Danfoss VLT HVAC Drive FC 102 Option Modules
Option parameters of the VLT HVAC Drive FC 102, as an addition to the drive template.
The Danfoss VLT HVAC Drive FC 102 takes options for fieldbus, extra analog and digital I/O, a bypass and temperature sensors, and has pressure sensor functions for filter monitoring in air handling units. This Modbus RTU template holds those option parameters, so you can read their status and change their settings from ModbusCloud next to the drive template.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 300, read and write
- Brand
- Danfoss
- Key readings
- Filter pressure sensors 1 to 4 · Current specific fan power · Filter running hours and costs · Bypass status and running hours · Fieldbus warning words
- Available commands
- Pressure thresholds per filter · Filter replacement settings · Bypass mode and delays · Extra analog and digital I/O · Fieldbus settings
- Compatible models
- VLT HVAC Drive FC 102
- Last updated
Registers (300)
300 read, 211 write
| Name | Unit | Access | Address (Hidden until you confirm your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Setpoint | Read | ||||
| Actual Value | Read | ||||
| PCD Write Configuration | Read and write | ||||
| PCD Read Configuration | Read and write | ||||
| Node Address | Read and write | ||||
| Telegram Selection | Read and write | ||||
| Parameters for Signals | Read | ||||
| Parameter Edit | Read and write | ||||
| Process Control | Read and write | ||||
| Fault Message Counter | Read | ||||
| Fault Code | Read | ||||
| Fault Number | Read | ||||
| Fault Situation Counter | Read and write | ||||
| PROFIBUS Warning Word | Read | ||||
| Actual Baud Rate | Read | ||||
| Device Identification | Read | ||||
| Profile Number | Read | ||||
| Control Word 1 | Read | ||||
| Status Word 1 | Read | ||||
| Programming Set-up | Read and write | ||||
| PROFIBUS Save Data Value | Read and write | ||||
| PROFIBUSDriveReset | Read and write | ||||
| Defined Parameters (1) | Read | ||||
| Defined Parameters (2) | Read | ||||
| Defined Parameters (3) | Read | ||||
| Defined Parameters (4) | Read | ||||
| Defined Parameters (5) | Read | ||||
| Defined Parameters (6) | Read | ||||
| Changed Parameters (1) | Read | ||||
| Changed Parameters (2) | Read | ||||
| Changed Parameters (4) | Read | ||||
| Changed Parameters (5) | Read | ||||
| PROFIBUS Revision Counter | Read | ||||
| CAN Protocol | Read and write | ||||
| Baud Rate Select | Read and write | ||||
| MAC ID | Read and write | ||||
| Readout Transmit Error Counter | Read | ||||
| Readout Receive Error Counter | Read | ||||
| Readout Bus Off Counter | Read | ||||
| Process Data Type Selection | Read and write | ||||
| Process Data Config Write 10-11 | Read and write | ||||
| Process Data Config Read 10-12 | Read and write | ||||
| Warning Parameter 10-13 | Read | ||||
| Net Reference 10-14 | Read and write | ||||
| Net Control 10-15 | Read and write | ||||
| COS Filter 1 | Read and write | ||||
| COS Filter 2 | Read and write | ||||
| COS Filter 3 | Read and write | ||||
| COS Filter 4 | Read and write | ||||
| Array Index | Read and write | ||||
| Store Data Value | Read and write | ||||
| Devicenet Revision | Read | ||||
| Store Always 10-33 | Read and write | ||||
| DeviceNet Product Code | Read and write | ||||
| Devicenet F Parameters | Read | ||||
| Neuron ID | Read | ||||
| Drive Profile | Read and write | ||||
| LON Warning Word | Read | ||||
| XIF Revision | Read | ||||
| LonWorks Revision | Read | ||||
| Store Data Values 11-21 | Read and write | ||||
| IP Address Assignment | Read and write | ||||
| IP Address | Read and write | ||||
| Subnet Mask | Read and write | ||||
| Default Gateway | Read and write | ||||
| DHCP Server | Read and write | ||||
| Lease Expires | Read | ||||
| Name Servers | Read and write | ||||
| Domain Name | Read and write | ||||
| Host Name | Read and write | ||||
| Physical Address | Read and write | ||||
| Link Status | Read | ||||
| Link Duration | Read | ||||
| Auto Negotiation | Read and write | ||||
| Link Speed | Read and write | ||||
| Link Duplex | Read and write | ||||
