Danfoss VLT HVAC Basic Drive FC 101
HVAC frequency converter for fans, pumps and compressors, over built-in Modbus RTU.
The Danfoss VLT HVAC Basic Drive FC 101 is a frequency converter that controls the speed of fans, pumps and compressors in buildings. This Modbus RTU template reads frequency, current, power, temperature, energy and alarms, and lets you start, stop and set the speed, ramps, limits and PI setpoints from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 488, read and write
- Brand
- Danfoss
- Key readings
- Output frequency · Motor current · Motor voltage · Motor power · DC link voltage · Heat sink temperature · kWh counter · Alarm word
- Available commands
- Control word · Speed reference · PI setpoint · Ramp up and ramp down time · Motor speed limits · Drive parameters
- Compatible models
- VLT HVAC Basic Drive FC 101
- Last updated
Registers (488)
455 read, 368 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| 16-01 Reference [Unit] | Read | ||||
| 16-02 Reference [%] | % | Read | |||
| 16-03 Status Word | Read | ||||
| 16-05 Main Actual Value [%] | % | Read | |||
| 16-09 Custom Readout | Read | ||||
| 16-10 Power [kW] | kW | Read | |||
| 16-11 Power [hp] | Read | ||||
| 16-12 Motor Voltage | V | Read | |||
| 16-13 Frequency | Hz | Read | |||
| 16-14 Motor Current | A | Read | |||
| 16-15 Frequency [%] | % | Read | |||
| 16-16 Torque [Nm] | Nm | Read | |||
| 16-17 Speed [RPM] | rpm | Read | |||
| 16-18 Motor Thermal | % | Read | |||
| 16-22 Torque [%] | % | Read | |||
| 16-26 Power Filtered [kW] | kW | Read | |||
| 16-27 Power Filtered [hp] | Read | ||||
| 16-30 DC Link Voltage | V | Read | |||
| 16-34 Heat Sink Temp. | °C | Read | |||
| 16-35 Inverter Thermal | % | Read | |||
| 16-36 Inv. Nom. Current | A | Read | |||
| 16-37 Inv. Max. Current | A | Read | |||
| 16-38 SL Controller State | Read | ||||
| 16-50 External Reference | % | Read | |||
| 16-52 Feedback [Unit] | Read | ||||
| 16-54 Feedback 1 [Unit] | Read | ||||
| 16-55 Feedback 2 [Unit] | Read | ||||
| 16-56 Feedback 3 [Unit] | Read | ||||
| 16-60 Digital Input | Read | ||||
| 16-61 Terminal 53 Setting | Read | ||||
| 16-62 Analog Input 53 | Read | ||||
| 16-63 Terminal 54 Setting | Read | ||||
| 16-64 Analog Input 54 | Read | ||||
| 16-65 Analog Output 42 [mA] | mA | Read | |||
| 16-66 Digital Output | Read | ||||
| 16-67 Pulse Input 29 [Hz] | Read | ||||
| 16-71 Relay Output | Read | ||||
| 16-72 Counter A | Read | ||||
| 16-73 Counter B | Read | ||||
| 16-79 Analog Output 45 [mA] | mA | Read | |||
| 16-86 FC Port REF 1 | Read | ||||
| 16-90 Alarm Word | Read | ||||
| 16-91 Alarm Word 2 | Read | ||||
| 16-92 Warning Word | Read | ||||
| 16-93 Warning Word 2 | Read | ||||
| 16-94 Ext. Status Word | Read | ||||
| 16-95 Ext. Status Word 2 | Read | ||||
| 16-97 Alarm Word 3 | Read | ||||
| 16-98 Warning Word 3 | Read | ||||
| 18-10 FireMode Log:Event | Read | ||||
| 18-50 Sensorless Readout [unit] | Read | ||||
| 18-87 Inv. Max. Current | A | Read | |||
| 18-88 Motor Current | A | Read | |||
| 18-90 Process PID Error | % | Read | |||
| 18-91 Process PID Output | % | Read | |||
| 18-92 Process PID Clamped Output | % | Read | |||
| 18-93 Process PID Gain Scaled Output | % | Read | |||
| Status Word Coil Control Ready | Read | ||||
| Status Word Coil Drive Ready | Read | ||||
| Status Word Coil Coasting Stop | Read | ||||
| Status Word Coil Alarm | Read | ||||
| Status Word Coil Not Used 37 | Read | ||||
| Status Word Coil Not Used 38 | Read | ||||
