DENT Instruments PowerScout 12 HD
Multi-circuit submeter that measures current, voltage, power, and energy on up to 12 CT channels.
The DENT Instruments PowerScout 12 HD is a networked multi-circuit power submeter that measures up to four three-phase or twelve single-phase circuits in the electrical panels of commercial and industrial buildings. This Modbus TCP template reads current, voltage, power, power factor and energy per channel and per element, and lets you set CT ratings, service type and pulse inputs or clear energy totals from ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 227, read and write
- Brand
- DENT Instruments
- Key readings
- Current per channel · Voltage L-N and L-L · Real power · Imported energy · Exported energy · Power factor · Peak demand · Frequency
- Available commands
- CT rating and type · Service type · Clear energy totals · Clear peak demand · Pulse input scaling
- Compatible models
- PowerScout 12 HD (PS12HD) · PowerScout 3 HD (PS3HD) · PowerScout 24 HD (PS24HD) · PowerScout 48 HD (PS48HD)
- Last updated
Registers (227)
217 read, 91 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Current Avg Element | A | Read | |||
| Current CH1 | A | Read | |||
| Current CH2 | A | Read | |||
| Current CH3 | A | Read | |||
| Voltage L-N Avg Element | V | Read | |||
| Voltage L1-N | V | Read | |||
| Voltage L2-N | V | Read | |||
| Voltage L3-N | V | Read | |||
| Voltage L-L Avg Element | V | Read | |||
| Voltage L1-L2 | V | Read | |||
| Voltage L2-L3 | V | Read | |||
| Voltage L3-L1 | V | Read | |||
| Line Frequency | Hz | Read | |||
| Power Sum Element | kW | Read | |||
| Power CH1 | kW | Read | |||
| Power CH2 | kW | Read | |||
| Power CH3 | kW | Read | |||
| VA Sum Element | kVA | Read | |||
| VA CH1 | kVA | Read | |||
| VA CH2 | kVA | Read | |||
| VA CH3 | kVA | Read | |||
| VAR Sum Element | kvar | Read | |||
| VAR CH1 | kvar | Read | |||
| VAR CH2 | kvar | Read | |||
| VAR CH3 | kvar | Read | |||
| Apparent PF Avg Element | Read | ||||
| Apparent PF CH1 | Read | ||||
| Apparent PF CH2 | Read | ||||
| Apparent PF CH3 | Read | ||||
| Exported Energy Sum Element | kWh | Read | |||
| Exported Energy CH1 | kWh | Read | |||
| Exported Energy CH2 | kWh | Read | |||
| Exported Energy CH3 | kWh | Read | |||
| Imported Energy Sum Element | kWh | Read | |||
| Imported Energy CH1 | kWh | Read | |||
| Imported Energy CH2 | kWh | Read | |||
| Imported Energy CH3 | kWh | Read | |||
| Exported VAh Sum Element | kVAh | Read | |||
| Exported VAh CH1 | kVAh | Read | |||
| Exported VAh CH2 | kVAh | Read | |||
| Exported VAh CH3 | kVAh | Read | |||
| Imported VAh Sum Element | kVAh | Read | |||
| Imported VAh CH1 | kVAh | Read | |||
| Imported VAh CH2 | kVAh | Read | |||
| Imported VAh CH3 | kVAh | Read | |||
| Imported VARh Q1 Sum Element | kvarh | Read | |||
| Imported VARh Q1 CH1 | kvarh | Read | |||
| Imported VARh Q1 CH2 | kvarh | Read | |||
| Imported VARh Q1 CH3 | kvarh | Read | |||
| Imported VARh Q2 Sum Element | kvarh | Read | |||
| Imported VARh Q2 CH1 | kvarh | Read | |||
| Imported VARh Q2 CH2 | kvarh | Read | |||
| Imported VARh Q2 CH3 | kvarh | Read | |||
| Exported VARh Q3 Sum Element | kvarh | Read | |||
| Exported VARh Q3 CH1 | kvarh | Read | |||
| Exported VARh Q3 CH2 | kvarh | Read | |||
| Exported VARh Q3 CH3 | kvarh | Read | |||
| Exported VARh Q4 Sum Element | kvarh | Read | |||