| Supervisor MAC | Read and write | ||||
| Supervisor IP Addr. | Read and write | ||||
| Control Instance | Read and write | ||||
| Process Data Config Write 12-21 | Read and write | ||||
| Process Data Config Read 12-22 | Read and write | ||||
| Primary Master | Read and write | ||||
| Store Data Values 12-28 | Read and write | ||||
| Store Always 12-29 | Read and write | ||||
| Warning Parameter 12-30 | Read | ||||
| Net Reference 12-31 | Read and write | ||||
| Net Control 12-32 | Read and write | ||||
| CIP Revision | Read | ||||
| CIP Product Code | Read and write | ||||
| EDS Parameter | Read | ||||
| COS Inhibit Timer | Read and write | ||||
| COS Filter | Read and write | ||||
| Status Parameter | Read | ||||
| Slave Message Count | Read | ||||
| Slave Exception Message Count | Read | ||||
| Ethernet Extended Status | Read and write | ||||
| FTP Server | Read and write | ||||
| HTTP Server | Read and write | ||||
| SMTP Service | Read and write | ||||
| SNMP Agent | Read and write | ||||
| Address Conflict Detection | Read and write | ||||
| ACD Last Conflict | Read and write | ||||
| NTP Host Server | Read and write | ||||
| SNTP Time Sync | min | Read and write | |||
| Transparent Socket Channel Port | Read and write | ||||
| Cable Diagnostics | Read and write | ||||
| Auto Cross Over | Read and write | ||||
| IGMP Snooping | Read and write | ||||
| Cable Error Length | Read and write | ||||
| Broadcast Storm Protection | % | Read and write | |||
| Inactivity Timeout | Read and write | ||||
| Port Config | Read and write | ||||
| QoS Priority | Read and write | ||||
| Interface Counters | Read | ||||
| Media Counters | Read | ||||
| Terminal X42/1 Mode | Read and write | ||||
| Terminal X42/3 Mode | Read and write | ||||
| Terminal X42/5 Mode | Read and write | ||||
| Terminal X42/1 Low Voltage | V | Read and write | |||
| Terminal X42/1 High Voltage | V | Read and write | |||
| Term. X42/1 Low Ref./Feedb. Value | Read and write | ||||
| Term. X42/1 High Ref./Feedb. Value | Read and write | ||||
| Term. X42/1 Filter Time Constant | s | Read and write | |||
| Term. X42/1 Live Zero | Read and write | ||||
| Terminal X42/3 Low Voltage | V | Read and write | |||
| Terminal X42/3 High Voltage | V | Read and write | |||
| Term. X42/3 Low Ref./Feedb. Value | Read and write | ||||
| Term. X42/3 High Ref./Feedb. Value | Read and write | ||||
| Term. X42/3 Filter Time Constant | s | Read and write | |||
| Term. X42/3 Live Zero | Read and write | ||||
| Terminal X42/5 Low Voltage | V | Read and write | |||
| Terminal X42/5 High Voltage | V | Read and write | |||
| Term. X42/5 Low Ref./Feedb. Value | Read and write | ||||
| Term. X42/5 High Ref./Feedb. Value | Read and write | ||||
| Term. X42/5 Filter Time Constant | s | Read and write | |||
| Term. X42/5 Live Zero | Read and write | ||||
| Terminal X42/7 Output | Read and write | ||||
| Terminal X42/7 Min. Scale | % | Read and write | |||
| Terminal X42/7 Max. Scale | % | Read and write | |||
| Terminal X42/7 Bus Control | % | Read and write | |||
| Terminal X42/7 Timeout Preset | % | Read and write | |||
| Terminal X42/9 Output | Read and write | ||||
| Terminal X42/9 Min. Scale | % | Read and write | |||
| Terminal X42/9 Max. Scale | % | Read and write | |||
| Terminal X42/9 Bus Control | % | Read and write | |||
| Terminal X42/9 Timeout Preset | % | Read and write | |||
| Terminal X42/11 Output | Read and write | ||||
| Terminal X42/11 Min. Scale | % | Read and write | |||
| Terminal X42/11 Max. Scale | % | Read and write | |||
| Terminal X42/11 Bus Control | % | Read and write | |||
| Terminal X42/11 Timeout Preset | % | Read and write | |||
| Bypass Mode | Read and write | ||||
| Bypass Start Time Delay | s | Read and write | |||
| Bypass Trip Time Delay | s | Read and write | |||
| Test Mode Activation | Read and write | ||||
| Bypass Status Word | Read | ||||
| Bypass Running Hours | h | Read | |||
| Remote Bypass Activation | Read and write | ||||
| Pressure/Speed Curve Adjustment | Read and write | ||||
| Below Level Threshold | Read and write | ||||
| Above Level Threshold W1 | Read and write | ||||
