Danfoss VLT Refrigeration Drive FC 103
Frequency converter for refrigeration compressors and condenser fans with pack control.
The Danfoss VLT Refrigeration Drive FC 103 is a frequency converter that controls compressors, condenser fans and pumps in commercial and industrial refrigeration. This Modbus RTU template reads frequency, current, power, temperatures, suction pressure and alarms, and lets you start, stop and adjust speed and setpoints from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 878, read and write
- Brand
- Danfoss
- Key readings
- Output frequency · Motor current · Power · Motor voltage · DC link voltage · Heatsink temperature · Suction pressure P0 · Alarm and warning words
- Available commands
- Start and stop · Speed reference · P0 setpoint · Setpoints 1 to 3 · Ramp times · Pack controller settings
- Compatible models
- VLT Refrigeration Drive FC 103 · VLT Refrigeration Drive FC 103 1.1 to 90 kW · VLT Refrigeration Drive FC 103 110 to 800 kW
- Last updated
Registers (878)
844 read, 686 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Frequency | Hz | Read | |||
| Motor Current | A | Read | |||
| Power [kW] | kW | Read | |||
| Motor Voltage | V | Read | |||
| Speed [RPM] | rpm | Read | |||
| Torque [Nm] | Nm | Read | |||
| Torque [%] | % | Read | |||
| DC Link Voltage | V | Read | |||
| Heatsink Temp. | °C | Read | |||
| Control Card Temp. | °C | Read | |||
| Motor Thermal | % | Read | |||
| Inverter Thermal | % | Read | |||
| Reference | Read | ||||
| Reference [%] | % | Read | |||
| Main Actual Value [%] | % | Read | |||
| Feedback | Read | ||||
| Feedback 1 | Read | ||||
| Feedback 2 | Read | ||||
| Feedback 3 | Read | ||||
| Discharge Temperature | Read | ||||
| P0 | K | Read | |||
| P0 Setpoint | K | Read and write | |||
| P0 Reference | K | Read | |||
| Monitor 1 Pressure 1 | Read | ||||
| Monitor 2 Pressure 2 | Read | ||||
| Pack Capacity [%] | % | Read | |||
| Pack Status | Read | ||||
| Compressor Status | Read | ||||
| Lead Compressor | Read | ||||
| Relay Status | Read | ||||
| Compressor ON Time | h | Read | |||
| Relay ON Time | h | Read | |||
| Alarm Word | Read | ||||
| Alarm Word 2 | Read | ||||
| Warning Word | Read | ||||
| Warning Word 2 | Read | ||||
| Ext. Status Word | Read | ||||
| Ext. Status Word 2 | Read | ||||
| Maintenance Word | Read | ||||
| Ext. Status Word 3 | Read | ||||
| Control Word | Read | ||||
| Status Word | Read | ||||
| Operating Hours | h | Read | |||
| Running Hours | h | Read | |||
| kWh Counter | kWh | Read | |||
| Power Up's | Read | ||||
| Over Temp's | Read | ||||
| Over Volt's | Read | ||||
| Number of Starts | Read | ||||
| Fan Running Hours | h | Read | |||
| Status Coil Control Ready | Read | ||||
| Status Coil Drive Ready | Read | ||||
| Status Coil Coasting Stop or Safety Closed | Read | ||||
| Status Coil Alarm | Read | ||||
| Status Coil Bit 04 | Read | ||||
| Status Coil Bit 05 | Read | ||||
| Status Coil Bit 06 | Read | ||||
| Status Coil Warning | Read | ||||
| Status Coil At Reference | Read | ||||
| Status Coil Auto Mode | Read | ||||
| Status Coil In Frequency Range | Read | ||||
| Status Coil Running | Read | ||||
| Status Coil Bit 12 | Read | ||||
| Status Coil Voltage Warning | Read | ||||
| Status Coil Current Limit | Read | ||||
| Status Coil Thermal Warning | Read | ||||
| Actual Value Coil Bit 0 | Read | ||||
| Actual Value Coil Bit 1 | Read | ||||
| Actual Value Coil Bit 2 | Read | ||||
| Actual Value Coil Bit 3 | Read | ||||
| Actual Value Coil Bit 4 | Read | ||||
| Actual Value Coil Bit 5 | Read | ||||
| Actual Value Coil Bit 6 | Read | ||||
| Actual Value Coil Bit 7 | Read | ||||
| Actual Value Coil Bit 8 | Read | ||||
| Actual Value Coil Bit 9 | Read | ||||
| Actual Value Coil Bit 10 | Read | ||||
| Actual Value Coil Bit 11 | Read | ||||
| Actual Value Coil Bit 12 | Read | ||||
| Actual Value Coil Bit 13 | Read | ||||
| Actual Value Coil Bit 14 | Read | ||||
| Actual Value Coil Bit 15 | Read | ||||
| Bus Status Word | Read | ||||
| Main Actual Value | Read | ||||
| Last Error Code | Read | ||||
| Control Coil Preset Reference LSB | Write | ||||
| Control Coil Preset Reference MSB | Write | ||||
| Control Coil DC Brake | Write | ||||
| Control Coil Coast Stop | Write | ||||
| Control Coil Quick Stop | Write | ||||
| Control Coil Freeze Frequency | Write | ||||
| Control Coil Ramp Stop or Start | Write | ||||
| Control Coil Reset | Write | ||||
| Control Coil Jog | Write | ||||
| Control Coil Ramp 1 or 2 | Write | ||||
| Control Coil Data Valid | Write | ||||
| Control Coil Relay 1 | Write | ||||
| Control Coil Relay 2 | Write | ||||
| Control Coil Set-up LSB | Write | ||||
| Control Coil Set-up MSB | Write | ||||
| Control Coil Reversing | Write | ||||
| Reference Coil Bit 0 | Write | ||||
| Reference Coil Bit 1 | Write | ||||
| Reference Coil Bit 2 | Write | ||||
| Reference Coil Bit 3 | Write | ||||
| Reference Coil Bit 4 | Write | ||||
| Reference Coil Bit 5 | Write | ||||
| Reference Coil Bit 6 | Write | ||||
| Reference Coil Bit 7 | Write | ||||
| Reference Coil Bit 8 | Write | ||||
| Reference Coil Bit 9 | Write | ||||
| Reference Coil Bit 10 | Write | ||||
| Reference Coil Bit 11 | Write | ||||
| Reference Coil Bit 12 | Write | ||||
| Reference Coil Bit 13 | Write | ||||
| Reference Coil Bit 14 | Write | ||||
| Reference Coil Bit 15 | Write | ||||
| Parameter Write Control | Read and write | ||||
| Bus Control Word | Write | ||||
| Bus Reference | Write | ||||