| Exported VARh Q4 CH1 | kvarh | Read | |||
| Exported VARh Q4 CH2 | kvarh | Read | |||
| Exported VARh Q4 CH3 | kvarh | Read | |||
| Active Energy Net Sum Element | kWh | Read | |||
| Active Energy Net CH1 | kWh | Read | |||
| Active Energy Net CH2 | kWh | Read | |||
| Active Energy Net CH3 | kWh | Read | |||
| Apparent Energy Net Sum Element | kVAh | Read | |||
| Apparent Energy Net CH1 | kVAh | Read | |||
| Apparent Energy Net CH2 | kVAh | Read | |||
| Apparent Energy Net CH3 | kVAh | Read | |||
| Reactive Energy Net Sum Element | kvarh | Read | |||
| Reactive Energy Net CH1 | kvarh | Read | |||
| Reactive Energy Net CH2 | kvarh | Read | |||
| Reactive Energy Net CH3 | kvarh | Read | |||
| Watt Peak Demand Element | kW | Read | |||
| Watt Demand This Interval Element | kW | Read | |||
| VA Peak Demand Element | kVA | Read | |||
| VA Demand This Interval Element | kVA | Read | |||
| Displacement PF Avg Element | Read | ||||
| Displacement PF CH1 | Read | ||||
| Displacement PF CH2 | Read | ||||
| Displacement PF CH3 | Read | ||||
| Apparent PF Element | Read | ||||
| Apparent PF CH1 Duplicate | Read | ||||
| Apparent PF CH2 Duplicate | Read | ||||
| Apparent PF CH3 Duplicate | Read | ||||
| Distortion PF Avg Element | Read | ||||
| Distortion PF CH1 | Read | ||||
| Distortion PF CH2 | Read | ||||
| Distortion PF CH3 | Read | ||||
| THD Avg Element | % | Read | |||
| THD CH1 | % | Read | |||
| THD CH2 | % | Read | |||
| THD CH3 | % | Read | |||
| Theta CH1 | ° | Read | |||
| Theta CH2 | ° | Read | |||
| Theta CH3 | ° | Read | |||
| Theta Element | ° | Read | |||
| Pulse Input 1 Accumulator | Read | ||||
| Pulse Input 2 Accumulator | Read | ||||
| Pulse Input 3 Accumulator | Read | ||||
| Pulse Input 4 Accumulator | Read | ||||
| Time Since Reset | s | Read | |||
| Events | Read | ||||
| Phase Check System Status | Read | ||||
| Phase Check Element Status | Read | ||||
| Alarm Output Status | Read and write | ||||
| Voltage Vin1 Alarm Status Under | Read | ||||
| Voltage Vin2 Alarm Status Under | Read | ||||
| Reset Processor | Write | ||||
| Clear Accumulated Measurements All | Write | ||||
| Clear Accumulated Measurements Element | Write | ||||
| Clear Peak Demand Element | Write | ||||
| Clear Peak Demand All | Write | ||||
| Reset to User Defaults | Write | ||||
| Pulse Input 1 Accumulator Clear | Write | ||||
| Pulse Input 2 Accumulator Clear | Write | ||||
| Pulse Input 3 Accumulator Clear | Write | ||||
| Pulse Input 4 Accumulator Clear | Write | ||||
| Demand Window Type | Read | ||||
| Demand Window | min | Read | |||
| Volt Multiplier VINPUT1 | Read and write | ||||
| Volt Multiplier VINPUT2 | Read and write | ||||
| Service Type Element | Read and write | ||||
| Millivolt Snap Threshold | % | Read and write | |||
| RoCoil Snap Threshold | % | Read and write | |||
| Voltage Snap Threshold | V | Read and write | |||
| Communications Mode | Read | ||||
| RoCoil Millivolt per Kiloamp | Read and write | ||||
| Voltage Input Element | Read and write | ||||
| CH1 CT Full Scale Rating | A | Read and write | |||
| CH1 CT Voltage Reference | Read and write | ||||
| CH1 CT Multiplier | Read and write | ||||
| CH1 CT Type | Read and write | ||||
| CH1 CT Phase Shift | ° | Read and write | |||
| CH1 CT Sign | Read and write | ||||
| CH2 CT Full Scale Rating | A | Read and write | |||
