Danfoss Danfoss VLT AutomationDrive FC 302 Option Modules Modbus RTU template

Danfoss VLT AutomationDrive FC 302 Option Modules

Motion control, option, safety and condition monitoring parameters of the FC 302, as an addition to the drive template.

The Danfoss VLT AutomationDrive FC 302 has parameter groups for the MCO motion controller, option cards, safety functions and condition based monitoring. This Modbus RTU template holds groups 32 to 49, so you can read their status and change their settings from ModbusCloud next to the drive template, which covers groups 0 to 31.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
589, read and write
Brand
Danfoss
Key readings
MCO process data · Safety function status · Unit readouts and logs · Condition monitoring status · Sensor option temperatures
Available commands
Encoder and positioning settings · Synchronisation settings · Condition monitoring limits · Option analog and digital I/O · Temperature input limits
Compatible models
FC 302 · FC 301 (same parameter numbering, fewer parameters)
Last updated

Registers (589)

589 read, 357 write

NameUnitAccessAddress (Hidden until you confirm your email)Function (hidden)Type (hidden)
Incremental Signal Type 32-00Read and write
Incremental Resolution 32-01Read and write
Absolute Protocol 32-02Read and write
Absolute Resolution 32-03Read and write
Absolute Encoder Baudrate X55Read and write
Absolute Encoder Data Length 32-05Read and write
Absolute Encoder Clock Frequency 32-06HzRead and write
Absolute Encoder Clock Generation 32-07Read and write
Absolute Encoder Cable Length 32-08Read and write
Encoder Monitoring 32-09Read and write
Rotational DirectionRead and write
User Unit DenominatorRead and write
User Units NumeratorRead and write
Enc.2 ControlRead and write
Enc.2 Node IDRead and write
Enc.2 CAN GuardRead and write
Incremental Signal Type 32-30Read and write
Incremental Resolution 32-31Read and write
Absolute Protocol 32-32Read and write
Absolute Resolution 32-33Read and write
Absolute Encoder Data Length 32-35Read and write
Absolute Encoder Clock Frequency 32-36HzRead and write
Absolute Encoder Clock Generation 32-37Read and write
Absolute Encoder Cable Length 32-38Read and write
Encoder Monitoring 32-39Read and write
Encoder TerminationRead and write
Enc.1 ControlRead and write
Enc.1 Node IDRead and write
Enc.1 CAN GuardRead and write
Source SlaveRead and write
MCO 302 Last WillRead and write
Source MasterRead and write
Proportional FactorRead and write
Derivative FactorRead and write
Integral FactorRead and write
Limit Value for Integral SumRead and write
PID BandwidthRead and write
Velocity Feed-ForwardRead and write
Acceleration Feed-ForwardRead and write
Max. Tolerated Position ErrorRead and write
Reverse Behavior for SlaveRead and write
Sampling Time for PID ControlmsRead and write
Scan Time for Profile GeneratormsRead and write
Size of the Control Window (Activation)Read and write
Size of the Control Window (Deactiv.)Read and write
Integral Limit Filter TimemsRead and write
Position Error Filter TimemsRead and write
Maximum Velocity (Encoder)rpmRead and write
Shortest RampsRead and write
Ramp TypeRead and write
Velocity ResolutionRead and write
Default VelocityRead and write
Default AccelerationRead and write
Acc. Up for Limited JerkmsRead and write
Acc. Down for Limited JerkmsRead and write
Dec. Up for Limited JerkmsRead and write
Dec. Down for Limited JerkmsRead and write
Force HOMERead and write
Zero Point Offset from Home Pos.Read and write
Ramp for Home MotionRead and write
Velocity for Home MotionRead and write
Behavior During HomeMotionRead and write
Sync Factor MasterRead and write