| Array Index Pointer | Read and write | ||||
| Language | Read and write | ||||
| Motor Speed Unit | Read and write | ||||
| Regional Settings | Read and write | ||||
| Operating State at Power-up | Read and write | ||||
| Local Mode Unit | Read and write | ||||
| Active Set-up | Read and write | ||||
| Programming Set-up | Read and write | ||||
| This Set-up Linked to | Read and write | ||||
| Readout: Linked Set-ups | Read and write | ||||
| Readout: Prog. Set-ups / Channel | Read and write | ||||
| Display Line 1.1 Small | Read and write | ||||
| Display Line 1.2 Small | Read and write | ||||
| Display Line 1.3 Small | Read and write | ||||
| Display Line 2 Large | Read and write | ||||
| Display Line 3 Large | Read and write | ||||
| My Personal Menu | Read and write | ||||
| Custom Readout Unit | Read and write | ||||
| Custom Readout Min Value | Read and write | ||||
| Custom Readout Max Value | Read and write | ||||
| Display Text 1 | Read and write | ||||
| Display Text 2 | Read and write | ||||
| Display Text 3 | Read and write | ||||
| [Hand On] Key on LCP | Read and write | ||||
| [Off] Key on LCP | Read and write | ||||
| [Auto On] Key on LCP | Read and write | ||||
| [Reset] Key on LCP | Read and write | ||||
| LCP Copy | Read and write | ||||
| Set-up Copy | Read and write | ||||
| Main Menu Password | Read and write | ||||
| Access to Main Menu w/o Password | Read and write | ||||
| Personal Menu Password | Read and write | ||||
| Access to Personal Menu w/o Password | Read and write | ||||
| Bus Password Access | Read and write | ||||
| Set Date and Time | Read and write | ||||
| Date Format | Read and write | ||||
| Time Format | Read and write | ||||
| DST/Summertime | Read and write | ||||
| DST/Summertime Start | Read and write | ||||
| DST/Summertime End | Read and write | ||||
| Clock Fault | Read and write | ||||
| Working Days | Read and write | ||||
| Additional Working Days | Read and write | ||||
| Additional Non-Working Days | Read and write | ||||
| Date and Time Readout | Read | ||||
| Configuration Mode | Read and write | ||||
| Torque Characteristics | Read and write | ||||
| Clockwise Direction | Read and write | ||||
| Motor Construction | Read and write | ||||
| Damping Gain | % | Read and write | |||
| Low Speed Filter Time Const. | Read and write | ||||
| High Speed Filter Time Const. | Read and write | ||||
| Voltage Filter Time Const. | Read and write | ||||
| Motor Power [kW] | kW | Read and write | |||
| Motor Power [HP] | Read and write | ||||
| Motor Voltage (1-22) | Read and write | ||||
| Motor Frequency | Read and write | ||||
| Motor Current (1-24) | Read and write | ||||
| Motor Nominal Speed | Read and write | ||||
| Motor Cont. Rated Torque | Read and write | ||||
| Motor Rotation Check | Read and write | ||||
| Automatic Motor Adaptation (AMA) | Read and write | ||||
| Stator Resistance (Rs) | Read and write | ||||
| Rotor Resistance (Rr) | Read and write | ||||
| Main Reactance (Xh) | Read and write | ||||
| Iron Loss Resistance (Rfe) | Read and write | ||||
| D-axis Inductance (Ld) | Read and write | ||||
| Q-axis Inductance (Lq) | Read and write | ||||
| Motor Poles | Read and write | ||||
| Back EMF at 1000 RPM | Read and write | ||||
| Motor Angle Offset | Read and write | ||||
| D-axis Inductance Sat. (LdSat) | Read and write | ||||
| Q-axis Inductance Sat. (LqSat) | Read and write | ||||
| Position Detection Gain | % | Read and write | |||
| Torque Calibration | Read and write | ||||
| Inductance Sat. Point | Read and write | ||||
| Motor Magnetisation at Zero Speed | % | Read and write | |||
| Min Speed Normal Magnetising [RPM] | rpm | Read and write | |||
| Min Speed Normal Magnetising [Hz] | Hz | Read and write | |||
| Flying Start Test Pulses Current | Read and write | ||||
| Flying Start Test Pulses Frequency | Read and write | ||||
| Low Speed Load Compensation | % | Read and write | |||
| High Speed Load Compensation | % | Read and write | |||
| Slip Compensation | % | Read and write | |||
| Slip Compensation Time Constant | Read and write | ||||
| Resonance Dampening | % | Read and write | |||
| Resonance Dampening Time Constant | ms | Read and write | |||
| Min. Current at Low Speed | Read and write | ||||
| PM Start Mode | Read and write | ||||
| Start Delay | s | Read and write | |||
| Start Function | Read and write | ||||
| Flying Start | Read and write | ||||
| Start Speed [RPM] | rpm | Read and write | |||
| Start Speed [Hz] | Hz | Read and write | |||
| Start Current | A | Read and write | |||
| Compressor Start Max Speed [RPM] | rpm | Read and write | |||
| Compressor Start Max Speed [Hz] | Hz | Read and write | |||
| Compressor Start Max Time to Trip | s | Read and write | |||
| Function at Stop | Read and write | ||||
| Min Speed for Function at Stop [RPM] | rpm | Read and write | |||
| Min Speed for Function at Stop [Hz] | Hz | Read and write | |||
| Compressor Min. Speed for Trip [RPM] | rpm | Read and write | |||
| Compressor Min. Speed for Trip [Hz] | Hz | Read and write | |||
| Motor Thermal Protection | Read and write | ||||
| Motor External Fan | Read and write | ||||
| Thermistor Source | Read and write | ||||
| DC Hold/Preheat Current | % | Read and write | |||
| DC Brake Current | % | Read and write | |||
| DC Braking Time | s | Read and write | |||
| DC Brake Cut In Speed [RPM] | rpm | Read and write | |||
| DC Brake Cut In Speed [Hz] | Hz | Read and write | |||
| Parking Current | % | Read and write | |||
