Danfoss Danfoss VLT HVAC Basic Drive FC 101 Modbus RTU template

Danfoss VLT HVAC Basic Drive FC 101

HVAC frequency converter for fans, pumps and compressors, over built-in Modbus RTU.

The Danfoss VLT HVAC Basic Drive FC 101 is a frequency converter that controls the speed of fans, pumps and compressors in buildings. This Modbus RTU template reads frequency, current, power, temperature, energy and alarms, and lets you start, stop and set the speed, ramps, limits and PI setpoints from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
488, read and write
Brand
Danfoss
Key readings
Output frequency · Motor current · Motor voltage · Motor power · DC link voltage · Heat sink temperature · kWh counter · Alarm word
Available commands
Control word · Speed reference · PI setpoint · Ramp up and ramp down time · Motor speed limits · Drive parameters
Compatible models
VLT HVAC Basic Drive FC 101
Last updated

Registers (488)

455 read, 368 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
16-01 Reference [Unit]Read
16-02 Reference [%]%Read
16-03 Status WordRead
16-05 Main Actual Value [%]%Read
16-09 Custom ReadoutRead
16-10 Power [kW]kWRead
16-11 Power [hp]Read
16-12 Motor VoltageVRead
16-13 FrequencyHzRead
16-14 Motor CurrentARead
16-15 Frequency [%]%Read
16-16 Torque [Nm]NmRead
16-17 Speed [RPM]rpmRead
16-18 Motor Thermal%Read
16-22 Torque [%]%Read
16-26 Power Filtered [kW]kWRead
16-27 Power Filtered [hp]Read
16-30 DC Link VoltageVRead
16-34 Heat Sink Temp.°CRead
16-35 Inverter Thermal%Read
16-36 Inv. Nom. CurrentARead
16-37 Inv. Max. CurrentARead
16-38 SL Controller StateRead
16-50 External Reference%Read
16-52 Feedback [Unit]Read
16-54 Feedback 1 [Unit]Read
16-55 Feedback 2 [Unit]Read
16-56 Feedback 3 [Unit]Read
16-60 Digital InputRead
16-61 Terminal 53 SettingRead
16-62 Analog Input 53Read
16-63 Terminal 54 SettingRead
16-64 Analog Input 54Read
16-65 Analog Output 42 [mA]mARead
16-66 Digital OutputRead
16-67 Pulse Input 29 [Hz]Read
16-71 Relay OutputRead
16-72 Counter ARead
16-73 Counter BRead
16-79 Analog Output 45 [mA]mARead
16-86 FC Port REF 1Read
16-90 Alarm WordRead
16-91 Alarm Word 2Read
16-92 Warning WordRead
16-93 Warning Word 2Read
16-94 Ext. Status WordRead
16-95 Ext. Status Word 2Read
16-97 Alarm Word 3Read
16-98 Warning Word 3Read
18-10 FireMode Log:EventRead
18-50 Sensorless Readout [unit]Read
18-87 Inv. Max. CurrentARead
18-88 Motor CurrentARead
18-90 Process PID Error%Read
18-91 Process PID Output%Read
18-92 Process PID Clamped Output%Read
18-93 Process PID Gain Scaled Output%Read
Status Word Coil Control ReadyRead
Status Word Coil Drive ReadyRead
Status Word Coil Coasting StopRead
Status Word Coil AlarmRead
Status Word Coil Not Used 37Read
Status Word Coil Not Used 38Read
Status Word Coil Not Used 39Read
Status Word Coil WarningRead
Status Word Coil At ReferenceRead
Status Word Coil Auto ModeRead
Status Word Coil In Frequency RangeRead
Status Word Coil RunningRead
Status Word Coil Not Used 45Read
Status Word Coil Voltage WarningRead
Status Word Coil Current LimitRead
Status Word Coil Thermal WarningRead
Output Frequency Coil Bit 0Read
Output Frequency Coil Bit 1Read
Output Frequency Coil Bit 2Read
Output Frequency Coil Bit 3Read
Output Frequency Coil Bit 4Read
Output Frequency Coil Bit 5Read
Output Frequency Coil Bit 6Read
Output Frequency Coil Bit 7Read
Output Frequency Coil Bit 8Read
Output Frequency Coil Bit 9Read
Output Frequency Coil Bit 10Read
Output Frequency Coil Bit 11Read
Output Frequency Coil Bit 12Read
Output Frequency Coil Bit 13Read
Output Frequency Coil Bit 14Read
Output Frequency Coil Bit 15Read
Parameter Write ControlWrite
Control Word Coil Preset Reference LSBWrite
Control Word Coil Preset Reference MSBWrite
Control Word Coil DC BrakeWrite
Control Word Coil Coast StopWrite
Control Word Coil Quick StopWrite
Control Word Coil Freeze FrequencyWrite
Control Word Coil Ramp Stop or StartWrite
Control Word Coil ResetWrite
Control Word Coil JogWrite
Control Word Coil Ramp 1 or 2Write
