Danfoss Danfoss Optyma Plus Modbus RTU template

Danfoss Optyma Plus

Condensing unit controller for commercial refrigeration: pressures, temperatures, fan speed and alarms.

The Danfoss Optyma Plus is an air cooled condensing unit with its own controller that runs the compressor and condenser fan for cold rooms and display cases. This Modbus RTU template reads pressures, temperatures, superheat, fan speed, compressor capacity and alarms, and lets you write the main switch and suction setpoint from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
42, read and write
Brand
Danfoss
Key readings
Suction pressure · Condenser pressure · Discharge temperature · Superheat · Fan speed · Compressor capacity · Alarms
Available commands
Main switch · Suction setpoint · Night offset · Day and night times
Compatible models
Optyma Plus Controller 084B8080 · Optyma Plus Controller 084B8180 · Danfoss Optyma Plus condensing units with the Optyma Plus controller, SW 3.10 to 3.7x
Last updated

Registers (42)

42 read, 7 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
SuperheatKRead
Suction Pressure PsbarRead
Suction Temperature Ts°CRead
Suction Temperature S4°CRead
Discharge Temperature S3°CRead
Ambient Temperature S2°CRead
Condenser Pressure PcbarRead
Condensing Temperature Tc°CRead
Tc Reference°CRead
Compressor Capacity%Read
Fan Speed%Read
Auxiliary Temperature S5°CRead
Auxiliary Temperature S6°CRead
DI1 StatusRead
Night ConditionRead
DI2 StatusRead
DI3 StatusRead
Control StateRead
Controller ErrorRead
Internal Controller ErrorRead
Pc Sensor ErrorRead
Ps Sensor ErrorRead
Ambient Sensor ErrorRead
Discharge Sensor ErrorRead
Suction Sensor ErrorRead
Auxiliary Sensor ErrorRead
Low Suction Pressure AlarmRead
Refrigerant Not SelectedRead
Max Discharge Temperature AlarmRead
DI2 AlarmRead
High Pressure AlarmRead
Safety Input AlarmRead
Standby ModeRead
Condenser Air Flow BlockedRead
Drive AlarmRead
Main SwitchRead and write
Night OffsetKRead and write
Ts Reference°CRead and write
Day StarthRead and write
Night StarthRead and write
Clock HourshRead and write
Clock MinutesminRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show suction pressure, condensing temperature and discharge temperature of every condensing unit on one dashboard.
  • Get an email when the high pressure, low suction pressure or max discharge temperature alarm turns on.
  • Watch fan speed and compressor capacity over a year to spot fouled condensers before summer.
  • Switch a unit off remotely with the main switch during maintenance on the cold room.
  • Adjust the suction setpoint or night offset from ModbusCloud when the cold room use changes.

Installation

  1. Wire the RS485 terminals of the Optyma Plus controller to the RS485 port of the ModbusCloud Gateway, with a 120 ohm resistor at both ends of the bus.

  2. Give the controller a unique Modbus address and keep the bus at 19200 baud, 8 data bits, even parity, 1 stop bit.

  3. In ModbusCloud, add a Modbus device (RTU) with that address and import this template.

  4. Check that suction pressure, condenser pressure and ambient temperature show plausible values.

  5. Set alarm rules on the alarm registers you want to be told about, such as high pressure and max discharge temperature.

Things to watch for

The controller does not answer on the bus. What should I check?

Use even parity and 1 stop bit, and check the address set on the controller. The controller detects 9600, 19200 or 38400 baud by itself, but only after a few requests at the new speed, so give it a moment after changing the master. Swap A and B if it still does not answer.

Why do pressures and temperatures look ten times too high?

Most readings are sent as whole numbers in tenths, so 52 means 5.2. The template applies that scale. The suction setpoint and the setting registers are whole numbers without a decimal.

How do I get notified of a unit fault?

Each alarm, such as high pressure, low suction pressure, max discharge temperature or a sensor error, has its own register that reads 1 while the alarm is active. Put an alarm rule on the ones that matter, for example equal to 1.

Is it safe to write the main switch and suction setpoint?

Main switch 0 stops the unit and -1 puts it in service mode, so write it only when you mean to stop refrigeration. Keep the suction setpoint within -30 to 10 and agree changes with whoever is responsible for the cold room.