| Parking Time | s | Read and write | |||
| Brake Function | Read and write | ||||
| AC Brake Max. Current | % | Read and write | |||
| Over-voltage Control | Read and write | ||||
| Minimum Reference | Read and write | ||||
| Maximum Reference | Read and write | ||||
| Reference Function | Read and write | ||||
| Preset Reference | % | Read and write | |||
| Jog Speed [Hz] | Hz | Read and write | |||
| Reference Site | Read and write | ||||
| Preset Relative Reference | % | Read and write | |||
| Reference 1 Source | Read and write | ||||
| Reference 2 Source | Read and write | ||||
| Reference 3 Source | Read and write | ||||
| Jog Speed [RPM] | rpm | Read and write | |||
| Ramp 1 Ramp Up Time | Read and write | ||||
| Ramp 1 Ramp Down Time | Read and write | ||||
| Ramp 2 Ramp Up Time | Read and write | ||||
| Ramp 2 Ramp Down Time | Read and write | ||||
| Jog Ramp Time | Read and write | ||||
| Quick Stop Ramp Time | Read and write | ||||
| Starting Ramp Up Time | Read and write | ||||
| Step Size | % | Read and write | |||
| Ramp Time | s | Read and write | |||
| Power Restore | Read and write | ||||
| Maximum Limit | % | Read and write | |||
| Minimum Limit | % | Read and write | |||
| Ramp Delay | Read and write | ||||
| Motor Speed Direction | Read and write | ||||
| Motor Speed Low Limit [RPM] | rpm | Read and write | |||
| Motor Speed Low Limit [Hz] | Hz | Read and write | |||
| Motor Speed High Limit [RPM] | rpm | Read and write | |||
| Motor Speed High Limit [Hz] | Hz | Read and write | |||
| Torque Limit Motor Mode | % | Read and write | |||
| Torque Limit Generator Mode | % | Read and write | |||
| Current Limit | Read and write | ||||
| Max Output Frequency | Read and write | ||||
| Warning Current Low | A | Read and write | |||
| Warning Current High | Read and write | ||||
| Warning Speed Low | rpm | Read and write | |||
| Warning Speed High | Read and write | ||||
| Warning Reference Low | Read and write | ||||
| Warning Reference High | Read and write | ||||
| Warning Feedback Low | Read and write | ||||
| Warning Feedback High | Read and write | ||||
| Missing Motor Phase Function | Read and write | ||||
| Motor Check At Start | Read and write | ||||
| Bypass Speed From [RPM] | rpm | Read and write | |||
| Bypass Speed From [Hz] | Hz | Read and write | |||
| Bypass Speed To [RPM] | rpm | Read and write | |||
| Bypass Speed To [Hz] | Hz | Read and write | |||
| Semi-Auto Bypass Set-up | Read and write | ||||
| Digital I/O Mode | Read and write | ||||
| Terminal 27 Mode | Read and write | ||||
| Terminal 29 Mode | Read and write | ||||
| Terminal 18 Digital Input | Read and write | ||||
| Terminal 19 Digital Input | Read and write | ||||
| Terminal 27 Digital Input | Read and write | ||||
| Terminal 29 Digital Input | Read and write | ||||
| Terminal 32 Digital Input | Read and write | ||||
| Terminal 33 Digital Input | Read and write | ||||
| Terminal X30/2 Digital Input | Read and write | ||||
| Terminal X30/3 Digital Input | Read and write | ||||
| Terminal X30/4 Digital Input | Read and write | ||||
| Terminal 37 Safe Stop | Read and write | ||||
| Terminal X46/1 Digital Input | Read and write | ||||
| Terminal X46/3 Digital Input | Read and write | ||||
| Terminal X46/5 Digital Input | Read and write | ||||
| Terminal X46/7 Digital Input | Read and write | ||||
| Terminal X46/9 Digital Input | Read and write | ||||
| Terminal X46/11 Digital Input | Read and write | ||||
| Terminal X46/13 Digital Input | Read and write | ||||
| Terminal 27 Digital Output | Read and write | ||||
| Terminal 29 Digital Output | Read and write | ||||
| Term X30/6 Digi Out (MCB 101) | Read and write | ||||
| Term X30/7 Digi Out (MCB 101) | Read and write | ||||
| Function Relay | Read and write | ||||
| On Delay, Relay | s | Read and write | |||
| Off Delay, Relay | s | Read and write | |||
| Term. 29 Low Frequency | Hz | Read and write | |||
| Term. 29 High Frequency | Hz | Read and write | |||
| Term. 29 Low Ref./Feedb. Value | Read and write | ||||
| Term. 29 High Ref./Feedb. Value | Read and write | ||||
| Pulse Filter Time Constant #29 | ms | Read and write | |||
| Term. 33 Low Frequency | Hz | Read and write | |||
| Term. 33 High Frequency | Hz | Read and write | |||
| Term. 33 Low Ref./Feedb. Value | Read and write | ||||
| Term. 33 High Ref./Feedb. Value | Read and write | ||||
| Pulse Filter Time Constant #33 | ms | Read and write | |||
| Terminal 27 Pulse Output Variable | Read and write | ||||
| Pulse Output Max Freq #27 | Hz | Read and write | |||
| Terminal 29 Pulse Output Variable | Read and write | ||||
| Pulse Output Max Freq #29 | Hz | Read and write | |||
| Terminal X30/6 Pulse Output Variable | Read and write | ||||
| Pulse Output Max Freq #X30/6 | Hz | Read and write | |||
| AHF Cap Reconnect Delay | s | Read and write | |||
| Digital & Relay Bus Control | Read and write | ||||
| Pulse Out #27 Bus Control | % | Read and write | |||
| Pulse Out #27 Timeout Preset | % | Read and write | |||
| Pulse Out #29 Bus Control | % | Read and write | |||
| Pulse Out #29 Timeout Preset | % | Read and write | |||
| Pulse Out #X30/6 Bus Control | % | Read and write | |||
| Pulse Out #X30/6 Timeout Preset | % | Read and write | |||
| Live Zero Timeout Time | s | Read and write | |||
| Live Zero Timeout Function | Read and write | ||||
| Terminal 53 Low Voltage | V | Read and write | |||
| Terminal 53 High Voltage | V | Read and write | |||
| Terminal 53 Low Current | mA | Read and write | |||