| CH2 CT Voltage Reference | Read and write | ||||
| CH2 CT Multiplier | Read and write | ||||
| CH2 CT Type | Read and write | ||||
| CH2 CT Phase Shift | ° | Read and write | |||
| CH2 CT Sign | Read and write | ||||
| CH3 CT Full Scale Rating | A | Read and write | |||
| CH3 CT Voltage Reference | Read and write | ||||
| CH3 CT Multiplier | Read and write | ||||
| CH3 CT Type | Read and write | ||||
| CH3 CT Phase Shift | ° | Read and write | |||
| CH3 CT Sign | Read and write | ||||
| PF Sign Convention | Read and write | ||||
| Communication Inactivity Timeout | min | Read and write | |||
| User Config | Read and write | ||||
| Pulse Input 1 Enable | Read and write | ||||
| Pulse Input 1 Scale Factor | Read and write | ||||
| Pulse Input 1 Units | Read and write | ||||
| Pulse Input 2 Enable | Read and write | ||||
| Pulse Input 2 Scale Factor | Read and write | ||||
| Pulse Input 2 Units | Read and write | ||||
| Pulse Input 3 Enable | Read and write | ||||
| Pulse Input 3 Scale Factor | Read and write | ||||
| Pulse Input 3 Units | Read and write | ||||
| Pulse Input 4 Enable | Read and write | ||||
| Pulse Input 4 Scale Factor | Read and write | ||||
| Pulse Input 4 Units | Read and write | ||||
| Voltage Alarm Vin1 Mask | Read and write | ||||
| Voltage Alarm Vin2 Mask | Read and write | ||||
| Voltage Alarm Vin1 L1N Under | V | Read and write | |||
| Voltage Alarm Vin1 L2N Under | V | Read and write | |||
| Voltage Alarm Vin1 L3N Under | V | Read and write | |||
| Voltage Alarm Vin1 L1L2 Under | V | Read and write | |||
| Voltage Alarm Vin1 L2L3 Under | V | Read and write | |||
| Voltage Alarm Vin1 L3L1 Under | V | Read and write | |||
| Voltage Alarm Vin2 L1N Under | V | Read and write | |||
| Voltage Alarm Vin2 L2N Under | V | Read and write | |||
| Voltage Alarm Vin2 L3N Under | V | Read and write | |||
| Voltage Alarm Vin2 L1L2 Under | V | Read and write | |||
| Voltage Alarm Vin2 L2L3 Under | V | Read and write | |||
| Voltage Alarm Vin2 L3L1 Under | V | Read and write | |||
| Voltage Alarm Persistence | s | Read and write | |||
| Real Time Clock | s | Read and write | |||
| System Description | Read and write | ||||
| Element Description | Read and write | ||||
| BACnet Description | Read | ||||
| Modbus Device Address | Read and write | ||||
| DHCP Static Config | Read and write | ||||
| NTP DNS Control | Read and write | ||||
| IP Address | Read and write | ||||
| Netmask | Read and write | ||||
| IP Gateway | Read and write | ||||
| DNS1 Address | Read and write | ||||
| DNS2 Address | Read and write | ||||
| MAC Address | Read | ||||
| Link Control | Read | ||||
| Serial Interface Name | Read and write | ||||
| Serial Baud Rate | Read and write | ||||
| Serial Data Bits | Read and write | ||||
| Serial Parity | Read and write | ||||
| Serial Duplex | Read and write | ||||
| Serial Flow Control | Read and write | ||||
| Serial Interface Type | Read | ||||
| Serial Protocol Selection | Read | ||||
| Modbus TCP Port | Read | ||||
| BACnet UDP Port | Read and write | ||||
| BACnet Vendor ID | Read | ||||
| BACnet Device ID | Read and write | ||||
| BACnet Max Info Frames | Read and write | ||||
| BACnet Max Masters | Read and write | ||||
| BBMD IP Address | Read and write | ||||
| LCD WebApp Read Password | Read and write | ||||
| LCD WebApp Read Write Password | Read and write | ||||