Control Word Coil Data ValidWrite
Control Word Coil Relay 1Write
Control Word Coil Relay 2Write
Control Word Coil Setup LSBWrite
Control Word Coil Bit 14Write
Control Word Coil ReversingWrite
Speed Reference Coil Bit 0Write
Speed Reference Coil Bit 1Write
Speed Reference Coil Bit 2Write
Speed Reference Coil Bit 3Write
Speed Reference Coil Bit 4Write
Speed Reference Coil Bit 5Write
Speed Reference Coil Bit 6Write
Speed Reference Coil Bit 7Write
Speed Reference Coil Bit 8Write
Speed Reference Coil Bit 9Write
Speed Reference Coil Bit 10Write
Speed Reference Coil Bit 11Write
Speed Reference Coil Bit 12Write
Speed Reference Coil Bit 13Write
Speed Reference Coil Bit 14Write
Speed Reference Coil Bit 15Write
0-01 LanguageRead and write
Modbus ConfRead and write
Last Error CodeRead
Last Error RegisterRead
Index PointerRead and write
0-03 Regional SettingsRead and write
0-04 Operating State at Power-upRead and write
0-06 GridTypeRead and write
0-07 Auto DC BrakingRead and write
0-10 Active Set-upRead and write
0-11 Programming Set-upRead and write
0-12 Link SetupsRead and write
0-30 Custom Readout UnitRead and write
0-31 Custom Readout Min ValueRead and write
0-32 Custom Readout Max ValueRead and write
0-37 Display Text 1Read and write
0-38 Display Text 2Read and write
0-39 Display Text 3Read and write
0-40 [Hand on] Key on LCPRead and write
0-42 [Auto on] Key on LCPRead and write
0-44 [Off/Reset] Key on LCPRead and write
0-50 LCP CopyRead and write
0-51 Set-up CopyRead and write
0-60 Main Menu PasswordRead and write
0-61 Access to Main Menu w/o PasswordRead and write
1-00 Configuration ModeRead and write
1-01 Motor Control PrincipleRead and write
1-03 Torque CharacteristicsRead and write
1-06 Clockwise DirectionRead and write
1-08 Motor Control BandwidthRead and write
1-10 Motor ConstructionRead and write
1-14 Damping Gain%Read and write
1-15 Low Speed Filter Time Const.sRead and write
1-16 High Speed Filter Time Const.sRead and write
1-17 Voltage Filter Time Const.sRead and write
1-20 Motor PowerRead and write
1-22 Motor VoltageVRead and write
1-23 Motor FrequencyHzRead and write
1-24 Motor CurrentARead and write
1-25 Motor Nominal SpeedrpmRead and write
1-26 Motor Cont. Rated TorqueNmRead and write
1-29 Automatic Motor Adaption (AMA)Read and write
1-30 Stator Resistance (Rs)ΩRead and write
1-31 Rotor Resistance (Rr)ΩRead and write
1-33 Stator Leakage Reactance (X1)ΩRead and write
1-35 Main Reactance (Xh)ΩRead and write
1-37 d-axis Inductance (Ld)Read and write
1-38 q-axis Inductance (Lq)Read and write
1-39 Motor PolesRead and write
1-40 Back EMF at 1000 RPMVRead and write
1-42 Motor Cable LengthmRead and write
1-43 Motor Cable Length FeetRead and write
1-44 d-axis Inductance Sat. (LdSat)Read and write
1-45 q-axis Inductance Sat. (LqSat)Read and write
1-46 Position Detection Gain%Read and write
1-48 Current at Min Inductance for d-axis%Read and write
1-49 Current at Min Inductance for q-axis%Read and write
1-50 Motor Magnetization at Zero Speed%Read and write
1-52 Min Speed Normal Magnetizing [Hz]HzRead and write
1-55 U/f Characteristic - UVRead and write
1-56 U/f Characteristic - FHzRead and write
1-60 Low Speed Load Compensation%Read and write
1-61 High Speed Load Compensation%Read and write
1-62 Slip Compensation%Read and write
1-63 Slip Compensation Time ConstantsRead and write
1-64 Resonance Dampening%Read and write
1-65 Resonance Dampening Time ConstantsRead and write
1-66 Min. Current at Low Speed%Read and write
1-70 Start ModeRead and write
1-71 Start DelaysRead and write
1-72 Start FunctionRead and write
1-73 Flying StartRead and write
1-78 Compressor Start Max Speed [Hz]HzRead and write
1-79 Compressor Start Max Time to TripsRead and write
1-80 Function at StopRead and write
1-82 Min Speed for Function at Stop [Hz]HzRead and write
1-87 Trip Speed Low [Hz]HzRead and write
1-88 AC Brake GainRead and write
1-90 Motor Thermal ProtectionRead and write
1-93 Thermistor SourceRead and write
2-00 DC Hold/Motor Preheat Current%Read and write