| Terminal 53 High Current | mA | Read and write | |||
| Terminal 53 Low Ref./Feedb. Value | Read and write | ||||
| Terminal 53 High Ref./Feedb. Value | Read and write | ||||
| Terminal 53 Filter Time Constant | s | Read and write | |||
| Terminal 53 Live Zero | Read and write | ||||
| Terminal 54 Low Voltage | V | Read and write | |||
| Terminal 54 High Voltage | V | Read and write | |||
| Terminal 54 Low Current | mA | Read and write | |||
| Terminal 54 High Current | mA | Read and write | |||
| Terminal 54 Low Ref./Feedb. Value | Read and write | ||||
| Terminal 54 High Ref./Feedb. Value | Read and write | ||||
| Terminal 54 Filter Time Constant | s | Read and write | |||
| Terminal 54 Live Zero | Read and write | ||||
| Terminal X30/11 Low Voltage | V | Read and write | |||
| Terminal X30/11 High Voltage | V | Read and write | |||
| Term. X30/11 Low Ref./Feedb. Value | Read and write | ||||
| Term. X30/11 High Ref./Feedb. Value | Read and write | ||||
| Term. X30/11 Filter Time Constant | s | Read and write | |||
| Term. X30/11 Live Zero | Read and write | ||||
| Terminal X30/12 Low Voltage | V | Read and write | |||
| Terminal X30/12 High Voltage | V | Read and write | |||
| Term. X30/12 Low Ref./Feedb. Value | Read and write | ||||
| Term. X30/12 High Ref./Feedb. Value | Read and write | ||||
| Term. X30/12 Filter Time Constant | s | Read and write | |||
| Term. X30/12 Live Zero | Read and write | ||||
| Terminal 42 Output | Read and write | ||||
| Terminal 42 Output Min Scale | % | Read and write | |||
| Terminal 42 Output Max Scale | % | Read and write | |||
| Terminal 42 Output Bus Control | % | Read and write | |||
| Terminal 42 Output Timeout Preset | % | Read and write | |||
| Terminal X30/8 Output | Read and write | ||||
| Terminal X30/8 Min. Scale | % | Read and write | |||
| Terminal X30/8 Max. Scale | % | Read and write | |||
| Terminal X30/8 Output Bus Control | % | Read and write | |||
| Terminal X30/8 Output Timeout Preset | % | Read and write | |||
| Terminal X45/1 Output | Read and write | ||||
| Terminal X45/1 Min. Scale | % | Read and write | |||
| Terminal X45/1 Max. Scale | % | Read and write | |||
| Terminal X45/1 Bus Control | % | Read and write | |||
| Terminal X45/1 Output Timeout Preset | % | Read and write | |||
| Terminal X45/3 Output | Read and write | ||||
| Terminal X45/3 Min. Scale | % | Read and write | |||
| Terminal X45/3 Max. Scale | % | Read and write | |||
| Terminal X45/3 Bus Control | % | Read and write | |||
| Terminal X45/3 Output Timeout Preset | % | Read and write | |||
| Control Site | Read and write | ||||
| Control Source | Read and write | ||||
| Control Timeout Time | Read and write | ||||
| Control Timeout Function | Read and write | ||||
| End-of-Timeout Function | Read and write | ||||
| Reset Control Timeout | Read and write | ||||
| Diagnosis Trigger | Read and write | ||||
| Control Profile | Read and write | ||||
| Configurable Status Word STW | Read and write | ||||
| Store Data Values | Read and write | ||||
| Protocol | Read and write | ||||
| Address | Read and write | ||||
| Baud Rate | Read and write | ||||
| Parity / Stop Bits | Read and write | ||||
| Minimum Response Delay | ms | Read and write | |||
| Maximum Response Delay | Read and write | ||||
| Maximum Inter-Char Delay | Read and write | ||||
| Telegram Selection | Read and write | ||||
| PCD Write Configuration | Read and write | ||||
| PCD Read Configuration | Read and write | ||||
| BTM Transaction Command | Read and write | ||||
| BTM Transaction Status | Read and write | ||||
| BTM Timeout | s | Read and write | |||
| Coasting Select | Read and write | ||||
| DC Brake Select | Read and write | ||||
| Start Select | Read and write | ||||
| Reversing Select | Read and write | ||||
| Set-up Select | Read and write | ||||
| Preset Reference Select | Read and write | ||||
| Bus Message Count | Read and write | ||||
| Bus Error Count | Read and write | ||||
| Slave Message Count | Read and write | ||||
| Slave Error Count | Read and write | ||||
| Bus Jog 1 Speed | rpm | Read and write | |||
| Bus Jog 2 Speed | Read and write | ||||
| Bus Feedback 1 | Read and write | ||||
| Bus Feedback 2 | Read and write | ||||
| Bus Feedback 3 | Read and write | ||||
| Store Data Values (11-21) | Read and write | ||||
| VLT Network Address | Read and write | ||||
| AK Service Pin | Read and write | ||||
| Alarm Text | Read | ||||
| Alarm Status | Read | ||||
| SL Controller Mode | Read and write | ||||
| Start Event | Read and write | ||||
| Stop Event | Read and write | ||||
| Reset SLC | Read and write | ||||
| Comparator Operand | Read and write | ||||
| Comparator Operator | Read and write | ||||
| Comparator Value | Read and write | ||||
| SL Controller Timer | Read and write | ||||
| Logic Rule Boolean 1 | Read and write | ||||
| Logic Rule Operator 1 | Read and write | ||||
| Logic Rule Boolean 2 | Read and write | ||||
| Logic Rule Operator 2 | Read and write | ||||
| Logic Rule Boolean 3 | Read and write | ||||
| SL Controller Event | Read and write | ||||
| SL Controller Action | Read and write | ||||
| Alert Trigger | Read and write | ||||
| Alert Action | Read and write | ||||
| Alert Text | Read and write | ||||
| Alert Alarm Word | Read | ||||
| Alert Warning Word | Read | ||||
| Alert Status Word | Read | ||||
| Switching Pattern | Read and write | ||||
| Switching Frequency | Read and write | ||||
| Overmodulation | Read and write | ||||