| Status Word Coil Not Used 39 | Read | ||||
| Status Word Coil Warning | Read | ||||
| Status Word Coil At Reference | Read | ||||
| Status Word Coil Auto Mode | Read | ||||
| Status Word Coil In Frequency Range | Read | ||||
| Status Word Coil Running | Read | ||||
| Status Word Coil Not Used 45 | Read | ||||
| Status Word Coil Voltage Warning | Read | ||||
| Status Word Coil Current Limit | Read | ||||
| Status Word Coil Thermal Warning | Read | ||||
| Output Frequency Coil Bit 0 | Read | ||||
| Output Frequency Coil Bit 1 | Read | ||||
| Output Frequency Coil Bit 2 | Read | ||||
| Output Frequency Coil Bit 3 | Read | ||||
| Output Frequency Coil Bit 4 | Read | ||||
| Output Frequency Coil Bit 5 | Read | ||||
| Output Frequency Coil Bit 6 | Read | ||||
| Output Frequency Coil Bit 7 | Read | ||||
| Output Frequency Coil Bit 8 | Read | ||||
| Output Frequency Coil Bit 9 | Read | ||||
| Output Frequency Coil Bit 10 | Read | ||||
| Output Frequency Coil Bit 11 | Read | ||||
| Output Frequency Coil Bit 12 | Read | ||||
| Output Frequency Coil Bit 13 | Read | ||||
| Output Frequency Coil Bit 14 | Read | ||||
| Output Frequency Coil Bit 15 | Read | ||||
| Parameter Write Control | Write | ||||
| Control Word Coil Preset Reference LSB | Write | ||||
| Control Word Coil Preset Reference MSB | Write | ||||
| Control Word Coil DC Brake | Write | ||||
| Control Word Coil Coast Stop | Write | ||||
| Control Word Coil Quick Stop | Write | ||||
| Control Word Coil Freeze Frequency | Write | ||||
| Control Word Coil Ramp Stop or Start | Write | ||||
| Control Word Coil Reset | Write | ||||
| Control Word Coil Jog | Write | ||||
| Control Word Coil Ramp 1 or 2 | Write | ||||
| Control Word Coil Data Valid | Write | ||||
| Control Word Coil Relay 1 | Write | ||||
| Control Word Coil Relay 2 | Write | ||||
| Control Word Coil Setup LSB | Write | ||||
| Control Word Coil Bit 14 | Write | ||||
| Control Word Coil Reversing | Write | ||||
| Speed Reference Coil Bit 0 | Write | ||||
| Speed Reference Coil Bit 1 | Write | ||||
| Speed Reference Coil Bit 2 | Write | ||||
| Speed Reference Coil Bit 3 | Write | ||||
| Speed Reference Coil Bit 4 | Write | ||||
| Speed Reference Coil Bit 5 | Write | ||||
| Speed Reference Coil Bit 6 | Write | ||||
| Speed Reference Coil Bit 7 | Write | ||||
| Speed Reference Coil Bit 8 | Write | ||||
| Speed Reference Coil Bit 9 | Write | ||||
| Speed Reference Coil Bit 10 | Write | ||||
| Speed Reference Coil Bit 11 | Write | ||||
| Speed Reference Coil Bit 12 | Write | ||||
| Speed Reference Coil Bit 13 | Write | ||||
| Speed Reference Coil Bit 14 | Write | ||||
| Speed Reference Coil Bit 15 | Write | ||||
| 0-01 Language | Read and write | ||||
| Modbus Conf | Read and write | ||||
| Last Error Code | Read | ||||
| Last Error Register | Read | ||||
| Index Pointer | Read and write | ||||
| 0-03 Regional Settings | Read and write | ||||
| 0-04 Operating State at Power-up | Read and write | ||||
| 0-06 GridType | Read and write | ||||
| 0-07 Auto DC Braking | Read and write | ||||
| 0-10 Active Set-up | Read and write | ||||
| 0-11 Programming Set-up | Read and write | ||||
| 0-12 Link Setups | Read and write | ||||
| 0-30 Custom Readout Unit | Read and write | ||||
| 0-31 Custom Readout Min Value | Read and write | ||||
| 0-32 Custom Readout Max Value | Read and write | ||||
| 0-37 Display Text 1 | Read and write | ||||
| 0-38 Display Text 2 | Read and write | ||||
| 0-39 Display Text 3 | Read and write | ||||