Sync Factor SlaveRead and write
Position Offset for SynchronizationRead and write
Accuracy Window for Position Sync.Read and write
Marker Number for MasterRead and write
Marker Number for SlaveRead and write
Master Marker DistanceRead and write
Slave Marker DistanceRead and write
Master Marker TypeRead and write
Slave Marker TypeRead and write
Master Marker Tolerance WindowRead and write
Slave Marker Tolerance WindowRead and write
Start Behavior for Marker SyncRead and write
Marker Number for FaultRead and write
Marker Number for ReadyRead and write
Velocity FilterRead and write
Offset Filter TimemsRead and write
Marker Filter ConfigurationRead and write
Filter Time for Marker FiltermsRead and write
Maximum Marker CorrectionRead and write
Synchronization TypeRead and write
Feed Forward Velocity AdaptationRead and write
Velocity Filter WindowRead and write
Slave Marker Filter TimemsRead and write
Behavior atEnd Limit SwitchRead and write
Negative Software End LimitRead and write
Positive Software End LimitRead and write
Negative Software End Limit ActiveRead and write
Positive Software End Limit ActiveRead and write
Time in Target WindowmsRead and write
Target Window LimitValueRead and write
Size of Target WindowRead and write
Terminal X57/2 Digital InputRead and write
Terminal X57/3 Digital InputRead and write
Terminal X57/4 Digital InputRead and write
Terminal X57/5 Digital InputRead and write
Terminal X57/6 Digital InputRead and write
Terminal X57/7 Digital InputRead and write
Terminal X57/8 Digital InputRead and write
Terminal X57/9 Digital InputRead and write
Terminal X57/10 Digital InputRead and write
Terminal X59/1 and X59/2 ModeRead and write
Terminal X59/1 Digital InputRead and write
Terminal X59/2 Digital InputRead and write
Terminal X59/1 Digital OutputRead and write
Terminal X59/3 Digital OutputRead and write
Terminal X59/4 Digital OutputRead and write
Terminal X59/5 Digital OutputRead and write
Terminal X59/6 Digital OutputRead and write
Terminal X59/7 Digital OutputRead and write
Terminal X59/8 Digital OutputRead and write
Activated Program NumberRead and write
Power-up StateRead and write
Drive Status MonitoringRead and write
Behavior afterErrorRead and write
Behavior afterEsc.Read and write
MCO Supplied by External 24VDCRead and write
Terminal at AlarmRead and write
Terminal State at AlarmRead and write
Status Word at AlarmRead and write
X62 MCO CAN node IDRead and write
X62 MCO CAN Baud RateRead and write
X60 MCO RS485 Serial TerminationRead and write
X60 MCO RS485 Serial Baud RateRead and write
PCD 1 Write to MCORead
PCD 2 Write to MCORead
PCD 3 Write to MCORead
PCD 4 Write to MCORead
PCD 5 Write to MCORead
PCD 6 Write to MCORead
PCD 7 Write to MCORead
PCD 8 Write to MCORead
PCD 9 Write to MCORead
PCD 10 Write to MCORead
PCD 1 Read from MCORead
PCD 2 Read from MCORead
PCD 3 Read from MCORead
PCD 4 Read from MCORead
PCD 5 Read from MCORead
PCD 6 Read from MCORead
PCD 7 Read from MCORead
PCD 8 Read from MCORead
PCD 9 Read from MCORead
PCD 10 Read from MCORead
Digital InputsRead
Digital OutputsRead
Actual PositionRead
Commanded PositionRead
Actual Master PositionRead
Slave Index PositionRead
Master Index PositionRead
Curve PositionRead
Track ErrorRead
Synchronizing ErrorRead
Actual VelocityRead
Actual Master VelocityRead
Synchronizing StatusRead
Axis StatusRead
Program StatusRead
MCO 302 StatusRead
MCO 302 ControlRead
SPI Error CounterRead
MCO Alarm Word 1Read
MCO Alarm Word 2Read
Term. X48/4 Temperature UnitRead and write
Term. X48/4 Input TypeRead
Term. X48/7 Temperature UnitRead and write
Term. X48/7 Input TypeRead
Term. X48/10 Temperature UnitRead and write