| PWM Random | Read and write | ||||
| Mains Failure | Read and write | ||||
| Mains Voltage at Mains Fault | Read and write | ||||
| Function at Mains Imbalance | Read and write | ||||
| Kin. Backup Gain | % | Read and write | |||
| Reset Mode | Read and write | ||||
| Automatic Restart Time | s | Read and write | |||
| Operation Mode | Read and write | ||||
| Trip Delay at Torque Limit | s | Read and write | |||
| Trip Delay at Inverter Fault | Read and write | ||||
| Production Settings | Read and write | ||||
| Service Code | Read and write | ||||
| Current Lim Ctrl, Proportional Gain | % | Read and write | |||
| Current Lim Ctrl, Integration Time | Read and write | ||||
| VT Level | % | Read and write | |||
| AEO Minimum Magnetisation | Read and write | ||||
| Minimum AEO Frequency | Read and write | ||||
| Motor Cosphi | Read and write | ||||
| RFI Filter | Read and write | ||||
| DC Link Compensation | Read and write | ||||
| Fan Control | Read and write | ||||
| Fan Monitor | Read and write | ||||
| Output Filter | Read and write | ||||
| Actual Number of Inverter Units | Read | ||||
| Function at Over Temperature | Read and write | ||||
| Function at Inverter Overload | Read and write | ||||
| Inv. Overload Derate Current | % | Read and write | |||
| Option Supplied By External 24VDC | Read and write | ||||
| Option Detection | Read and write | ||||
| Fault Level | Read and write | ||||
| Reset kWh Counter | Read and write | ||||
| Reset Running Hours Counter | Read and write | ||||
| Logging Source | Read and write | ||||
| Logging Interval | Read and write | ||||
| Trigger Event | Read and write | ||||
| Logging Mode | Read and write | ||||
| Samples Before Trigger | Read and write | ||||
| Historic Log: Event | Read | ||||
| Historic Log: Value | Read | ||||
| Historic Log: Time | ms | Read | |||
| Historic Log: Date and Time | Read | ||||
| Alarm Log: Error Code | Read | ||||
| Alarm Log: Value | Read | ||||
| Alarm Log: Time | s | Read | |||
| Alarm Log: Date and Time | Read | ||||
| Alarm Log: Status | Read | ||||
| Alarm Log: Alarm Text | Read | ||||
| Preset Fan Running Hours | h | Read and write | |||
| Custom Readout | Read | ||||
| Power [hp] | Read | ||||
| Frequency [%] | % | Read | |||
| Calibrated Stator Resistance | Ω | Read | |||
| System Temp. | °C | Read | |||
| Brake Energy /s | kW | Read | |||
| Brake Energy /2 Min | kW | Read | |||
| Inv. Nom. Current | Read | ||||
| Inv. Max. Current | Read | ||||
| SL Controller State | Read | ||||
| Logging Buffer Full | Read | ||||
| LCP Bottom Statusline | Read | ||||
| Current Fault Source | Read | ||||
| External Reference | Read | ||||
| Digi Pot Reference | Read | ||||
| Digital Input | Read | ||||
| Terminal 53 Switch Setting | Read | ||||
| Analog Input 53 | Read | ||||
| Terminal 54 Switch Setting | Read | ||||
| Analog Input 54 | Read | ||||
| Analog Output 42 [mA] | mA | Read | |||
| Digital Output [bin] | Read | ||||
| Pulse Input #29 [Hz] | Hz | Read | |||
| Pulse Input #33 [Hz] | Hz | Read | |||
| Pulse Output #27 [Hz] | Hz | Read | |||
| Pulse Output #29 [Hz] | Hz | Read | |||
| Relay Output [bin] | Read | ||||
| Counter A | Read | ||||
| Counter B | Read | ||||
| Analog In X30/11 | Read | ||||
| Analog In X30/12 | Read | ||||
| Analog Out X30/8 [mA] | mA | Read | |||
| Analog Out X45/1 [mA] | mA | Read | |||
| Analog Out X45/3 [mA] | mA | Read | |||
| Fieldbus CTW 1 | Read | ||||
| Fieldbus REF 1 | Read | ||||
| Comm. Option STW | Read | ||||
| FC Port CTW 1 | Read | ||||
| FC Port REF 1 | Read | ||||
| Maintenance Log: Item | Read | ||||
| Maintenance Log: Action | Read | ||||
| Maintenance Log: Time | s | Read | |||
| Maintenance Log: Date and Time | Read | ||||
| Analog Input X42/1 | Read | ||||
| Analog Input X42/3 | Read | ||||
| Analog Input X42/5 | Read | ||||
| Analog Out X42/7 [V] | V | Read | |||
| Analog Out X42/9 [V] | V | Read | |||
| Analog Out X42/11 [V] | V | Read | |||
| Air Pressure to Flow Air Flow | Read | ||||
| Digital Input 2 | Read | ||||
| Mains Voltage | V | Read | |||
| Mains Frequency | Hz | Read | |||
| Mains Imbalance | % | Read | |||
| Rectifier DC Volt. | V | Read | |||
| Feedback 1 Source | Read and write | ||||
| Feedback 1 Conversion | Read and write | ||||
| Feedback 1 Source Unit | Read and write | ||||
| Feedback 2 Source | Read and write | ||||
| Feedback 2 Conversion | Read and write | ||||
| Feedback 2 Source Unit | Read and write | ||||
| Feedback 3 Source | Read and write | ||||
| Feedback 3 Conversion | Read and write | ||||
| Feedback 3 Source Unit | Read and write | ||||
| Reference/Feedback Unit | Read and write | ||||
| Feedback Function | Read and write | ||||
| Setpoint 1 | Read and write | ||||
| Setpoint 2 | Read and write | ||||
| Setpoint 3 | Read and write | ||||
| Setpoint Type | Read and write | ||||
| Refrigerant | Read and write | ||||
| User Defined Refrigerant A1 | Read and write | ||||
| User Defined Refrigerant A2 | Read and write | ||||
| User Defined Refrigerant A3 | Read and write | ||||
| Thermostat/Pressostat Function | Read and write | ||||
| Cut-out Value | Read and write | ||||
| Cut-in Value | Read and write | ||||
| Closed Loop Type | Read and write | ||||
| PID Performance | Read and write | ||||
| PID Output Change | Read and write | ||||
| Minimum Feedback Level | Read and write | ||||
| Maximum Feedback Level | Read and write | ||||
| PID Autotuning | Read and write | ||||
| PID Normal/ Inverse Control | Read and write | ||||