| 0-40 [Hand on] Key on LCP | Read and write | ||||
| 0-42 [Auto on] Key on LCP | Read and write | ||||
| 0-44 [Off/Reset] Key on LCP | Read and write | ||||
| 0-50 LCP Copy | Read and write | ||||
| 0-51 Set-up Copy | Read and write | ||||
| 0-60 Main Menu Password | Read and write | ||||
| 0-61 Access to Main Menu w/o Password | Read and write | ||||
| 1-00 Configuration Mode | Read and write | ||||
| 1-01 Motor Control Principle | Read and write | ||||
| 1-03 Torque Characteristics | Read and write | ||||
| 1-06 Clockwise Direction | Read and write | ||||
| 1-08 Motor Control Bandwidth | Read and write | ||||
| 1-10 Motor Construction | Read and write | ||||
| 1-14 Damping Gain | % | Read and write | |||
| 1-15 Low Speed Filter Time Const. | s | Read and write | |||
| 1-16 High Speed Filter Time Const. | s | Read and write | |||
| 1-17 Voltage Filter Time Const. | s | Read and write | |||
| 1-20 Motor Power | Read and write | ||||
| 1-22 Motor Voltage | V | Read and write | |||
| 1-23 Motor Frequency | Hz | Read and write | |||
| 1-24 Motor Current | A | Read and write | |||
| 1-25 Motor Nominal Speed | rpm | Read and write | |||
| 1-26 Motor Cont. Rated Torque | Nm | Read and write | |||
| 1-29 Automatic Motor Adaption (AMA) | Read and write | ||||
| 1-30 Stator Resistance (Rs) | Ω | Read and write | |||
| 1-31 Rotor Resistance (Rr) | Ω | Read and write | |||
| 1-33 Stator Leakage Reactance (X1) | Ω | Read and write | |||
| 1-35 Main Reactance (Xh) | Ω | Read and write | |||
| 1-37 d-axis Inductance (Ld) | Read and write | ||||
| 1-38 q-axis Inductance (Lq) | Read and write | ||||
| 1-39 Motor Poles | Read and write | ||||
| 1-40 Back EMF at 1000 RPM | V | Read and write | |||
| 1-42 Motor Cable Length | m | Read and write | |||
| 1-43 Motor Cable Length Feet | Read and write | ||||
| 1-44 d-axis Inductance Sat. (LdSat) | Read and write | ||||
| 1-45 q-axis Inductance Sat. (LqSat) | Read and write | ||||
| 1-46 Position Detection Gain | % | Read and write | |||
| 1-48 Current at Min Inductance for d-axis | % | Read and write | |||
| 1-49 Current at Min Inductance for q-axis | % | Read and write | |||
| 1-50 Motor Magnetization at Zero Speed | % | Read and write | |||
| 1-52 Min Speed Normal Magnetizing [Hz] | Hz | Read and write | |||
| 1-55 U/f Characteristic - U | V | Read and write | |||
| 1-56 U/f Characteristic - F | Hz | Read and write | |||
| 1-60 Low Speed Load Compensation | % | Read and write | |||
| 1-61 High Speed Load Compensation | % | Read and write | |||
| 1-62 Slip Compensation | % | Read and write | |||
| 1-63 Slip Compensation Time Constant | s | Read and write | |||
| 1-64 Resonance Dampening | % | Read and write | |||
| 1-65 Resonance Dampening Time Constant | s | Read and write | |||
| 1-66 Min. Current at Low Speed | % | Read and write | |||
| 1-70 Start Mode | Read and write | ||||
| 1-71 Start Delay | s | Read and write | |||
| 1-72 Start Function | Read and write | ||||
| 1-73 Flying Start | Read and write | ||||
| 1-78 Compressor Start Max Speed [Hz] | Hz | Read and write | |||
| 1-79 Compressor Start Max Time to Trip | s | Read and write | |||
| 1-80 Function at Stop | Read and write | ||||
| 1-82 Min Speed for Function at Stop [Hz] | Hz | Read and write | |||
| 1-87 Trip Speed Low [Hz] | Hz | Read and write | |||
| 1-88 AC Brake Gain | Read and write | ||||
| 1-90 Motor Thermal Protection | Read and write | ||||
| 1-93 Thermistor Source | Read and write | ||||