2-01 DC Brake Current%Read and write
2-02 DC Braking TimesRead and write
2-04 DC Brake Cut In SpeedHzRead and write
2-06 Parking Current%Read and write
2-07 Parking TimesRead and write
2-10 Brake FunctionRead and write
2-16 AC Brake, Max Current%Read and write
2-17 Overvoltage ControlRead and write
2-19 Overvoltage Gain%Read and write
3-02 Minimum ReferenceRead and write
3-03 Maximum ReferenceRead and write
3-04 Reference FunctionRead and write
3-10 Preset Reference%Read and write
3-11 Jog Speed [Hz]HzRead and write
3-13 Reference SiteRead and write
3-14 Preset Relative Reference%Read and write
3-15 Reference 1 SourceRead and write
3-16 Reference 2 SourceRead and write
3-17 Reference 3 SourceRead and write
3-41 Ramp 1 Ramp Up TimesRead and write
3-42 Ramp 1 Ramp Down TimesRead and write
3-51 Ramp 2 Ramp Up TimesRead and write
3-52 Ramp 2 Ramp Down TimesRead and write
3-80 Jog Ramp TimesRead and write
3-81 Quick Stop Ramp TimesRead and write
3-82 Starting Ramp Up TimesRead and write
4-10 Motor Speed DirectionRead and write
4-12 Motor Speed Low Limit [Hz]HzRead and write
4-14 Motor Speed High Limit [Hz]HzRead and write
4-18 Current Limit%Read and write
4-19 Max Output FrequencyHzRead and write
4-40 Warning Freq. LowHzRead and write
4-41 Warning Freq. HighHzRead and write
4-50 Warning Current LowARead and write
4-51 Warning Current HighARead and write
4-54 Warning Reference LowRead and write
4-55 Warning Reference HighRead and write
4-56 Warning Feedback LowRead and write
4-57 Warning Feedback HighRead and write
4-58 Missing Motor Phase FunctionRead and write
4-61 Bypass Speed From [Hz]HzRead and write
4-63 Bypass Speed To [Hz]HzRead and write
4-64 Semi-Auto Bypass Set-upRead and write
5-00 Digital Input ModeRead and write
5-03 Digital Input 29 ModeRead and write
5-10 Terminal 18 Digital InputRead and write
5-11 Terminal 19 Digital InputRead and write
5-12 Terminal 27 Digital InputRead and write
5-13 Terminal 29 Digital InputRead and write
5-40 Function RelayRead and write
5-41 On Delay, RelaysRead and write
5-42 Off Delay, RelaysRead and write
5-50 Term. 29 Low FrequencyHzRead and write
5-51 Term. 29 High FrequencyHzRead and write
5-52 Term. 29 Low Ref./Feedb. ValueRead and write
5-53 Term. 29 High Ref./Feedb. ValueRead and write
5-54 Term. 29 Pulse Filter Time ConstantmsRead and write
5-80 AHF Cap Reconnect DelaysRead and write
5-90 Digital & Relay Bus ControlRead and write
6-00 Live Zero Timeout TimesRead and write
6-01 Live Zero Timeout FunctionRead and write
6-02 Fire Mode Live Zero Timeout FunctionRead and write
6-10 Terminal 53 Low VoltageVRead and write
6-11 Terminal 53 High VoltageVRead and write
6-12 Terminal 53 Low CurrentmARead and write
6-13 Terminal 53 High CurrentmARead and write
6-14 Terminal 53 Low Ref./Feedb. ValueRead and write
6-15 Terminal 53 High Ref./Feedb. ValueRead and write
6-16 Terminal 53 Filter Time ConstantsRead and write
6-19 Terminal 53 modeRead and write
6-20 Terminal 54 Low VoltageVRead and write
6-21 Terminal 54 High VoltageVRead and write
6-22 Terminal 54 Low CurrentmARead and write
6-23 Terminal 54 High CurrentmARead and write
6-24 Terminal 54 Low Ref./Feedb. ValueRead and write
6-25 Terminal 54 High Ref./Feedb. ValueRead and write
6-26 Terminal 54 Filter Time ConstantsRead and write
6-29 Terminal 54 ModeRead and write
6-70 Terminal 45 ModeRead and write
6-71 Terminal 45 Analog OutputRead and write
6-72 Terminal 45 Digital OutputRead and write
6-73 Terminal 45 Output Min Scale%Read and write
6-74 Terminal 45 Output Max Scale%Read and write
6-76 Terminal 45 Output Bus ControlRead and write
6-90 Terminal 42 ModeRead and write
6-91 Terminal 42 Analog OutputRead and write
6-92 Terminal 42 Digital OutputRead and write
6-93 Terminal 42 Output Min Scale%Read and write
6-94 Terminal 42 Output Max Scale%Read and write
6-96 Terminal 42 Output Bus ControlRead and write
6-98 Drive TypeRead and write
8-01 Control SiteRead and write
8-02 Control SourceRead and write