Term. X48/10 Input TypeRead
Temperature Sensor Alarm FunctionRead and write
Term. X48/4 Filter Time ConstantsRead and write
Term. X48/4 Temp. MonitorRead and write
Term. X48/4 Low Temp. LimitRead and write
Term. X48/4 High Temp. LimitRead and write
Term. X48/7 Filter Time ConstantsRead and write
Term. X48/7 Temp. MonitorRead and write
Term. X48/7 Low Temp. LimitRead and write
Term. X48/7 High Temp. LimitRead and write
Term. X48/10 Filter Time ConstantsRead and write
Term. X48/10 Temp. MonitorRead and write
Term. X48/10 Low Temp. LimitRead and write
Term. X48/10 High Temp. LimitRead and write
Term. X48/2 Low CurrentmARead and write
Term. X48/2 High CurrentmARead and write
Term. 48/2 Low Ref./Feedb. ValueRead and write
Term. 48/2 High Ref./Feedb. ValueRead and write
Term. X48/2 Filter Time ConstantsRead and write
Term. X49/1 ModeRead and write
Term. X49/3 ModeRead and write
Term. X49/5 ModeRead and write
Term. X49/7 ModeRead and write
Term. X49/9 ModeRead and write
Term. X49/11 ModeRead and write
Terminal X49/1 Low VoltageVRead and write
Terminal X49/1 Low CurrentmARead and write
Terminal X49/1 High VoltageVRead and write
Terminal X49/1 High CurrentmARead and write
Terminal X49/1 Low Ref./Feedb. ValueRead and write
Terminal X49/1 High Ref./Feedb. ValueRead and write
Term. X49/1 Filter Time ConstantsRead and write
Terminal X49/3 Low VoltageVRead and write
Terminal X49/3 Low Current 36-21mARead and write
Terminal X49/3 High VoltageVRead and write
Terminal X49/3 High CurrentmARead and write
Terminal X49/3 Low Ref./Feedb. ValueRead and write
Terminal X49/3 High Ref./Feedb. ValueRead and write
Term. X49/3 Filter Time ConstantsRead and write
Terminal X49/5 Low VoltageVRead and write
Terminal X49/3 Low Current 36-31mARead and write
Terminal X49/5 High VoltageVRead and write
Terminal X49/5 High CurrentmARead and write
Terminal X49/5 Low Ref./Feedb. ValueRead and write
Terminal X49/5 High Ref./Feedb. ValueRead and write
Term. X49/5 Filter Time ConstantsRead and write
Terminal X49/7 Analogue OutputRead and write
Terminal X49/7 Digital OutputRead and write
Terminal X49/7 Min Scale%Read and write
Terminal X49/7 Max. Scale%Read and write
Terminal X49/7 Bus Ctrl%Read and write
Terminal X49/7 Timeout Preset%Read and write
Terminal X49/9 Analogue OutputRead and write
Terminal X49/9 Digital OutputRead and write
Terminal X49/9 Min. Scale%Read and write
Terminal X49/9 Max. Scale%Read and write
Terminal X49/9 Bus Ctrl%Read and write
Terminal X49/9 Timeout Preset%Read and write
Terminal X49/11 Analogue OutputRead and write
Terminal X49/11 Digital OutputRead and write
Terminal X49/11 Min. Scale%Read and write
Terminal X49/11 Max. Scale%Read and write
Terminal X49/11 Bus Ctrl%Read and write
Terminal X49/11 Timeout Preset%Read and write
Kin. Back-up UdcRefVRead and write
Kin. Back-up Integral TimesRead and write
Kin. Back-up Lead Filter TimesRead and write
Kin. Back-up Min Run TimesRead and write
Mains Loss DurationsRead and write
Kin.Back-up Start OffVRead and write
Individual CurrentsRead and write
Back EMF VoltageVRead
Back EMF ProtectionRead and write
B-EMF Protection Log ReadoutRead
Acc. Delta SpeedRead and write
Acc. Delta TimesRead and write
Dec. Delta SpeedRead and write
Dec. Delta TimesRead and write
Error CodeRead
DS402 QstopsRead and write
DS 402 Current ActualRead
Motor Current%Read
Motor Torque%Read
Fault Log: Ext. Reference%Read
Alarm Log: FrequencyHzRead
Fault Log: CurrentARead
Fault Log: VoltageVRead
Fault Log: DC Link VoltageVRead
Fault Log: Control WordRead
Fault Log: Status WordRead
Alarm Log: TorqueNmRead
Alarm Log: CBM Value%Read
Alarm Log: CBM Threshold%Read
Flux Sensorless Model ShiftRead and write