| PID Start Speed [RPM] | rpm | Read and write | |||
| PID Start Speed [Hz] | Hz | Read and write | |||
| On Reference Bandwidth | % | Read and write | |||
| PID Anti Windup | Read and write | ||||
| PID Proportional Gain | Read and write | ||||
| PID Integral Time | s | Read and write | |||
| PID Differentiation Time | s | Read and write | |||
| PID Diff. Gain Limit | Read and write | ||||
| Ext. Loop Closed Loop Type | Read and write | ||||
| Ext. Loop PID Performance | Read and write | ||||
| Ext. Loop PID Output Change | Read and write | ||||
| Ext. Loop Minimum Feedback Level | Read and write | ||||
| Ext. Loop Maximum Feedback Level | Read and write | ||||
| Ext. Loop PID Autotuning | Read and write | ||||
| Ext. 1 Ref./Feedback Unit | Read and write | ||||
| Ext. 1 Minimum Reference | Read and write | ||||
| Ext. 1 Maximum Reference | Read and write | ||||
| Ext. 1 Reference Source | Read and write | ||||
| Ext. 1 Feedback Source | Read and write | ||||
| Ext. 1 Setpoint | Read and write | ||||
| Ext. 1 PID Conversion | Read and write | ||||
| Ext. 1 Reference | Read and write | ||||
| Ext. 1 Feedback | Read and write | ||||
| Ext. 1 Output [%] | % | Read and write | |||
| Ext. 1 Normal/Inverse Control | Read and write | ||||
| Ext. 1 Proportional Gain | Read and write | ||||
| Ext. 1 Integral Time | s | Read and write | |||
| Ext. 1 Differentation Time | s | Read and write | |||
| Ext. 1 Dif. Gain Limit | Read and write | ||||
| Ext. 2 Ref./Feedback Unit | Read and write | ||||
| Ext. 2 Minimum Reference | Read and write | ||||
| Ext. 2 Maximum Reference | Read and write | ||||
| Ext. 2 Reference Source | Read and write | ||||
| Ext. 2 Feedback Source | Read and write | ||||
| Ext. 2 Setpoint | Read and write | ||||
| Ext. 2 PID Conversion | Read and write | ||||
| Ext. 2 Reference | Read and write | ||||
| Ext. 2 Feedback | Read and write | ||||
| Ext. 2 Output [%] | % | Read and write | |||
| Ext. 2 Normal/Inverse Control | Read and write | ||||
| Ext. 2 Proportional Gain | Read and write | ||||
| Ext. 2 Integral Time | s | Read and write | |||
| Ext. 2 Differentation Time | s | Read and write | |||
| Ext. 2 Dif. Gain Limit | Read and write | ||||
| Ext. 3 Ref./Feedback Unit | Read and write | ||||
| Ext. 3 Minimum Reference | Read and write | ||||
| Ext. 3 Maximum Reference | Read and write | ||||
| Ext. 3 Reference Source | Read and write | ||||
| Ext. 3 Feedback Source | Read and write | ||||
| Ext. 3 Setpoint | Read and write | ||||
| Ext. 3 PID Conversion | Read and write | ||||
| Ext. 3 Reference | Read and write | ||||
| Ext. 3 Feedback | Read and write | ||||
| Ext. 3 Output [%] | % | Read and write | |||
| Ext. 3 Normal/Inverse Control | Read and write | ||||
| Ext. 3 Proportional Gain | Read and write | ||||
| Ext. 3 Integral Time | s | Read and write | |||
| Ext. 3 Differentation Time | s | Read and write | |||
| Ext. 3 Dif. Gain Limit | Read and write | ||||
| Ext. Loop Refrigerant | Read and write | ||||
| Ext. Loop User Defined Refrigerant A1 | Read and write | ||||
| Ext. Loop User Defined Refrigerant A2 | Read and write | ||||
| Ext. Loop User Defined Refrigerant A3 | Read and write | ||||
| External Interlock Delay | s | Read and write | |||
| Air Pressure to Flow Signal Source | Read and write | ||||
| Air Pressure to Flow Fan K-factor | Read and write | ||||
| Air Pressure to Flow Air Density | Read and write | ||||
| Air Pressure to Flow Fan Flow Unit | Read and write | ||||
| Low Power Auto Set-up | Read and write | ||||
| Low Power Detection | Read and write | ||||
| Low Speed Detection | Read and write | ||||
| No-Flow Function | Read and write | ||||
| No-Flow Delay | s | Read and write | |||
| Dry Pump Function | Read and write | ||||
| Dry Pump Delay | s | Read and write | |||
| No-Flow Power | kW | Read and write | |||
| Power Correction Factor | % | Read and write | |||
| Low Speed [RPM] | rpm | Read and write | |||
| Low Speed [Hz] | Hz | Read and write | |||
| Low Speed Power [kW] | kW | Read and write | |||
| Low Speed Power [HP] | Read and write | ||||
| High Speed [RPM] | rpm | Read and write | |||
| High Speed [Hz] | Hz | Read and write | |||
| High Speed Power [kW] | kW | Read and write | |||
| High Speed Power [HP] | Read and write | ||||
| Minimum Run Time | s | Read and write | |||
| Minimum Sleep Time | s | Read and write | |||
| Wake-up Speed [RPM] | rpm | Read and write | |||
| Wake-up Speed [Hz] | Hz | Read and write | |||
| Wake-up Ref./FB Difference | % | Read and write | |||
| Setpoint Boost | % | Read and write | |||
| Maximum Boost Time | s | Read and write | |||
| End of Curve Function | Read and write | ||||
| End of Curve Delay | s | Read and write | |||
| Broken Belt Function | Read and write | ||||
| Broken Belt Torque | % | Read and write | |||
| Broken Belt Delay | s | Read and write | |||
| Short Cycle Protection | Read and write | ||||
| Interval between Starts | s | Read and write | |||
| Minimum Run Time (22-77) | s | Read and write | |||
| Minimum Run Time Override | Read and write | ||||
| Minimum Run Time Override Value | Read and write | ||||
| Flow Compensation | Read and write | ||||
| Square-linear Curve Approximation | % | Read and write | |||
| Work Point Calculation | Read and write | ||||
| Speed at No-Flow [RPM] | rpm | Read and write | |||
| Speed at No-Flow [Hz] | Hz | Read and write | |||
| Speed at Design Point [RPM] | rpm | Read and write | |||
| Speed at Design Point [Hz] | Hz | Read and write | |||