8-03 Control Timeout TimesRead and write
8-04 Control Timeout FunctionRead and write
8-30 ProtocolRead and write
8-31 AddressRead and write
8-32 Baud RateRead and write
8-33 Parity/Stop BitsRead and write
8-35 Minimum Response DelayRead and write
8-36 Maximum Response DelaysRead and write
8-37 Maximum Inter-char DelaysRead and write
8-42 PCD Write ConfigurationRead and write
8-43 PCD Read ConfigurationRead and write
8-44 PCD User DefineRead and write
8-50 Coasting SelectRead and write
8-51 Quick Stop SelectRead and write
8-52 DC Brake SelectRead and write
8-53 Start SelectRead and write
8-54 Reversing SelectRead and write
8-55 Set-up SelectRead and write
8-56 Preset Reference SelectRead and write
8-70 BACnet Device InstanceRead and write
8-72 MS/TP Max MastersRead and write
8-73 MS/TP Max Info FramesRead and write
8-74 "I am" ServiceRead and write
8-75 Initialization PasswordRead and write
8-79 Protocol Firmware versionRead and write
8-80 Bus Message CountRead and write
8-81 Bus Error CountRead and write
8-82 Slave Messages RcvdRead and write
8-83 Slave Error CountRead and write
8-84 Slave Messages SentRead and write
8-85 Slave Timeout ErrorsRead and write
8-88 Reset FC port DiagnosticsRead and write
8-94 Bus Feedback 1Read and write
8-95 Bus Feedback 2Read and write
13-00 SL Controller ModeRead and write
13-01 Start EventRead and write
13-02 Stop EventRead and write
13-03 Reset SLCRead and write
13-10 Comparator OperandRead and write
13-11 Comparator OperatorRead and write
13-12 Comparator ValueRead and write
13-20 SL Controller TimersRead and write
13-40 Logic Rule Boolean 1Read and write
13-41 Logic Rule Operator 1Read and write
13-42 Logic Rule Boolean 2Read and write
13-43 Logic Rule Operator 2Read and write
13-44 Logic Rule Boolean 3Read and write
13-51 SL Controller EventRead and write
13-52 SL Controller ActionRead and write
14-01 Switching FrequencyRead and write
14-03 OvermodulationRead and write
14-07 Dead Time Compensation LevelRead and write
14-08 Damping Gain Factor%Read and write
14-09 Dead Time Bias Current Level%Read and write
14-10 Mains FailureRead and write
14-11 Mains Fault Voltage LevelVRead and write
14-12 Response to Mains ImbalanceRead and write
14-15 Kin. Back-up Trip Recovery LevelRead and write
14-20 Reset ModeRead and write
14-21 Automatic Restart TimesRead and write
14-22 Operation ModeRead and write
14-23 Typecode SettingRead and write
14-24 Trip Delay at Current LimitsRead and write
14-27 Action At Inverter FaultRead and write
14-28 Production SettingsRead and write
14-29 Service CodeRead and write
14-30 Current Lim Ctrl, Proportional Gain%Read and write
14-31 Current Lim Ctrl, Integration TimesRead and write
14-32 Current Lim Ctrl, Filter TimemsRead and write
14-40 VT Level%Read and write
14-41 AEO Minimum Magnetization%Read and write
14-50 RFI FilterRead and write
14-51 DC-Link Voltage CompensationRead and write
14-52 Fan ControlRead and write
14-53 Fan MonitorRead and write
14-55 Output FilterRead and write
14-61 Function at Inverter OverloadRead and write
14-63 Min Switch FrequencyRead and write
14-64 Dead Time Compensation Zero Current LevelRead and write
14-65 Speed Derate Dead Time CompensationHzRead and write
14-90 Fault LevelRead and write
15-00 Operating HourshRead
20-00 Feedback 1 SourceRead and write
20-01 Feedback 1 ConversionRead and write
20-03 Feedback 2 SourceRead and write
20-04 Feedback 2 ConversionRead and write
20-06 Feedback 3 SourceRead and write
20-07 Feedback 3 ConversionRead and write
20-12 Reference/Feedback UnitRead and write
20-20 Feedback FunctionRead and write
20-21 Setpoint 1Read and write
20-60 Sensorless UnitRead and write
20-69 Sensorless InformationRead
20-81 PI Normal/Inverse ControlRead and write
20-83 PI Start Speed [Hz]HzRead and write
20-84 On Reference Bandwidth%Read and write
20-91 PI Anti WindupRead and write
20-93 PI Proportional GainRead and write
20-94 PI Integral TimesRead and write
20-97 PI Feed Forward Factor%Read and write
22-01 Power Filter TimesRead and write
