
Alternation Predefined TimeRead and write
Alternate Capacity is <%Read and write
Run Next Pump DelaysRead and write
Terminal X66/1 Digital InputRead and write
Terminal X66/3 Digital InputRead and write
Terminal X66/5 Digital InputRead and write
Terminal X66/7 Digital InputRead and write
Terminal X66/9 Digital InputRead and write
Terminal X66/11 Digital InputRead and write
Terminal X66/13 Digital InputRead and write
RelayRead and write
MultiMaster Primary RestoreRead and write
Master SetupRead and write
Cascade Reference%Read
% Of Total Capacity%Read
Cascade Option StatusRead
Cascade System StatusRead
Advanced Cascade Relay Output [bin]Read
Extended Cascade Relay Output [bin]Read
Bypass ModeRead and write
Bypass Start Time DelaysRead and write
Bypass Trip Time DelaysRead and write
Test Mode ActivationRead and write
Bypass Status WordRead
Bypass Running HourshRead
Remote Bypass ActivationRead and write
PCD 1 Write to MCORead
PCD 2 Write to MCORead
PCD 3 Write to MCORead
PCD 4 Write to MCORead
PCD 5 Write to MCORead
PCD 6 Write to MCORead
PCD 7 Write to MCORead
PCD 8 Write to MCORead
PCD 9 Write to MCORead
PCD 10 Write to MCORead
PCD 1 Read from MCORead
PCD 2 Read from MCORead
PCD 3 Read from MCORead
PCD 4 Read from MCORead
PCD 5 Read from MCORead
PCD 6 Read from MCORead
PCD 7 Read from MCORead
PCD 8 Read from MCORead
PCD 9 Read from MCORead
PCD 10 Read from MCORead
Term. X48/4 Temperature UnitRead and write
Term. X48/4 Input TypeRead
Term. X48/7 Temperature UnitRead and write
Term. X48/7 Input TypeRead
Term. X48/10 Temperature UnitRead and write
Term. X48/10 Input TypeRead
Temperature Sensor Alarm FunctionRead and write
Term. X48/4 Filter Time ConstantsRead and write
Term. X48/4 Temp. MonitorRead and write
Term. X48/4 Low Temp. LimitRead and write
Term. X48/4 High Temp. LimitRead and write
Term. X48/7 Filter Time ConstantsRead and write
Term. X48/7 Temp. MonitorRead and write
Term. X48/7 Low Temp. LimitRead and write
Term. X48/7 High Temp. LimitRead and write
Term. X48/10 Filter Time ConstantsRead and write
Term. X48/10 Temp. MonitorRead and write
Term. X48/10 Low Temp. LimitRead and write
Term. X48/10 High Temp. LimitRead and write
Term. X48/2 Low CurrentmARead and write
Term. X48/2 High CurrentmARead and write
Term. 48/2 Low Ref./Feedb. ValueRead and write
Term. 48/2 High Ref./Feedb. ValueRead and write
Term. X48/2 Filter Time ConstantsRead and write
Term. X48/2 Live ZeroRead and write
Term. X49/1 ModeRead and write
Term. X49/3 ModeRead and write
Term. X49/5 ModeRead and write
Term. X49/7 ModeRead and write
Term. X49/9 ModeRead and write
Term. X49/11 ModeRead and write
Terminal X49/1 Low VoltageVRead and write
Terminal X49/1 Low CurrentmARead and write
Terminal X49/1 High VoltageVRead and write
Terminal X49/1 High CurrentmARead and write
Terminal X49/1 Low Ref./Feedb. ValueRead and write
Terminal X49/1 High Ref./Feedb. ValueRead and write
Term. X49/1 Filter Time ConstantsRead and write
Term. X49/1 Live ZeroRead and write
Terminal X49/3 Low VoltageVRead and write
Terminal X49/3 Low Current 36-21mARead and write
Terminal X49/3 High VoltageVRead and write
Terminal X49/3 High CurrentmARead and write
Terminal X49/3 Low Ref./Feedb. ValueRead and write
Terminal X49/3 High Ref./Feedb. ValueRead and write
Term. X49/3 Filter Time ConstantsRead and write
Term. X49/3 Live ZeroRead and write
Terminal X49/5 Low VoltageVRead and write
Terminal X49/3 Low Current 36-31mARead and write
Terminal X49/5 High VoltageVRead and write
Terminal X49/5 High CurrentmARead and write
Terminal X49/5 Low Ref./Feedb. ValueRead and write
Terminal X49/5 High Ref./Feedb. ValueRead and write
Term. X49/5 Filter Time ConstantsRead and write
Term. X49/5 Live ZeroRead and write
Terminal X49/7 Analogue OutputRead and write
Terminal X49/7 Digital OutputRead and write
Terminal X49/7 Min Scale%Read and write
Terminal X49/7 Max. Scale%Read and write
Terminal X49/7 Bus Ctrl%Read and write
Terminal X49/7 Timeout Preset%Read and write
Terminal X49/9 Analogue OutputRead and write
Terminal X49/9 Digital OutputRead and write
Terminal X49/9 Min. Scale%Read and write
Terminal X49/9 Max. Scale%Read and write
Terminal X49/9 Bus Ctrl%Read and write
Terminal X49/9 Timeout Preset%Read and write
Terminal X49/11 Analogue OutputRead and write
Terminal X49/11 Digital OutputRead and write
Terminal X49/11 Min. Scale%Read and write
Terminal X49/11 Max. Scale%Read and write
Terminal X49/11 Bus Ctrl%Read and write
Terminal X49/11 Timeout Preset%Read and write
Parameter Array IndexRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show which pumps of a cascade station are running and the share of total capacity on a dashboard.
  • Send an email when the bypass status word changes, so you know the drive was bypassed.
  • Keep a history of the extra temperature inputs of the sensor option card.
  • Change staging and destaging limits of a cascade controller from the portal.

Installation

  1. Add the Danfoss VLT AQUA Drive FC 202 template as described there; this template uses the same RS485 connection, address and settings.

  2. In ModbusCloud, add a second Modbus RTU device with the same address on the Gateway and import this template.

  3. Delete the registers of option cards that are not fitted in your drive.

  4. Check that the values of your option cards look plausible.

Things to watch for

Most registers return an error or 0.

These parameters only exist when the matching option card is fitted in the drive. Keep the registers of the cards you have and delete the rest from the device in ModbusCloud.

How do I find the register of a Danfoss parameter?

The register number is the parameter number times ten, so parameter 27-91 is register 27910 and address 27909 in the template. The parameter number is in the comment of each register.

Some array parameters always show the first value.

For array parameters the drive returns the element chosen in Parameter Array Index. Write the index you want there first, then read the array parameter.