| On Delay Time | s | Read and write | |||
| Reset Delay Time | s | Read and write | |||
| Pressure Filter Time Constant | s | Read and write | |||
| Pressure Sensor 1 | Read | ||||
| Pressure Sensor 2 | Read | ||||
| Pressure Sensor 3 | Read | ||||
| Pressure Sensor 4 | Read | ||||
| Press Sens Cmp State | Read | ||||
| Press Sens Toggle | Read | ||||
| Toggled Readout Configuration | Read and write | ||||
| Toggled Readout Text | Read and write | ||||
| Pressure Range | Read and write | ||||
| Pressure Source | Read and write | ||||
| Bus Feedback Pressure 1 | Read and write | ||||
| Bus Feedback Pressure 2 | Read and write | ||||
| Bus Feedback Pressure 3 | Read and write | ||||
| Bus Feedback Pressure 4 | Read and write | ||||
| Above Level Threshold W2 | Read and write | ||||
| Pressure Warning W2 | Read | ||||
| Filter Monitoring Preference | Read and write | ||||
| Normal Air Flow | Read and write | ||||
| Min Limit Monitoring | % | Read and write | |||
| Current Specific Fan Power | Read | ||||
| Nominal SFP Trigger | Read and write | ||||
| Captured Air Flow | Read and write | ||||
| Nominal Specific Fan Power | Read and write | ||||
| Nominal Pressure Sensor 1 | Read | ||||
| Nominal Pressure Sensor 2 | Read | ||||
| Nominal Pressure Sensor 3 | Read | ||||
| Nominal Pressure Sensor 4 | Read | ||||
| Nominal SFP History | Read and write | ||||
| SFP Threshold W1 | % | Read and write | |||
| SFP Threshold W2 | % | Read and write | |||
| Filter Replacement Cost | Read and write | ||||
| Cost Per KWH Energy | Read and write | ||||
| Differential Energy Cost | Read and write | ||||
| Differential KWh Counter | kWh | Read | |||
| Reset Function | Read and write | ||||
| Differential Energy Cost Per Day | Read | ||||
| Replacement Days | Read | ||||
| Energy Reset Date | Read | ||||
| Energy Running Hours | h | Read | |||
| Filter Reset Date | Read | ||||
| Filter Running Hours | h | Read | |||
| PCD 1 Write to MCO | Read | ||||
| PCD 2 Write to MCO | Read | ||||
| PCD 3 Write to MCO | Read | ||||
| PCD 4 Write to MCO | Read | ||||
| PCD 5 Write to MCO | Read | ||||
| PCD 6 Write to MCO | Read | ||||
| PCD 7 Write to MCO | Read | ||||
| PCD 8 Write to MCO | Read | ||||
| PCD 9 Write to MCO | Read | ||||
| PCD 10 Write to MCO | Read | ||||
| PCD 1 Read from MCO | Read | ||||
| PCD 2 Read from MCO | Read | ||||
| PCD 3 Read from MCO | Read | ||||
| PCD 4 Read from MCO | Read | ||||
| PCD 5 Read from MCO | Read | ||||
| PCD 6 Read from MCO | Read | ||||
| PCD 7 Read from MCO | Read | ||||
| PCD 8 Read from MCO | Read | ||||
| PCD 9 Read from MCO | Read | ||||
| PCD 10 Read from MCO | Read | ||||
| Term. X48/4 Temperature Unit | Read and write | ||||
| Term. X48/4 Input Type | Read | ||||
| Term. X48/7 Temperature Unit | Read and write | ||||
| Term. X48/7 Input Type | Read | ||||
| Term. X48/10 Temperature Unit | Read and write | ||||
| Term. X48/10 Input Type | Read | ||||
| Temperature Sensor Alarm Function | Read and write | ||||
| Term. X48/4 Filter Time Constant | s | Read and write | |||
| Term. X48/4 Temp. Monitor | Read and write | ||||
| Term. X48/4 Low Temp. Limit | Read and write | ||||
| Term. X48/4 High Temp. Limit | Read and write | ||||
| Term. X48/7 Filter Time Constant | s | Read and write | |||
| Term. X48/7 Temp. Monitor | Read and write | ||||
| Term. X48/7 Low Temp. Limit | Read and write | ||||
| Term. X48/7 High Temp. Limit | Read and write | ||||
| Term. X48/10 Filter Time Constant | s | Read and write | |||
| Term. X48/10 Temp. Monitor | Read and write | ||||
| Term. X48/10 Low Temp. Limit | Read and write | ||||
| Term. X48/10 High Temp. Limit | Read and write | ||||
| Term. X48/2 Low Current | mA | Read and write | |||
| Term. X48/2 High Current | mA | Read and write | |||
| Term. 48/2 Low Ref./Feedb. Value | Read and write | ||||
| Term. 48/2 High Ref./Feedb. Value | Read and write | ||||
| Term. X48/2 Filter Time Constant | s | Read and write | |||
| Term. X48/10 Live Zero | Read and write | ||||
| Term. X49/1 Mode | Read and write | ||||
| Term. X49/3 Mode | Read and write | ||||
| Term. X49/5 Mode | Read and write | ||||
| Term. X49/7 Mode | Read and write | ||||