22-02 Sleepmode CL Control ModeRead and write
22-04 Check Valve MonitorRead and write
22-23 No-Flow FunctionRead and write
22-24 No-Flow DelaysRead and write
22-26 Dry Pump FunctionRead and write
22-27 Dry Pump DelaysRead and write
22-30 No-Flow PowerkWRead and write
22-31 Power Correction Factor%Read and write
22-33 Low Speed [Hz]HzRead and write
22-34 Low Speed Power [kW]kWRead and write
22-37 High Speed [Hz]HzRead and write
22-38 High Speed Power [kW]kWRead and write
22-40 Minimum Run TimesRead and write
22-41 Minimum Sleep TimesRead and write
22-43 Wake-Up Speed [Hz]Read and write
22-44 Wake-Up Ref./FB Diff%Read and write
22-45 Setpoint Boost%Read and write
22-46 Maximum Boost TimesRead and write
22-47 Sleep Speed [Hz]Read and write
22-48 Sleep Delay TimesRead and write
22-49 Wake-Up Delay TimesRead and write
22-50 End of Curve FunctionRead and write
22-51 End of Curve DelaysRead and write
22-60 Broken Belt FunctionRead and write
22-61 Broken Belt Torque%Read and write
22-62 Broken Belt DelaysRead and write
22-80 Flow CompensationRead and write
22-81 Square-linear Curve Approximation%Read and write
22-82 Work Point CalculationRead and write
22-84 Speed at No-Flow [Hz]HzRead and write
22-86 Speed at Design Point [Hz]HzRead and write
22-87 Pressure at No-Flow SpeedRead and write
22-88 Pressure at Rated SpeedRead and write
22-89 Flow at Design PointRead and write
22-90 Flow at Rated SpeedRead and write
23-05 Interval Between OperationminRead and write
23-06 Running TimesRead and write
23-07 Running Speed and DirectionHzRead and write
24-00 FM FunctionRead and write
24-01 Fire Mode ConfigurationRead and write
24-03 Fire Mode Min ReferenceRead and write
24-04 Fire Mode Max ReferenceRead and write
24-05 FM Preset Reference%Read and write
24-06 Fire Mode Reference SourceRead and write
24-07 Fire Mode Feedback SourceRead and write
24-08 Mul FM Preset Reference%Read and write
24-09 FM Alarm HandlingRead and write
24-10 Drive Bypass FunctionRead and write
24-11 Drive Bypass Delay TimesRead and write
24-90 Missing Motor FunctionRead and write
24-91 Missing Motor Coefficient 1Read and write
24-92 Missing Motor Coefficient 2Read and write
24-93 Missing Motor Coefficient 3Read and write
24-94 Missing Motor Coefficient 4Read and write
24-95 Locked Rotor FunctionRead and write
24-96 Locked Rotor Coefficient 1Read and write
24-97 Locked Rotor Coefficient 2Read and write
24-98 Locked Rotor Coefficient 3Read and write
24-99 Locked Rotor Coefficient 4Read and write
30-22 Locked Rotor ProtectionRead and write
30-23 Locked Rotor Detection Time [s]sRead and write
30-58 LockPasswordRead and write
15-01 Running HourshRead
15-02 kWh CounterkWhRead
15-03 Power Up'sRead
15-04 Over Temp'sRead
15-05 Overvolt'sRead
15-06 Reset kWh CounterRead and write
15-07 Reset Running Hours CounterRead and write
15-30 Alarm Log: Error CodeRead
15-31 InternalFaultReasonRead
15-32 Alarm Log: TimesRead
15-40 FC TypeRead
15-41 Power SectionRead
15-42 VoltageRead
15-43 Software VersionRead
15-44 Ordered TypeCodeRead
15-45 Actual Typecode StringRead
15-46 Drive Ordering NoRead
15-48 LCP Id NoRead
15-49 SW ID Control CardRead
15-50 SW ID Power CardRead
15-51 Drive Serial NumberRead
15-52 OEM InformationRead
15-53 Power Card Serial NumberRead
15-57 File VersionRead
15-59 FilenameRead
15-92 Defined ParametersRead
15-97 Application TypeRead
15-98 Drive IdentificationRead
16-00 Control WordRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show output frequency, motor current and power of every fan and pump drive on a ModbusCloud dashboard.
  • Get an email alert when the alarm word is no longer 0 or the heat sink temperature passes a limit.
  • Keep 365 days of kWh counter and running hours history to compare consumption per fan or pump.
  • Change the PI setpoint of a pressure or temperature loop remotely without visiting the plant room.
  • Start, stop or change the speed of a fan from an automation on a time schedule or the energy price.