| Pressure at No-Flow Speed | Read and write | ||||
| Pressure at Rated Speed | Read and write | ||||
| Flow at Design Point | Read and write | ||||
| Flow at Rated Speed | Read and write | ||||
| ON Time | Read and write | ||||
| ON Action | Read and write | ||||
| OFF Time | Read and write | ||||
| OFF Action | Read and write | ||||
| Occurrence | Read and write | ||||
| Maintenance Item | Read and write | ||||
| Maintenance Action | Read and write | ||||
| Maintenance Time Base | Read and write | ||||
| Maintenance Time Interval | h | Read and write | |||
| Maintenance Date and Time | Read and write | ||||
| Reset Maintenance Word | Read and write | ||||
| Maintenance Text | Read and write | ||||
| Energy Log Resolution | Read and write | ||||
| Period Start | Read and write | ||||
| Energy Log | Read | ||||
| Reset Energy Log | Read and write | ||||
| Trend Variable | Read and write | ||||
| Continuous Bin Data | Read | ||||
| Timed Bin Data | Read | ||||
| Timed Period Start | Read and write | ||||
| Timed Period Stop | Read and write | ||||
| Minimum Bin Value | Read and write | ||||
| Reset Continuous Bin Data | Read and write | ||||
| Reset Timed Bin Data | Read and write | ||||
| Power Reference Factor | % | Read and write | |||
| Energy Cost | Read and write | ||||
| Investment | Read and write | ||||
| Energy Savings | kWh | Read | |||
| Cost Savings | Read | ||||
| Pack Controller | Read and write | ||||
| Motor Start | Read and write | ||||
| Pump Cycling | Read and write | ||||
| Fixed Lead Compressor | Read and write | ||||
| Number of Compressors | Read and write | ||||
| Neutral Zone | Read and write | ||||
| + Zone | Read and write | ||||
| - Zone | Read and write | ||||
| Fixed Speed Neutral Zone | Read and write | ||||
| + Zone Delay | s | Read and write | |||
| - Zone Delay | s | Read and write | |||
| ++ Zone Delay | s | Read and write | |||
| -- Zone Delay | s | Read and write | |||
| Override Bandwidth Ramp Time | Read and write | ||||
| Destage At No-Flow | Read and write | ||||
| Stage Function | Read and write | ||||
| Stage Function Time | s | Read and write | |||
| Destage Function | Read and write | ||||
| Destage Function Time | s | Read and write | |||
| Staging Threshold | Read and write | ||||
| Destaging Threshold | Read and write | ||||
| Staging Speed [RPM] | rpm | Read and write | |||
| Staging Speed [Hz] | Hz | Read and write | |||
| Destaging Speed [RPM] | rpm | Read and write | |||
| Destaging Speed [Hz] | Hz | Read and write | |||
| Lead Pump Alternation | Read and write | ||||
| Alternation Event | Read and write | ||||
| Alternation Time Interval | h | Read and write | |||
| Alternation Timer Value | Read | ||||
| Alternation Predefined Time | Read and write | ||||
| Alternate if Load < 50% | Read and write | ||||
| Staging Mode at Alternation | Read and write | ||||
| Run Next Pump Delay | s | Read and write | |||
| Run on Mains Delay | s | Read and write | |||
| Reset Relay Counters | Read and write | ||||
| Inverse Interlock | Read | ||||
| Compressor Interlock | Read and write | ||||
| Manual Alternation | Read and write | ||||
| Terminal X42/1 Mode | Read and write | ||||
| Terminal X42/3 Mode | Read and write | ||||
| Terminal X42/5 Mode | Read and write | ||||
| Terminal X42/1 Low Voltage | V | Read and write | |||
| Terminal X42/1 High Voltage | V | Read and write | |||
| Term. X42/1 Low Ref./Feedb. Value | Read and write | ||||
| Term. X42/1 High Ref./Feedb. Value | Read and write | ||||
| Term. X42/1 Filter Time Constant | s | Read and write | |||
| Term. X42/1 Live Zero | Read and write | ||||
| Terminal X42/3 Low Voltage | V | Read and write | |||
| Terminal X42/3 High Voltage | V | Read and write | |||
| Term. X42/3 Low Ref./Feedb. Value | Read and write | ||||
| Term. X42/3 High Ref./Feedb. Value | Read and write | ||||
| Term. X42/3 Filter Time Constant | s | Read and write | |||
| Term. X42/3 Live Zero | Read and write | ||||
| Terminal X42/5 Low Voltage | V | Read and write | |||
| Terminal X42/5 High Voltage | V | Read and write | |||
| Term. X42/5 Low Ref./Feedb. Value | Read and write | ||||
| Term. X42/5 High Ref./Feedb. Value | Read and write | ||||
| Term. X42/5 Filter Time Constant | s | Read and write | |||
| Term. X42/5 Live Zero | Read and write | ||||
| Terminal X42/7 Output | Read and write | ||||
| Terminal X42/7 Min. Scale | % | Read and write | |||
| Terminal X42/7 Max. Scale | % | Read and write | |||
| Terminal X42/7 Bus Control | % | Read and write | |||
| Terminal X42/7 Timeout Preset | % | Read and write | |||
| Terminal X42/9 Output | Read and write | ||||
| Terminal X42/9 Min. Scale | % | Read and write | |||
| Terminal X42/9 Max. Scale | % | Read and write | |||
| Terminal X42/9 Bus Control | % | Read and write | |||
| Terminal X42/9 Timeout Preset | % | Read and write | |||
| Terminal X42/11 Output | Read and write | ||||
| Terminal X42/11 Min. Scale | % | Read and write | |||
| Terminal X42/11 Max. Scale | % | Read and write | |||
| Terminal X42/11 Bus Control | % | Read and write | |||
| Terminal X42/11 Timeout Preset | % | Read and write | |||
| Oil Return Management | Read and write | ||||
| Low Speed Running Time | min | Read and write | |||
| Fixed Boost Interval | h | Read and write | |||
| Boost Duration | s | Read and write | |||
| Adequate Oil Return Speed [RPM] | rpm | Read and write | |||
| Adequate Oil Return Speed [Hz] | Hz | Read and write | |||
| Oil Boost Speed [RPM] | rpm | Read and write | |||