| Term. X49/9 Mode | Read and write | ||||
| Term. X49/11 Mode | Read and write | ||||
| Terminal X49/1 Low Voltage | V | Read and write | |||
| Terminal X49/1 Low Current | mA | Read and write | |||
| Terminal X49/1 High Voltage | V | Read and write | |||
| Terminal X49/1 High Current | mA | Read and write | |||
| Terminal X49/1 Low Ref./Feedb. Value | Read and write | ||||
| Terminal X49/1 High Ref./Feedb. Value | Read and write | ||||
| Term. X49/1 Filter Time Constant | s | Read and write | |||
| Term. X49/1 Live Zero | Read and write | ||||
| Terminal X49/3 Low Voltage | V | Read and write | |||
| Terminal X49/3 Low Current 36-21 | mA | Read and write | |||
| Terminal X49/3 High Voltage | V | Read and write | |||
| Terminal X49/3 High Current | mA | Read and write | |||
| Terminal X49/3 Low Ref./Feedb. Value | Read and write | ||||
| Terminal X49/3 High Ref./Feedb. Value | Read and write | ||||
| Term. X49/3 Filter Time Constant | s | Read and write | |||
| Term. X49/3 Live Zero | Read and write | ||||
| Terminal X49/5 Low Voltage | V | Read and write | |||
| Terminal X49/3 Low Current 36-31 | mA | Read and write | |||
| Terminal X49/5 High Voltage | V | Read and write | |||
| Terminal X49/5 High Current | mA | Read and write | |||
| Terminal X49/5 Low Ref./Feedb. Value | Read and write | ||||
| Terminal X49/5 High Ref./Feedb. Value | Read and write | ||||
| Term. X49/5 Filter Time Constant | s | Read and write | |||
| Term. X49/5 Live Zero | Read and write | ||||
| Terminal X49/7 Analogue Output | Read and write | ||||
| Terminal X49/7 Digital Output | Read and write | ||||
| Terminal X49/7 Min Scale | % | Read and write | |||
| Terminal X49/7 Max. Scale | % | Read and write | |||
| Terminal X49/7 Bus Ctrl | % | Read and write | |||
| Terminal X49/7 Timeout Preset | % | Read and write | |||
| Terminal X49/9 Analogue Output | Read and write | ||||
| Terminal X49/9 Digital Output | Read and write | ||||
| Terminal X49/9 Min. Scale | % | Read and write | |||
| Terminal X49/9 Max. Scale | % | Read and write | |||
| Terminal X49/9 Bus Ctrl | % | Read and write | |||
| Terminal X49/9 Timeout Preset | % | Read and write | |||
| Terminal X49/11 Analogue Output | Read and write | ||||
| Terminal X49/11 Digital Output | Read and write | ||||
| Terminal X49/11 Min. Scale | % | Read and write | |||
| Terminal X49/11 Max. Scale | % | Read and write | |||
| Terminal X49/11 Bus Ctrl | % | Read and write | |||
| Terminal X49/11 Timeout Preset | % | Read and write | |||
| Changed Parameters (3) | Read | ||||
| Array Index Pointer | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show the pressure across up to four filters of an air handling unit and the current specific fan power on a dashboard.
- Send an email when the bypass status word changes, so you know the drive was bypassed.
- Track filter running hours and the extra energy cost of a dirty filter to plan the replacement.
- Keep a history of the extra temperature inputs of the sensor input option.
Installation
Add the Danfoss VLT HVAC Drive FC 102 template as described there; this template uses the same RS485 connection, address and settings.
In ModbusCloud, add a second Modbus RTU device with the same address on the Gateway and import this template.
Delete the registers of options that are not fitted in your drive.
Check that the values of your options look plausible.
Things to watch for
Most registers return an error or 0.
The option card parameters only exist when the matching card is fitted in the drive, and the pressure sensor functions only give values when sensors are configured. Keep the registers you use and delete the rest from the device in ModbusCloud.
How do I find the register of a Danfoss parameter?
The register number is the parameter number times ten, so parameter 31-26 is register 31260 and address 31259 in the template. The parameter number is in the comment of each register.
Some array parameters always show the first value.
For array parameters the drive returns the element chosen in Array Index Pointer. Write the index you want there first, then read the array parameter.