Danfoss Danfoss VLT HVAC Drive FC 102 Option Modules Modbus RTU template

Danfoss VLT HVAC Drive FC 102 Option Modules

Option parameters of the VLT HVAC Drive FC 102, as an addition to the drive template.

The Danfoss VLT HVAC Drive FC 102 takes options for fieldbus, extra analog and digital I/O, a bypass and temperature sensors, and has pressure sensor functions for filter monitoring in air handling units. This Modbus RTU template holds those option parameters, so you can read their status and change their settings from ModbusCloud next to the drive template.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
300, read and write
Brand
Danfoss
Key readings
Filter pressure sensors 1 to 4 · Current specific fan power · Filter running hours and costs · Bypass status and running hours · Fieldbus warning words
Available commands
Pressure thresholds per filter · Filter replacement settings · Bypass mode and delays · Extra analog and digital I/O · Fieldbus settings
Compatible models
VLT HVAC Drive FC 102
Last updated

Registers (300)

300 read, 211 write

NameUnitAccessAddress (Hidden until you confirm your email)Function (hidden)Type (hidden)
SetpointRead
Actual ValueRead
PCD Write ConfigurationRead and write
PCD Read ConfigurationRead and write
Node AddressRead and write
Telegram SelectionRead and write
Parameters for SignalsRead
Parameter EditRead and write
Process ControlRead and write
Fault Message CounterRead
Fault CodeRead
Fault NumberRead
Fault Situation CounterRead and write
PROFIBUS Warning WordRead
Actual Baud RateRead
Device IdentificationRead
Profile NumberRead
Control Word 1Read
Status Word 1Read
Programming Set-upRead and write
PROFIBUS Save Data ValueRead and write
PROFIBUSDriveResetRead and write
Defined Parameters (1)Read
Defined Parameters (2)Read
Defined Parameters (3)Read
Defined Parameters (4)Read
Defined Parameters (5)Read
Defined Parameters (6)Read
Changed Parameters (1)Read
Changed Parameters (2)Read
Changed Parameters (4)Read
Changed Parameters (5)Read
PROFIBUS Revision CounterRead
CAN ProtocolRead and write
Baud Rate SelectRead and write
MAC IDRead and write
Readout Transmit Error CounterRead
Readout Receive Error CounterRead
Readout Bus Off CounterRead
Process Data Type SelectionRead and write
Process Data Config Write 10-11Read and write
Process Data Config Read 10-12Read and write
Warning Parameter 10-13Read
Net Reference 10-14Read and write
Net Control 10-15Read and write
COS Filter 1Read and write
COS Filter 2Read and write
COS Filter 3Read and write
COS Filter 4Read and write
Array IndexRead and write
Store Data ValueRead and write
Devicenet RevisionRead
Store Always 10-33Read and write
DeviceNet Product CodeRead and write
Devicenet F ParametersRead
Neuron IDRead
Drive ProfileRead and write
LON Warning WordRead
XIF RevisionRead
LonWorks RevisionRead
Store Data Values 11-21Read and write
IP Address AssignmentRead and write
IP AddressRead and write
Subnet MaskRead and write
Default GatewayRead and write
DHCP ServerRead and write
Lease ExpiresRead
Name ServersRead and write
Domain NameRead and write
Host NameRead and write
Physical AddressRead and write
Link StatusRead
Link DurationRead
Auto NegotiationRead and write
Link SpeedRead and write
Link DuplexRead and write
Supervisor MACRead and write
Supervisor IP Addr.Read and write
Control InstanceRead and write
Process Data Config Write 12-21Read and write
Process Data Config Read 12-22Read and write
Primary MasterRead and write
Store Data Values 12-28Read and write
Store Always 12-29Read and write
Warning Parameter 12-30Read
Net Reference 12-31Read and write
Net Control 12-32Read and write
CIP RevisionRead
CIP Product CodeRead and write
EDS ParameterRead
COS Inhibit TimerRead and write
COS FilterRead and write
Status ParameterRead
Slave Message CountRead
Slave Exception Message CountRead
Ethernet Extended StatusRead and write
FTP ServerRead and write
HTTP ServerRead and write
SMTP ServiceRead and write
SNMP AgentRead and write
Address Conflict DetectionRead and write
ACD Last ConflictRead and write
NTP Host ServerRead and write
SNTP Time SyncminRead and write
Transparent Socket Channel PortRead and write
Cable DiagnosticsRead and write
Auto Cross OverRead and write
IGMP SnoopingRead and write
Cable Error LengthRead and write