| 2-00 DC Hold/Motor Preheat Current | % | Read and write | |||
| 2-01 DC Brake Current | % | Read and write | |||
| 2-02 DC Braking Time | s | Read and write | |||
| 2-04 DC Brake Cut In Speed | Hz | Read and write | |||
| 2-06 Parking Current | % | Read and write | |||
| 2-07 Parking Time | s | Read and write | |||
| 2-10 Brake Function | Read and write | ||||
| 2-16 AC Brake, Max Current | % | Read and write | |||
| 2-17 Overvoltage Control | Read and write | ||||
| 2-19 Overvoltage Gain | % | Read and write | |||
| 3-02 Minimum Reference | Read and write | ||||
| 3-03 Maximum Reference | Read and write | ||||
| 3-04 Reference Function | Read and write | ||||
| 3-10 Preset Reference | % | Read and write | |||
| 3-11 Jog Speed [Hz] | Hz | Read and write | |||
| 3-13 Reference Site | Read and write | ||||
| 3-14 Preset Relative Reference | % | Read and write | |||
| 3-15 Reference 1 Source | Read and write | ||||
| 3-16 Reference 2 Source | Read and write | ||||
| 3-17 Reference 3 Source | Read and write | ||||
| 3-41 Ramp 1 Ramp Up Time | s | Read and write | |||
| 3-42 Ramp 1 Ramp Down Time | s | Read and write | |||
| 3-51 Ramp 2 Ramp Up Time | s | Read and write | |||
| 3-52 Ramp 2 Ramp Down Time | s | Read and write | |||
| 3-80 Jog Ramp Time | s | Read and write | |||
| 3-81 Quick Stop Ramp Time | s | Read and write | |||
| 3-82 Starting Ramp Up Time | s | Read and write | |||
| 4-10 Motor Speed Direction | Read and write | ||||
| 4-12 Motor Speed Low Limit [Hz] | Hz | Read and write | |||
| 4-14 Motor Speed High Limit [Hz] | Hz | Read and write | |||
| 4-18 Current Limit | % | Read and write | |||
| 4-19 Max Output Frequency | Hz | Read and write | |||
| 4-40 Warning Freq. Low | Hz | Read and write | |||
| 4-41 Warning Freq. High | Hz | Read and write | |||
| 4-50 Warning Current Low | A | Read and write | |||
| 4-51 Warning Current High | A | Read and write | |||
| 4-54 Warning Reference Low | Read and write | ||||
| 4-55 Warning Reference High | Read and write | ||||
| 4-56 Warning Feedback Low | Read and write | ||||
| 4-57 Warning Feedback High | Read and write | ||||
| 4-58 Missing Motor Phase Function | Read and write | ||||
| 4-61 Bypass Speed From [Hz] | Hz | Read and write | |||
| 4-63 Bypass Speed To [Hz] | Hz | Read and write | |||
| 4-64 Semi-Auto Bypass Set-up | Read and write | ||||
| 5-00 Digital Input Mode | Read and write | ||||
| 5-03 Digital Input 29 Mode | Read and write | ||||
| 5-10 Terminal 18 Digital Input | Read and write | ||||
| 5-11 Terminal 19 Digital Input | Read and write | ||||
| 5-12 Terminal 27 Digital Input | Read and write | ||||
| 5-13 Terminal 29 Digital Input | Read and write | ||||
| 5-40 Function Relay | Read and write | ||||
| 5-41 On Delay, Relay | s | Read and write | |||
| 5-42 Off Delay, Relay | s | Read and write | |||
| 5-50 Term. 29 Low Frequency | Hz | Read and write | |||
| 5-51 Term. 29 High Frequency | Hz | Read and write | |||
| 5-52 Term. 29 Low Ref./Feedb. Value | Read and write | ||||
| 5-53 Term. 29 High Ref./Feedb. Value | Read and write | ||||
| 5-54 Term. 29 Pulse Filter Time Constant | ms | Read and write | |||
| 5-80 AHF Cap Reconnect Delay | s | Read and write | |||
| 5-90 Digital & Relay Bus Control | Read and write | ||||
| 6-00 Live Zero Timeout Time | s | Read and write | |||
| 6-01 Live Zero Timeout Function | Read and write | ||||
| 6-02 Fire Mode Live Zero Timeout Function | Read and write | ||||
| 6-10 Terminal 53 Low Voltage | V | Read and write | |||