| Oil Boost Speed [Hz] | Hz | Read and write | |||
| Cancel Oil Boost at Low Feedback | Read and write | ||||
| Cancel Oil Boost at High Feedback | Read and write | ||||
| Temperature Source | Read and write | ||||
| Temperature Unit | Read and write | ||||
| Warning Level | Read and write | ||||
| Warning Action | Read and write | ||||
| Emergency Level | Read and write | ||||
| Day/Night Bus Indicator | Read and write | ||||
| Enable Day/Night Via Bus | Read and write | ||||
| Night Setback | Read and write | ||||
| Night Speed Drop [RPM] | rpm | Read and write | |||
| Night Speed Drop Override | Read and write | ||||
| Night Speed Drop [Hz] | Hz | Read and write | |||
| dP0 Offset | K | Read and write | |||
| P0 Minimum Reference | K | Read and write | |||
| P0 Maximum Reference | K | Read and write | |||
| Most Loaded Controller | Read | ||||
| Injection On | Read and write | ||||
| Delayed Compressor Start | Read and write | ||||
| Pre/Post Lube Function | Read and write | ||||
| Pre Lube Time | s | Read and write | |||
| Post Lube Time | s | Read and write | |||
| Locked Rotor Protection | Read and write | ||||
| Locked Rotor Detection Time [s] | s | Read and write | |||
| Monitor 1 Pressure Transmitter | Read and write | ||||
| Monitor 1 Pressure Conversion | Read and write | ||||
| Monitor 1 Pressure Source Unit | Read and write | ||||
| Monitor 1 Temperature Unit | Read and write | ||||
| Monitor 1 High Pres. Stop | Read and write | ||||
| Monitor 1 High Pres. Start | Read and write | ||||
| Monitor 1 Low Pres. Stop | Read and write | ||||
| Monitor 1 Low Pres. Start | Read and write | ||||
| Monitor 2 Pressure Transmitter | Read and write | ||||
| Monitor 2 Pressure Conversion | Read and write | ||||
| Monitor 2 Pressure Source Unit | Read and write | ||||
| Monitor 2 Temperature Unit | Read and write | ||||
| Monitor 2 High Pres. Stop | Read and write | ||||
| Monitor 2 High Pres. Start | Read and write | ||||
| Monitor 2 Low Pres. Stop | Read and write | ||||
| Monitor 2 Low Pres. Start | Read and write | ||||
| Monitor 2 Pressure Stop Ramp Time | Read and write | ||||
| Heat Sink Fan Mode | Read and write | ||||
| FC Type | Read | ||||
| Power Section | Read | ||||
| Voltage | Read | ||||
| Software Version | Read | ||||
| Ordered Typecode String | Read | ||||
| Actual Typecode String | Read | ||||
| Frequency Converter Ordering No | Read | ||||
| Power Card Ordering No | Read | ||||
| LCP Id No | Read | ||||
| SW ID Control Card | Read | ||||
| SW ID Power Card | Read | ||||
| Frequency Converter Serial Number | Read | ||||
| Power Card Serial Number | Read | ||||
| Option Mounted | Read | ||||
| Option SW Version | Read | ||||
| Option Ordering No | Read | ||||
| Option Serial No | Read | ||||
| Option in Slot A | Read | ||||
| Slot A Option SW Version | Read | ||||
| Option in Slot B | Read | ||||
| Slot B Option SW Version | Read | ||||
| Option in Slot C0/E0 | Read | ||||
| Slot C0/E0 Option SW Version | Read | ||||
| Option in Slot C1/E1 | Read | ||||
| Slot C1/E1 Option SW Version | Read | ||||
| Defined Parameters | Read | ||||
| Modified Parameters | Read | ||||
| Parameter Metadata | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show output frequency, motor current and power of each compressor drive on one ModbusCloud dashboard.
- Send an email alert when the alarm word is not 0 so the service engineer knows a drive tripped.
- Keep a year of suction pressure, P0 setpoint and pack capacity to spot short cycling or poor control.
- Change the P0 setpoint or night setback remotely without a visit to the plant room.
- Track running hours, number of starts and kWh per drive for maintenance planning and energy reports.
Installation
Connect RS485 terminals 68 (+) and 69 (-) of the drive to RS485 A and B of the ModbusCloud Gateway and set switch S801 to on at the last device on the bus.
On the drive set 8-30 Protocol to Modbus RTU, a unique address in 8-31 and the same baud rate and parity in 8-32 and 8-33 as in ModbusCloud.
In ModbusCloud add a Modbus device with the same address and serial settings and import this template.
Check that Frequency, Motor Voltage and DC Link Voltage show plausible values before you write any register.
Things to watch for
The drive does not answer on the bus. What should I check?
Check that 8-30 is set to Modbus RTU and not to FC protocol, and that address, baud rate and parity in 8-31 to 8-33 match ModbusCloud. Swap A and B if needed and set the termination switch only at both ends of the line.
Why do some parameters show strange values or change when I read again?
Many parameters are arrays, such as preset references or log entries. The drive returns the element set in the Array Index Pointer register. Write the index you want there first, then read the parameter.
Can I write parameters, and are the changes kept after a restart?
Yes, every setting is writable, but some only with the motor stopped. Coil 65, Parameter Write Control, decides where writes go: 0 keeps them in RAM only, 1 also stores them in EEPROM. Read a value first and change one parameter at a time, because a wrong ramp or limit can stop the compressor.
How do I start the drive and set its speed over Modbus?
Write the control word to Bus Control Word or to the control coils and the speed reference to Bus Reference, where 0x4000 equals 100 percent. The Data Valid bit must be 1, and 8-50 and related parameters decide whether the bus or the digital inputs have priority.