Broadcast Storm Protection%Read and write
Inactivity TimeoutRead and write
Port ConfigRead and write
QoS PriorityRead and write
Interface CountersRead
Media CountersRead
Terminal X42/1 ModeRead and write
Terminal X42/3 ModeRead and write
Terminal X42/5 ModeRead and write
Terminal X42/1 Low VoltageVRead and write
Terminal X42/1 High VoltageVRead and write
Term. X42/1 Low Ref./Feedb. ValueRead and write
Term. X42/1 High Ref./Feedb. ValueRead and write
Term. X42/1 Filter Time ConstantsRead and write
Term. X42/1 Live ZeroRead and write
Terminal X42/3 Low VoltageVRead and write
Terminal X42/3 High VoltageVRead and write
Term. X42/3 Low Ref./Feedb. ValueRead and write
Term. X42/3 High Ref./Feedb. ValueRead and write
Term. X42/3 Filter Time ConstantsRead and write
Term. X42/3 Live ZeroRead and write
Terminal X42/5 Low VoltageVRead and write
Terminal X42/5 High VoltageVRead and write
Term. X42/5 Low Ref./Feedb. ValueRead and write
Term. X42/5 High Ref./Feedb. ValueRead and write
Term. X42/5 Filter Time ConstantsRead and write
Term. X42/5 Live ZeroRead and write
Terminal X42/7 OutputRead and write
Terminal X42/7 Min. Scale%Read and write
Terminal X42/7 Max. Scale%Read and write
Terminal X42/7 Bus Control%Read and write
Terminal X42/7 Timeout Preset%Read and write
Terminal X42/9 OutputRead and write
Terminal X42/9 Min. Scale%Read and write
Terminal X42/9 Max. Scale%Read and write
Terminal X42/9 Bus Control%Read and write
Terminal X42/9 Timeout Preset%Read and write
Terminal X42/11 OutputRead and write
Terminal X42/11 Min. Scale%Read and write
Terminal X42/11 Max. Scale%Read and write
Terminal X42/11 Bus Control%Read and write
Terminal X42/11 Timeout Preset%Read and write
Bypass ModeRead and write
Bypass Start Time DelaysRead and write
Bypass Trip Time DelaysRead and write
Test Mode ActivationRead and write
Bypass Status WordRead
Bypass Running HourshRead
Remote Bypass ActivationRead and write
Pressure/Speed Curve AdjustmentRead and write
Below Level ThresholdRead and write
Above Level Threshold W1Read and write
On Delay TimesRead and write
Reset Delay TimesRead and write
Pressure Filter Time ConstantsRead and write
Pressure Sensor 1Read
Pressure Sensor 2Read
Pressure Sensor 3Read
Pressure Sensor 4Read
Press Sens Cmp StateRead
Press Sens ToggleRead
Toggled Readout ConfigurationRead and write
Toggled Readout TextRead and write
Pressure RangeRead and write
Pressure SourceRead and write
Bus Feedback Pressure 1Read and write
Bus Feedback Pressure 2Read and write
Bus Feedback Pressure 3Read and write
Bus Feedback Pressure 4Read and write
Above Level Threshold W2Read and write
Pressure Warning W2Read
Filter Monitoring PreferenceRead and write
Normal Air FlowRead and write
Min Limit Monitoring%Read and write
Current Specific Fan PowerRead
Nominal SFP TriggerRead and write
Captured Air FlowRead and write
Nominal Specific Fan PowerRead and write
Nominal Pressure Sensor 1Read
Nominal Pressure Sensor 2Read
Nominal Pressure Sensor 3Read
Nominal Pressure Sensor 4Read
Nominal SFP HistoryRead and write
SFP Threshold W1%Read and write
SFP Threshold W2%Read and write
Filter Replacement CostRead and write
Cost Per KWH EnergyRead and write
Differential Energy CostRead and write
Differential KWh CounterkWhRead
Reset FunctionRead and write
Differential Energy Cost Per DayRead
Replacement DaysRead
Energy Reset DateRead
Energy Running HourshRead
Filter Reset DateRead
Filter Running HourshRead
PCD 1 Write to MCORead
PCD 2 Write to MCORead
PCD 3 Write to MCORead
PCD 4 Write to MCORead
PCD 5 Write to MCORead
PCD 6 Write to MCORead
PCD 7 Write to MCORead
PCD 8 Write to MCORead
PCD 9 Write to MCORead
PCD 10 Write to MCORead
PCD 1 Read from MCORead
PCD 2 Read from MCORead
PCD 3 Read from MCORead
PCD 4 Read from MCORead
PCD 5 Read from MCORead
PCD 6 Read from MCORead
PCD 7 Read from MCORead
PCD 8 Read from MCORead
PCD 9 Read from MCORead
PCD 10 Read from MCORead
Term. X48/4 Temperature UnitRead and write
Term. X48/4 Input TypeRead
Term. X48/7 Temperature UnitRead and write
Term. X48/7 Input TypeRead
Term. X48/10 Temperature UnitRead and write
Term. X48/10 Input TypeRead
Temperature Sensor Alarm FunctionRead and write
Term. X48/4 Filter Time ConstantsRead and write
Term. X48/4 Temp. MonitorRead and write
Term. X48/4 Low Temp. LimitRead and write
Term. X48/4 High Temp. LimitRead and write