| Manufacturer | Read | ||||
| Model | Read | ||||
| Options | Read | ||||
| Firmware Version | Read | ||||
| Serial Number | Read | ||||
| Network Interface Name | Read | ||||
| SunSpec ID | Read | ||||
| SunSpec Common Model ID | Read | ||||
| SunSpec Common Model Length | Read | ||||
| Common Model Pad | Read | ||||
| SunSpec Network Model ID | Read | ||||
| SunSpec Network Model Length | Read | ||||
| Network Model Pad | Read | ||||
| SunSpec Serial Model ID | Read | ||||
| SunSpec Serial Model Length | Read | ||||
| SunSpec Meter Model ID | Read | ||||
| SunSpec Meter Model Length | Read | ||||
| SunSpec End Marker | Read | ||||
| SunSpec End Length | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show live kW, current and voltage per circuit on a ModbusCloud dashboard, on a computer or in the browser on a phone.
- Keep 12 months of kWh history per circuit and compare tenants, floors or machines in Trends.
- Email a scheduled PDF report with imported, exported and net kWh per element.
- Get an email alarm when 15 minute demand or a channel current passes a threshold you set.
- Get notified when the voltage alarm status or phase check status of the meter changes.
- Clear peak demand or energy totals remotely at the start of a billing period.
Installation
Connect the ModbusCloud Gateway to the same local network as the Ethernet port of the PowerScout 12 HD.
Give the meter a fixed IP address. It uses DHCP by default; set a static address on the display, in the web app or with ViewPoint HD.
In ModbusCloud, add a Modbus device with the IP address of the meter, port 502 and unit ID 1 for element A, and import this template.
Repeat for every element in use: unit ID 2 for element B, 3 for C and 4 for D.
Check that current, voltage and kWh come in and match the values on the meter display or in the web app.
Things to watch for
The meter does not answer on Modbus TCP. What should I check?
Check that the ModbusCloud Gateway and the meter are in the same subnet and that the IP address is right. With DHCP the address can change after a power cycle, so give the meter a static address. The Modbus port is fixed at 502 and element A answers on unit ID 1.
Why do I only see the values of three channels?
Each element of three channels has its own Modbus address. Unit ID 1 is element A, 2 is B, 3 is C and 4 is D. Add a Modbus device per element with this template. Pulse inputs, network settings and identification are the same on every address.
A channel shows negative power. What is wrong?
The CT is probably mounted the wrong way round or paired with the wrong voltage. Turn the CT around or set CT Sign to Reversed for that channel, and check CT Voltage Reference. The phase check status values show the result of the meter's own phase check per CT.
Can I change CT settings or clear totals from ModbusCloud?
Yes. CT, service type, pulse input and alarm settings are writable, and the clear commands take the value 1234. Network and serial changes only take effect after you write 1234 to Reset Processor. Write CT settings with care: they change every reading of that channel.
The energy totals suddenly dropped to zero. Why?
The accumulators were cleared with a clear command, ViewPoint HD or the web app. Time Since Reset shows how many seconds ago that happened. The history from before the reset stays in ModbusCloud.