Danfoss AK-RC 305W-SD
Cold room controller for walk-in coolers and freezers: temperatures, relays, defrost and alarms.
The Danfoss AK-RC 305W-SD is a temperature controller in a wall box that runs the compressor, defrost, evaporator fans and light of a walk-in cooler or freezer. This Modbus RTU template reads probe temperatures, relay states and alarms, and lets you write the setpoint, start a defrost and switch standby and light from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 112, read and write
- Brand
- Danfoss
- Key readings
- Room temperature S1 · Evaporator temperature S2 · Effective setpoint · Cooling relay · Defrost state · Alarms
- Available commands
- Setpoint · Defrost start and stop · Standby · Light · Alarm limits
- Compatible models
- AK-RC 305W-SD (080Z5003)
- Last updated
Registers (112)
112 read, 76 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Probe S1 Temperature | °C | Read | |||
| Probe S2 Temperature | °C | Read | |||
| Probe S3 Temperature | °C | Read | |||
| Effective Setpoint | °C | Read | |||
| Cooling Relay State | Read | ||||
| Defrost Relay State | Read | ||||
| Fan Relay State | Read | ||||
| Defrost State | Read | ||||
| Standby State | Read | ||||
| Digital Input 1 State | Read | ||||
| Digital Input 2 State | Read | ||||
| Light State | Read | ||||
| AUX1 Remote State | Read | ||||
| AUX2 Remote State | Read | ||||
| Setpoint Change State | Read | ||||
| Continuous Cycle State | Read | ||||
| Mute State | Read | ||||
| Alarm Max S1 | Read | ||||
| Alarm Min S1 | Read | ||||
| Alarm Door Open | Read | ||||
| Alarm External | Read | ||||
| Alarm Severe External | Read | ||||
| Probe S1 Error | Read | ||||
| Probe S2 Error | Read | ||||
| Probe S3 Error | Read | ||||
| Alarm Moisture S2 | Read | ||||
| Alarm Moisture S3 | Read | ||||
| Alarm HACCP | Read | ||||
| Alert Defrost Time | Read | ||||
| Alert Pump Down Pd | Read | ||||
| Alert Pump Down LP | Read | ||||
| Alert Power Fail HACCP | Read | ||||
| Alert HACCP | Read | ||||
| Alarm SD 16 | Read | ||||
| Switch Standby | Read and write | ||||
| Switch Setpoint Change | Read and write | ||||
| Switch Continuous Cycle | Read and write | ||||
| Switch Light | Read and write | ||||
| Turn On Mute | Read and write | ||||
| Switch AUX1 | Read and write | ||||
| Switch AUX2 | Read and write | ||||
| Turn On Defrost | Read and write | ||||
| Turn Off Defrost | Read and write | ||||
| Setpoint | °C | Read and write | |||
| Regulation Mode | Read and write | ||||
| Probe 1 Calibration | K | Read and write | |||
| Probe 1 Differential | K | Read and write | |||
| Setpoint Upper Limit | °C | Read and write | |||
| Setpoint Lower Limit | °C | Read and write | |||
| Delay Type | Read and write | ||||
| Delay Time | Read and write | ||||
| Cooling On Probe Failure | Read and write | ||||
| Cooling Time On On Failure | Read and write | ||||
| Cooling Time Off On Failure | Read and write | ||||
| Max Duration Continuous Cycle | Read and write | ||||
| Setpoint Variation Continuous Cycle | K | Read and write | |||
| Setpoint Variation | K | Read and write | |||
| Max Time On Pump Down | Read and write | ||||
| Max Time Pump Down | Read and write | ||||
| Probe Displayed | Read and write | ||||
| Stop Fan With Cooling | Read and write | ||||
| Fan On Delay | Read and write | ||||
| Fan Stop Delay | Read and write | ||||
| S1 S3 Balance | Read and write | ||||
| S3 Calibration | K | Read and write | |||
| Defrost Frequency | Read and write | ||||
| Defrost Duration | Read and write | ||||
| Defrost Message | Read and write | ||||
| Defrost Message Duration | Read and write | ||||
| End Defrost Temperature | °C | Read and write | |||
| Defrost At Start Up | Read and write | ||||
| Start Up Defrost Delay | Read and write | ||||
| Defrost Type | Read and write | ||||