Term. X48/7 Filter Time ConstantsRead and write
Term. X48/7 Temp. MonitorRead and write
Term. X48/7 Low Temp. LimitRead and write
Term. X48/7 High Temp. LimitRead and write
Term. X48/10 Filter Time ConstantsRead and write
Term. X48/10 Temp. MonitorRead and write
Term. X48/10 Low Temp. LimitRead and write
Term. X48/10 High Temp. LimitRead and write
Term. X48/2 Low CurrentmARead and write
Term. X48/2 High CurrentmARead and write
Term. 48/2 Low Ref./Feedb. ValueRead and write
Term. 48/2 High Ref./Feedb. ValueRead and write
Term. X48/2 Filter Time ConstantsRead and write
Term. X48/10 Live ZeroRead and write
Term. X49/1 ModeRead and write
Term. X49/3 ModeRead and write
Term. X49/5 ModeRead and write
Term. X49/7 ModeRead and write
Term. X49/9 ModeRead and write
Term. X49/11 ModeRead and write
Terminal X49/1 Low VoltageVRead and write
Terminal X49/1 Low CurrentmARead and write
Terminal X49/1 High VoltageVRead and write
Terminal X49/1 High CurrentmARead and write
Terminal X49/1 Low Ref./Feedb. ValueRead and write
Terminal X49/1 High Ref./Feedb. ValueRead and write
Term. X49/1 Filter Time ConstantsRead and write
Term. X49/1 Live ZeroRead and write
Terminal X49/3 Low VoltageVRead and write
Terminal X49/3 Low Current 36-21mARead and write
Terminal X49/3 High VoltageVRead and write
Terminal X49/3 High CurrentmARead and write
Terminal X49/3 Low Ref./Feedb. ValueRead and write
Terminal X49/3 High Ref./Feedb. ValueRead and write
Term. X49/3 Filter Time ConstantsRead and write
Term. X49/3 Live ZeroRead and write
Terminal X49/5 Low VoltageVRead and write
Terminal X49/3 Low Current 36-31mARead and write
Terminal X49/5 High VoltageVRead and write
Terminal X49/5 High CurrentmARead and write
Terminal X49/5 Low Ref./Feedb. ValueRead and write
Terminal X49/5 High Ref./Feedb. ValueRead and write
Term. X49/5 Filter Time ConstantsRead and write
Term. X49/5 Live ZeroRead and write
Terminal X49/7 Analogue OutputRead and write
Terminal X49/7 Digital OutputRead and write
Terminal X49/7 Min Scale%Read and write
Terminal X49/7 Max. Scale%Read and write
Terminal X49/7 Bus Ctrl%Read and write
Terminal X49/7 Timeout Preset%Read and write
Terminal X49/9 Analogue OutputRead and write
Terminal X49/9 Digital OutputRead and write
Terminal X49/9 Min. Scale%Read and write
Terminal X49/9 Max. Scale%Read and write
Terminal X49/9 Bus Ctrl%Read and write
Terminal X49/9 Timeout Preset%Read and write
Terminal X49/11 Analogue OutputRead and write
Terminal X49/11 Digital OutputRead and write
Terminal X49/11 Min. Scale%Read and write
Terminal X49/11 Max. Scale%Read and write
Terminal X49/11 Bus Ctrl%Read and write
Terminal X49/11 Timeout Preset%Read and write
Changed Parameters (3)Read
Array Index PointerRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the pressure across up to four filters of an air handling unit and the current specific fan power on a dashboard.
  • Send an email when the bypass status word changes, so you know the drive was bypassed.
  • Track filter running hours and the extra energy cost of a dirty filter to plan the replacement.
  • Keep a history of the extra temperature inputs of the sensor input option.

Installation

  1. Add the Danfoss VLT HVAC Drive FC 102 template as described there; this template uses the same RS485 connection, address and settings.

  2. In ModbusCloud, add a second Modbus RTU device with the same address on the Gateway and import this template.

  3. Delete the registers of options that are not fitted in your drive.

  4. Check that the values of your options look plausible.

Things to watch for

Most registers return an error or 0.

The option card parameters only exist when the matching card is fitted in the drive, and the pressure sensor functions only give values when sensors are configured. Keep the registers you use and delete the rest from the device in ModbusCloud.

How do I find the register of a Danfoss parameter?

The register number is the parameter number times ten, so parameter 31-26 is register 31260 and address 31259 in the template. The parameter number is in the comment of each register.

Some array parameters always show the first value.

For array parameters the drive returns the element chosen in Array Index Pointer. Write the index you want there first, then read the array parameter.