Flux Sensorless Corr. GainRead and write
Speed PID Anti Windup Gain%Read and write
Current PID Anti Windup GainRead and write
Flux /w Feedback Dynamic ModeRead and write
Modulation Index%Read and write
Control Word Source InternalRead and write
Speed Deviation TimermsRead and write
Fast RampRead and write
Measured Speed SourceRead and write
Encoder ResolutionRead and write
Encoder DirectionRead and write
Gear RatioRead and write
Feedback TypeRead and write
Feedback FilterHzRead and write
Mounting TypeRead and write
Tolerance ErrorrpmRead and write
Zero Speed TimerhRead and write
Zero Speed LimitrpmRead and write
Safe FunctionRead and write
Type 42-21Read and write
Discrepancy TimemsRead and write
Stable Signal TimemsRead and write
Restart BehaviourRead and write
External Failure ReactionRead and write
Reset SourceRead and write
Parameter Set NameRead and write
S-CRC ValueRead and write
Level 1 PasswordRead and write
Level 1 Password BufferRead and write
Type 42-40Read and write
Ramp ProfileRead and write
Delay TimesRead and write
Delta T%Read and write
Deceleration RateRead and write
Delta VrpmRead and write
Zero SpeedrpmRead and write
Ramp TimesRead and write
S-ramp Ratio at Decel. Start%Read and write
S-ramp Ratio at Decel. End%Read and write
Cut Off Speed 42-50rpmRead and write
Speed LimitrpmRead and write
Fail Safe ReactionRead and write
Start RampRead and write
Ramp Down TimesRead and write
Telegram SelectionRead and write
Destination AddressRead and write
ActivationRead and write
Cut Off Speed 42-71rpmRead and write
Safe Option StatusRead
Safe Option Status 2Read and write
Safe Control WordRead
Safe Status WordRead
Active Safe Func.Read and write
Safe Option InfoRead and write
Time Until Manual TesthRead and write
Supported Customization File VersionRead and write
Customization File VersionRead and write
Restart the Safe OptionRead and write
Component Temp.°CRead
Auxiliary Temp.°CRead
Component SW IDRead
HS Temp. ph.U°CRead
HS Temp. ph.V°CRead
HS Temp. ph.W°CRead
PC Fan A SpeedrpmRead
PC Fan B SpeedrpmRead
PC Fan C SpeedrpmRead
FPC Fan A SpeedrpmRead
FPC Fan B SpeedrpmRead
FPC Fan C SpeedrpmRead
FPC Fan D SpeedrpmRead
FPC Fan E SpeedrpmRead
FPC Fan F SpeedrpmRead
Warning Log: Warning NumberRead
Warning Log: ValueRead
Warning Log: TimesRead
Warning Log: Date and TimeRead
Warning Log: SpeedrpmRead
Warning Log: DurationsRead
Warning Log: Ext. Reference%Read
Warning Log: FrequencyHzRead
Warning Log: CurrentARead
Warning Log: VoltageVRead
Warning: DC Link VoltageVRead
Warning Log: Control WordRead
Warning Log: TorqueNmRead
Warning Log: CBM Value%Read
Warning Log: CBM Threshold%Read
Max Cable ResistanceRead and write
Estimated D-axis Inductance (Ld)Read and write
Estimated Back EMF at 1000 RPMVRead and write
Function 45-00Read and write
Status 45-01Read
Start TimeRead
Stop TimeRead
Readout Setting 45-09Read and write
Alarm High Threshold%Read
Warning S2 High Threshold%Read
Warning S1 High Threshold%Read
Actual Monitor Value%Read
Warning S1 Low Threshold%Read
Warning S2 Low Threshold%Read
Alarm Low Threshold%Read
Type 45-20Read and write
Status 45-21Read
Progress%Read
Baseline Result InfoRead
DurationRead and write
Online Speed Band%Read and write
Min. SpeedRead and write
Max. SpeedRead and write
Speed PointsRead and write
Baseline StatisticsRead and write
Warning ModeRead and write
Alarm ModeRead and write
Alarm High 45-33Read and write
Warning S2 High 45-34Read and write
Warning S1 High 45-35Read and write
Warning S1 LowRead and write
Warning S2 Low 45-37Read and write
Alarm Low 45-38Read and write
Online Baseline CounterRead and write
Extend FactorRead and write
Threshold GenerationRead and write