| 6-11 Terminal 53 High Voltage | V | Read and write | |||
| 6-12 Terminal 53 Low Current | mA | Read and write | |||
| 6-13 Terminal 53 High Current | mA | Read and write | |||
| 6-14 Terminal 53 Low Ref./Feedb. Value | Read and write | ||||
| 6-15 Terminal 53 High Ref./Feedb. Value | Read and write | ||||
| 6-16 Terminal 53 Filter Time Constant | s | Read and write | |||
| 6-19 Terminal 53 mode | Read and write | ||||
| 6-20 Terminal 54 Low Voltage | V | Read and write | |||
| 6-21 Terminal 54 High Voltage | V | Read and write | |||
| 6-22 Terminal 54 Low Current | mA | Read and write | |||
| 6-23 Terminal 54 High Current | mA | Read and write | |||
| 6-24 Terminal 54 Low Ref./Feedb. Value | Read and write | ||||
| 6-25 Terminal 54 High Ref./Feedb. Value | Read and write | ||||
| 6-26 Terminal 54 Filter Time Constant | s | Read and write | |||
| 6-29 Terminal 54 Mode | Read and write | ||||
| 6-70 Terminal 45 Mode | Read and write | ||||
| 6-71 Terminal 45 Analog Output | Read and write | ||||
| 6-72 Terminal 45 Digital Output | Read and write | ||||
| 6-73 Terminal 45 Output Min Scale | % | Read and write | |||
| 6-74 Terminal 45 Output Max Scale | % | Read and write | |||
| 6-76 Terminal 45 Output Bus Control | Read and write | ||||
| 6-90 Terminal 42 Mode | Read and write | ||||
| 6-91 Terminal 42 Analog Output | Read and write | ||||
| 6-92 Terminal 42 Digital Output | Read and write | ||||
| 6-93 Terminal 42 Output Min Scale | % | Read and write | |||
| 6-94 Terminal 42 Output Max Scale | % | Read and write | |||
| 6-96 Terminal 42 Output Bus Control | Read and write | ||||
| 6-98 Drive Type | Read and write | ||||
| 8-01 Control Site | Read and write | ||||
| 8-02 Control Source | Read and write | ||||
| 8-03 Control Timeout Time | s | Read and write | |||
| 8-04 Control Timeout Function | Read and write | ||||
| 8-30 Protocol | Read and write | ||||
| 8-31 Address | Read and write | ||||
| 8-32 Baud Rate | Read and write | ||||
| 8-33 Parity/Stop Bits | Read and write | ||||
| 8-35 Minimum Response Delay | Read and write | ||||
| 8-36 Maximum Response Delay | s | Read and write | |||
| 8-37 Maximum Inter-char Delay | s | Read and write | |||
| 8-42 PCD Write Configuration | Read and write | ||||
| 8-43 PCD Read Configuration | Read and write | ||||
| 8-44 PCD User Define | Read and write | ||||
| 8-50 Coasting Select | Read and write | ||||
| 8-51 Quick Stop Select | Read and write | ||||
| 8-52 DC Brake Select | Read and write | ||||
| 8-53 Start Select | Read and write | ||||
| 8-54 Reversing Select | Read and write | ||||
| 8-55 Set-up Select | Read and write | ||||
| 8-56 Preset Reference Select | Read and write | ||||
| 8-70 BACnet Device Instance | Read and write | ||||
| 8-72 MS/TP Max Masters | Read and write | ||||
| 8-73 MS/TP Max Info Frames | Read and write | ||||
| 8-74 "I am" Service | Read and write | ||||
| 8-75 Initialization Password | Read and write | ||||
| 8-79 Protocol Firmware version | Read and write | ||||
| 8-80 Bus Message Count | Read and write | ||||
| 8-81 Bus Error Count | Read and write | ||||
| 8-82 Slave Messages Rcvd | Read and write | ||||
| 8-83 Slave Error Count | Read and write | ||||
| 8-84 Slave Messages Sent | Read and write | ||||
| 8-85 Slave Timeout Errors | Read and write | ||||
| 8-88 Reset FC port Diagnostics | Read and write | ||||
| 8-94 Bus Feedback 1 | Read and write | ||||
| 8-95 Bus Feedback 2 | Read and write | ||||
| 13-00 SL Controller Mode | Read and write | ||||