Installation

  1. Connect terminals 68 (P+) and 69 (N-) of the drive to RS485 A and B on the ModbusCloud Gateway and terminate the bus at both ends, on the drive with dip switch S801.

  2. Set 8-30 Protocol to Modbus RTU, then 8-31 Address, 8-32 Baud Rate and 8-33 Parity/Stop Bits.

  3. For control over Modbus, set 8-01 Control Site and 8-02 Control Source to the FC port, and 3-15 Reference 1 Source to Local bus reference.

  4. In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings, for example 1, 19200 baud, 8E1, and import this template.

  5. Check that output frequency and motor current match the display of the drive.

Things to watch for

The drive does not answer. What should I check?

Check that 8-30 is set to Modbus RTU and that address, baud rate and parity in 8-31 to 8-33 match the device in ModbusCloud. Changing the protocol can change the baud rate, so check 8-32 again. Then swap A and B and check the termination switch S801.

Why does a 32-bit value look wrong?

Many readouts, such as frequency, power and motor voltage, are 32-bit values over two registers with the high word first. The template reads them that way. If you read only the first register, you get the high word, which is usually 0.

How do I read one element of an array parameter?

Array parameters such as 3-10 Preset Reference or 5-40 Function Relay share one address. Write the index to holding register 9 first; all following reads and writes of array parameters then go to that element.

What should I keep in mind when writing parameters or the control word?

Coil 65 decides whether parameter writes go to RAM only (0) or also to EEPROM (1); keep it at 0 for values you change often. The control word and bus reference only act when 8-01, 8-02 and 3-15 allow it. Change motor data and limits only when you know the installation.

Want to see how it works?