Threshold LimitsRead and write
SourceRead and write
Sensor 1 UnitRead and write
Active Threshold%Read and write
Load ModeRead and write
Load Threshold%Read and write
Imbalance Limit%Read and write
Imbalance Value%Read
DC-link Ripple Limit%Read and write
DC-link Ripple Value%Read
Signature GainRead and write
Filter Time ConstantsRead and write
Fluctuation LimitsRead and write
Cavitation [%]%Read
Stator [%]%Read
Load [%]%Read
Sensor 1 [%]%Read
Sensor 1 [Unit]Read
Sensor 2 [%]%Read
Sensor 2 [Unit]Read
Sensor 3 [%]%Read
Sensor 3 [Unit]Read
Sensor 4 [%]%Read
Sensor 4 [Unit]Read
Last Change TimeRead
Monitoring Min SpeedrpmRead
Monitoring Max SpeedrpmRead
Monitoring SpeedsrpmRead and write
Alarm Time 46-10sRead and write
Warning S2 Time 46-11sRead and write
Warning S1 Time 46-12sRead and write
Interpolation TypeRead and write
Alarm High 46-20%Read and write
Warning S2 High 46-21%Read and write
Stator Warning S1%Read and write
Resonance Active%Read and write
Resonance Load%Read and write
Alarm High 46-30%Read and write
Warning S2 High 46-31%Read and write
Warning S1 High 46-32%Read and write
Warning S2 Low 46-34%Read and write
Alarm Low 46-35%Read and write
Alarm High 46-40%Read and write
Warning S2 High 46-41%Read and write
Warning S1 High 46-42%Read and write
Warning Low 46-43%Read and write
Alarm Low 46-44%Read and write
Alarm High 46-50%Read and write
Warning S2 High 46-51%Read and write
Warning S1 High 46-52%Read and write
Warning Low 46-53%Read and write
Alarm Low 46-54%Read and write
Alarm High 46-60%Read and write
Warning S2 High 46-61%Read and write
Warning S1 High 46-62%Read and write
Warning Low 46-63%Read and write
Alarm Low 46-64%Read and write
Alarm High 46-70%Read and write
Warning S2 High 46-71%Read and write
Warning S1 High 46-72%Read and write
Warning Low 46-73%Read and write
Alarm Low 46-74%Read and write
Alarm High 46-80%Read and write
Warning S2 High 46-81%Read and write
Warning S1 High 46-82%Read and write
Actual Start TimeRead
Actual Time StopRead
Previous Start TimeRead
Previous Stop TimeRead
Previous SpeedrpmRead
Actual Max 47-06%Read
Actual Mean + 3 Std. Dev. 47-07%Read
Actual Mean 47-08%Read
Actual Min 47-09%Read
Actual Counter 47-10Read
Previous Max 47-11%Read
Previous Mean + 3 Std. Dev. 47-12%Read
Previous Mean 47-13%Read
Previous Min 47-14%Read
Previous Counter 47-15Read
Actual Max 47-16%Read
Actual Mean + 3 Std. Dev. 47-17%Read
Actual Mean 47-18%Read
Actual Min 47-19%Read
Previous Max 47-20%Read
Previous Mean + 3 Std. Dev. 47-21%Read
Previous Mean 47-22%Read
Previous Min 47-23%Read
Actual Max 47-24%Read
Actual Mean + 3 Std. Dev. 47-25%Read
Actual Mean 47-26%Read
Actual Min 47-27%Read
Previous Max 47-28Read and write
Previous Mean + 3 Std. Dev. 47-29%Read
Previous Mean 47-30%Read
Previous Min 47-31%Read
Actual Max 47-32%Read
Actual Mean + 3 Std. Dev. 47-33%Read
Actual Mean 47-34%Read
Actual Mean - 3 Std. Dev.%Read
Actual Min 47-36%Read
Actual Counter 47-37Read
Previous Max 47-38%Read
Previous Mean + 3 Std. Dev. 47-39%Read
Previous Mean 47-40%Read
Previous Mean - 3 Std. Dev.%Read
Previous Min 47-42%Read
Previous Counter 47-43Read
Actual Max 47-44%Read
Actual Mean + 3 Std. Dev. 47-45%Read
Actual Mean 47-46%Read
Actual Min 47-47%Read
Actual Counter 47-48Read
Previous Max 47-49%Read
Previous Mean + 3 Std. Dev. 47-50%Read
Previous Mean 47-51%Read
Previous Min 47-52%Read
Previous Counter 47-53Read
Actual Max 47-54%Read
Actual Mean + 3 Std. Dev. 47-55%Read
Actual Mean 47-56%Read
Actual Min 47-57%Read
Actual Counter 47-58Read
Previous Max 47-59%Read
Previous Mean + 3 Std. Dev. 47-60%Read
Previous Mean 47-61%Read
Previous Min 47-62%Read
Previous Counter 47-63Read