| 13-01 Start Event | Read and write | ||||
| 13-02 Stop Event | Read and write | ||||
| 13-03 Reset SLC | Read and write | ||||
| 13-10 Comparator Operand | Read and write | ||||
| 13-11 Comparator Operator | Read and write | ||||
| 13-12 Comparator Value | Read and write | ||||
| 13-20 SL Controller Timer | s | Read and write | |||
| 13-40 Logic Rule Boolean 1 | Read and write | ||||
| 13-41 Logic Rule Operator 1 | Read and write | ||||
| 13-42 Logic Rule Boolean 2 | Read and write | ||||
| 13-43 Logic Rule Operator 2 | Read and write | ||||
| 13-44 Logic Rule Boolean 3 | Read and write | ||||
| 13-51 SL Controller Event | Read and write | ||||
| 13-52 SL Controller Action | Read and write | ||||
| 14-01 Switching Frequency | Read and write | ||||
| 14-03 Overmodulation | Read and write | ||||
| 14-07 Dead Time Compensation Level | Read and write | ||||
| 14-08 Damping Gain Factor | % | Read and write | |||
| 14-09 Dead Time Bias Current Level | % | Read and write | |||
| 14-10 Mains Failure | Read and write | ||||
| 14-11 Mains Fault Voltage Level | V | Read and write | |||
| 14-12 Response to Mains Imbalance | Read and write | ||||
| 14-15 Kin. Back-up Trip Recovery Level | Read and write | ||||
| 14-20 Reset Mode | Read and write | ||||
| 14-21 Automatic Restart Time | s | Read and write | |||
| 14-22 Operation Mode | Read and write | ||||
| 14-23 Typecode Setting | Read and write | ||||
| 14-24 Trip Delay at Current Limit | s | Read and write | |||
| 14-27 Action At Inverter Fault | Read and write | ||||
| 14-28 Production Settings | Read and write | ||||
| 14-29 Service Code | Read and write | ||||
| 14-30 Current Lim Ctrl, Proportional Gain | % | Read and write | |||
| 14-31 Current Lim Ctrl, Integration Time | s | Read and write | |||
| 14-32 Current Lim Ctrl, Filter Time | ms | Read and write | |||
| 14-40 VT Level | % | Read and write | |||
| 14-41 AEO Minimum Magnetization | % | Read and write | |||
| 14-50 RFI Filter | Read and write | ||||
| 14-51 DC-Link Voltage Compensation | Read and write | ||||
| 14-52 Fan Control | Read and write | ||||
| 14-53 Fan Monitor | Read and write | ||||
| 14-55 Output Filter | Read and write | ||||
| 14-61 Function at Inverter Overload | Read and write | ||||
| 14-63 Min Switch Frequency | Read and write | ||||
| 14-64 Dead Time Compensation Zero Current Level | Read and write | ||||
| 14-65 Speed Derate Dead Time Compensation | Hz | Read and write | |||
| 14-90 Fault Level | Read and write | ||||
| 15-00 Operating Hours | h | Read | |||
| 20-00 Feedback 1 Source | Read and write | ||||
| 20-01 Feedback 1 Conversion | Read and write | ||||
| 20-03 Feedback 2 Source | Read and write | ||||
| 20-04 Feedback 2 Conversion | Read and write | ||||
| 20-06 Feedback 3 Source | Read and write | ||||
| 20-07 Feedback 3 Conversion | Read and write | ||||
| 20-12 Reference/Feedback Unit | Read and write | ||||
| 20-20 Feedback Function | Read and write | ||||
| 20-21 Setpoint 1 | Read and write | ||||
| 20-60 Sensorless Unit | Read and write | ||||
| 20-69 Sensorless Information | Read | ||||
| 20-81 PI Normal/Inverse Control | Read and write | ||||
| 20-83 PI Start Speed [Hz] | Hz | Read and write | |||
| 20-84 On Reference Bandwidth | % | Read and write | |||
| 20-91 PI Anti Windup | Read and write | ||||
| 20-93 PI Proportional Gain | Read and write | ||||
| 20-94 PI Integral Time | s | Read and write | |||
| 20-97 PI Feed Forward Factor | % | Read and write | |||