| Time Between Defrosts Mode | Read and write | ||||
| Drip Time | Read and write | ||||
| Fan Stop Temperature | °C | Read and write | |||
| Probe 2 Differential | K | Read and write | |||
| Stop Fan With Compressor | Read and write | ||||
| Fans During Defrost | Read and write | ||||
| Fan Delay After Defrost | Read and write | ||||
| Fan Stop Evaporator Temperature | °C | Read and write | |||
| Fan On Cycle | Read and write | ||||
| Fan Off Cycle | Read and write | ||||
| Alarm Setup | Read and write | ||||
| Max Alarm S1 | °C | Read and write | |||
| Min Alarm S1 | °C | Read and write | |||
| Alarm Start Up Delay | Read and write | ||||
| Alarm Delay After Defrost | Read and write | ||||
| Temperature Alarm Delay | Read and write | ||||
| External Alarm Delay | Read and write | ||||
| External Alarm Off Delay | Read and write | ||||
| Defrost Warning | Read and write | ||||
| Alarm Relay Polarity | Read and write | ||||
| Alarm Differential | K | Read and write | |||
| Open Door Alarm Delay | Read and write | ||||
| Start Up Delay | Read and write | ||||
| Light Time | Read and write | ||||
| Password Function | Read and write | ||||
| Password | Read and write | ||||
| Acoustic Alarm | Read and write | ||||
| Work Units | Read and write | ||||
| Connected Probes | Read and write | ||||
| Digital Input 1 Setup | Read and write | ||||
| Digital Input 1 Polarity | Read and write | ||||
| Digital Input 2 Setup | Read and write | ||||
| Digital Input 2 Polarity | Read and write | ||||
| AUX1 Setup | Read and write | ||||
| AUX2 Setup | Read and write | ||||
| HACCP Temperature | °C | Read and write | |||
| HACCP Delay | Read and write | ||||
| Start Wizard | Read | ||||
| Pump Down | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show room temperature, evaporator temperature and relay states of every cold room on one dashboard.
- Get an email when the high or low temperature alarm, door alarm or a probe error turns on.
- Keep a year of cold room temperature history as a record for food safety checks.
- Start a manual defrost from ModbusCloud when the evaporator ices up.
- Raise or lower the setpoint remotely when the room changes from cooler to freezer use.
Installation
Wire the RS485 terminals of the AK-RC 305W-SD to the RS485 port of the ModbusCloud Gateway, with a 120 ohm resistor at both ends of the bus.
Check the address and serial settings of the controller; this template assumes 19200 baud, 8E1 and address 1.
In ModbusCloud, add a Modbus device (RTU) with those settings and import this template.
Check that probe S1 shows the room temperature and that the cooling relay state follows the display.
Add alarm rules on the alarm registers you want to follow, such as max and min alarm S1 and door open.
Things to watch for
The controller does not answer on the bus. What should I check?
The serial settings are not in the Modbus list, so check them on the controller first. Try 19200 baud, even parity, 1 stop bit and address 1. Swap A and B if nothing answers, and make sure the bus has a 120 ohm termination at both ends.
Why does a probe show -327.67?
That is the raw value -32767, which the controller sends when a probe has no valid reading. Check the probe and its wiring; the matching probe error register will be on as well.
Why are temperatures a hundred times too high?
Temperatures are sent in hundredths of a degree, so 450 means 4.50. The template applies that scale. If the controller is set to Fahrenheit, the values are in °F.
How do I start a defrost or change the setpoint safely?
Write 1 to Turn On Defrost to start one and to Turn Off Defrost to end it; Defrost State shows the result. Write the setpoint in degrees within the upper and lower setpoint limits. Agree remote changes with whoever is responsible for the cold room.