Actual Max 47-64%Read
Actual Mean + 3 Std. Dev. 47-65%Read
Actual Mean 47-66%Read
Actual Min 47-67%Read
Actual Counter 47-68Read
Previous Max 47-69%Read
Previous Mean + 3 Std. Dev. 47-70%Read
Previous Mean 47-71%Read
Previous Min 47-72%Read
Previous Counter 47-73Read
Actual Max 47-74%Read
Actual Mean + 3 Std. Dev. 47-75%Read
Actual Mean 47-76%Read
Actual Min 47-77%Read
Actual Counter 47-78Read
Previous Max 47-79%Read
Previous Mean + 3 Std. Dev. 47-80%Read
Previous Mean 47-81%Read
Previous Min 47-82%Read
Previous Counter 47-83Read
Actual Max 47-84%Read
Actual Mean + 3 Std. Dev. 47-85%Read
Actual Mean 47-86%Read
Actual Min 47-87%Read
Actual Counter 47-88Read
Previous Max 47-89%Read
Previous Mean + 3 Std. Dev. 47-90%Read
Previous Mean 47-91%Read
Previous Min 47-92%Read
Previous Counter 47-93Read
Actual Min SpeedrpmRead
Actual Max SpeedrpmRead
Previous Min SpeedrpmRead
Previous Max SpeedrpmRead
Function 48-00Read and write
Status 48-01Read
Step Change in Speed%Read and write
Step TimesRead and write
Return to ReferenceRead and write
Minimum Speed [RPM]rpmRead and write
Minimum Speed [Hz]HzRead and write
Autonomous FunctionRead and write
Autonomous StatusRead
Autonomous Capacitance Value%Read
Next MeasurementRead
Baseline GenerateRead and write
Baseline StatusRead
Baseline HistoryRead
Baseline Capacitance Value%Read
Frequency Sweep MinHzRead and write
Frequency Sweep MaxHzRead and write
Baseline ProgressRead and write
SineWave Filter TypeRead and write
Warning S1 Threshold%Read and write
Warning S2 Threshold%Read and write
Alarm Threshold%Read and write
Warning S1 Time 49-23minRead and write
Warning S2 Time 49-24minRead and write
Alarm Time 49-25minRead and write
Last Modified TimeRead
Readout Setting 49-30Read and write
Capacitance of Phase U%Read
Capacitance of Phase V%Read
Capacitance of Phase W%Read
Measurement HistoryRead
Relative Slave Velocity Limit%Read and write
Terminal X57/1 Digital InputRead and write
Terminal X59/2 Digital OutputRead and write
Motor Power%Read
Warning Log: Status WordRead
Actual SpeedrpmRead
Parameter IndexRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the condition based monitoring status of a pump or fan drive on a dashboard and send an email when it reports a deviation.
  • Read the MCO process data of a positioning axis next to speed and current from the drive template.
  • Keep a history of the temperature inputs of the sensor input option.
  • Change encoder, positioning or synchronisation settings from the portal during commissioning.

Installation

  1. Add the Danfoss VLT AutomationDrive FC 302 template as described there; this template uses the same RS485 connection, address and settings.

  2. In ModbusCloud, add a second Modbus RTU device with the same address on the Gateway and import this template.

  3. Delete the registers of options and functions you do not use.

  4. Check that the values look plausible against the drive display.

Things to watch for

Most registers return an error or 0.

Option card parameters only exist when the matching card is fitted, and MCO and condition monitoring values stay 0 while those functions are not set up. Keep the registers you use and delete the rest from the device in ModbusCloud.

How do I find the register of a Danfoss parameter?

The register number is the parameter number times ten, so parameter 45-21 is register 45210 and address 45209 in the template. The parameter number is in the comment of each register.

Some array parameters always show the first value.

For array parameters the drive returns the element chosen in Parameter Index. Write the index you want there first, then read the array parameter.