| 22-01 Power Filter Time | s | Read and write | |||
| 22-02 Sleepmode CL Control Mode | Read and write | ||||
| 22-04 Check Valve Monitor | Read and write | ||||
| 22-23 No-Flow Function | Read and write | ||||
| 22-24 No-Flow Delay | s | Read and write | |||
| 22-26 Dry Pump Function | Read and write | ||||
| 22-27 Dry Pump Delay | s | Read and write | |||
| 22-30 No-Flow Power | kW | Read and write | |||
| 22-31 Power Correction Factor | % | Read and write | |||
| 22-33 Low Speed [Hz] | Hz | Read and write | |||
| 22-34 Low Speed Power [kW] | kW | Read and write | |||
| 22-37 High Speed [Hz] | Hz | Read and write | |||
| 22-38 High Speed Power [kW] | kW | Read and write | |||
| 22-40 Minimum Run Time | s | Read and write | |||
| 22-41 Minimum Sleep Time | s | Read and write | |||
| 22-43 Wake-Up Speed [Hz] | Read and write | ||||
| 22-44 Wake-Up Ref./FB Diff | % | Read and write | |||
| 22-45 Setpoint Boost | % | Read and write | |||
| 22-46 Maximum Boost Time | s | Read and write | |||
| 22-47 Sleep Speed [Hz] | Read and write | ||||
| 22-48 Sleep Delay Time | s | Read and write | |||
| 22-49 Wake-Up Delay Time | s | Read and write | |||
| 22-50 End of Curve Function | Read and write | ||||
| 22-51 End of Curve Delay | s | Read and write | |||
| 22-60 Broken Belt Function | Read and write | ||||
| 22-61 Broken Belt Torque | % | Read and write | |||
| 22-62 Broken Belt Delay | s | Read and write | |||
| 22-80 Flow Compensation | Read and write | ||||
| 22-81 Square-linear Curve Approximation | % | Read and write | |||
| 22-82 Work Point Calculation | Read and write | ||||
| 22-84 Speed at No-Flow [Hz] | Hz | Read and write | |||
| 22-86 Speed at Design Point [Hz] | Hz | Read and write | |||
| 22-87 Pressure at No-Flow Speed | Read and write | ||||
| 22-88 Pressure at Rated Speed | Read and write | ||||
| 22-89 Flow at Design Point | Read and write | ||||
| 22-90 Flow at Rated Speed | Read and write | ||||
| 23-05 Interval Between Operation | min | Read and write | |||
| 23-06 Running Time | s | Read and write | |||
| 23-07 Running Speed and Direction | Hz | Read and write | |||
| 24-00 FM Function | Read and write | ||||
| 24-01 Fire Mode Configuration | Read and write | ||||
| 24-03 Fire Mode Min Reference | Read and write | ||||
| 24-04 Fire Mode Max Reference | Read and write | ||||
| 24-05 FM Preset Reference | % | Read and write | |||
| 24-06 Fire Mode Reference Source | Read and write | ||||
| 24-07 Fire Mode Feedback Source | Read and write | ||||
| 24-08 Mul FM Preset Reference | % | Read and write | |||
| 24-09 FM Alarm Handling | Read and write | ||||
| 24-10 Drive Bypass Function | Read and write | ||||
| 24-11 Drive Bypass Delay Time | s | Read and write | |||
| 24-90 Missing Motor Function | Read and write | ||||
| 24-91 Missing Motor Coefficient 1 | Read and write | ||||
| 24-92 Missing Motor Coefficient 2 | Read and write | ||||
| 24-93 Missing Motor Coefficient 3 | Read and write | ||||
| 24-94 Missing Motor Coefficient 4 | Read and write | ||||
| 24-95 Locked Rotor Function | Read and write | ||||
| 24-96 Locked Rotor Coefficient 1 | Read and write | ||||
| 24-97 Locked Rotor Coefficient 2 | Read and write | ||||
| 24-98 Locked Rotor Coefficient 3 | Read and write | ||||
| 24-99 Locked Rotor Coefficient 4 | Read and write | ||||
| 30-22 Locked Rotor Protection | Read and write | ||||
| 30-23 Locked Rotor Detection Time [s] | s | Read and write | |||
| 30-58 LockPassword | Read and write | ||||
| 15-01 Running Hours | h | Read | |||
| 15-02 kWh Counter | kWh | Read | |||
| 15-03 Power Up's | Read | ||||
| 15-04 Over Temp's | Read | ||||
| 15-05 Overvolt's | Read | ||||
| 15-06 Reset kWh Counter | Read and write | ||||
| 15-07 Reset Running Hours Counter | Read and write | ||||
| 15-30 Alarm Log: Error Code | Read | ||||
| 15-31 InternalFaultReason | Read | ||||
| 15-32 Alarm Log: Time | s | Read | |||
| 15-40 FC Type | Read | ||||
| 15-41 Power Section | Read | ||||
| 15-42 Voltage | Read | ||||
| 15-43 Software Version | Read | ||||
| 15-44 Ordered TypeCode | Read | ||||
| 15-45 Actual Typecode String | Read | ||||
| 15-46 Drive Ordering No | Read | ||||
| 15-48 LCP Id No | Read | ||||
| 15-49 SW ID Control Card | Read | ||||
| 15-50 SW ID Power Card | Read | ||||
| 15-51 Drive Serial Number | Read | ||||
| 15-52 OEM Information | Read | ||||
| 15-53 Power Card Serial Number | Read | ||||
| 15-57 File Version | Read | ||||
| 15-59 Filename | Read | ||||
| 15-92 Defined Parameters | Read | ||||
| 15-97 Application Type | Read | ||||
| 15-98 Drive Identification | Read | ||||
| 16-00 Control Word | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show output frequency, motor current and power of every fan and pump drive on a ModbusCloud dashboard.
- Get an email alert when the alarm word is no longer 0 or the heat sink temperature passes a limit.
- Keep 365 days of kWh counter and running hours history to compare consumption per fan or pump.
- Change the PI setpoint of a pressure or temperature loop remotely without visiting the plant room.
- Start, stop or change the speed of a fan from an automation on a time schedule or the energy price.
Installation
Connect terminals 68 (P+) and 69 (N-) of the drive to RS485 A and B on the ModbusCloud Gateway and terminate the bus at both ends, on the drive with dip switch S801.
Set 8-30 Protocol to Modbus RTU, then 8-31 Address, 8-32 Baud Rate and 8-33 Parity/Stop Bits.
For control over Modbus, set 8-01 Control Site and 8-02 Control Source to the FC port, and 3-15 Reference 1 Source to Local bus reference.
In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings, for example 1, 19200 baud, 8E1, and import this template.
Check that output frequency and motor current match the display of the drive.
Things to watch for
The drive does not answer. What should I check?
Check that 8-30 is set to Modbus RTU and that address, baud rate and parity in 8-31 to 8-33 match the device in ModbusCloud. Changing the protocol can change the baud rate, so check 8-32 again. Then swap A and B and check the termination switch S801.
Why does a 32-bit value look wrong?
Many readouts, such as frequency, power and motor voltage, are 32-bit values over two registers with the high word first. The template reads them that way. If you read only the first register, you get the high word, which is usually 0.
How do I read one element of an array parameter?
Array parameters such as 3-10 Preset Reference or 5-40 Function Relay share one address. Write the index to holding register 9 first; all following reads and writes of array parameters then go to that element.
What should I keep in mind when writing parameters or the control word?
Coil 65 decides whether parameter writes go to RAM only (0) or also to EEPROM (1); keep it at 0 for values you change often. The control word and bus reference only act when 8-01, 8-02 and 3-15 allow it. Change motor data and limits only when you know the installation.