DENT Instruments DENT Instruments PowerScout 12 HD Modbus TCP template

DENT Instruments PowerScout 12 HD

Multi-circuit submeter that measures current, voltage, power, and energy on up to 12 CT channels.

The DENT Instruments PowerScout 12 HD is a networked multi-circuit power submeter that measures up to four three-phase or twelve single-phase circuits in the electrical panels of commercial and industrial buildings. This Modbus TCP template reads current, voltage, power, power factor and energy per channel and per element, and lets you set CT ratings, service type and pulse inputs or clear energy totals from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
227, read and write
Key readings
Current per channel · Voltage L-N and L-L · Real power · Imported energy · Exported energy · Power factor · Peak demand · Frequency
Available commands
CT rating and type · Service type · Clear energy totals · Clear peak demand · Pulse input scaling
Compatible models
PowerScout 12 HD (PS12HD) · PowerScout 3 HD (PS3HD) · PowerScout 24 HD (PS24HD) · PowerScout 48 HD (PS48HD)
Last updated

Registers (227)

217 read, 91 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Current Avg ElementARead
Current CH1ARead
Current CH2ARead
Current CH3ARead
Voltage L-N Avg ElementVRead
Voltage L1-NVRead
Voltage L2-NVRead
Voltage L3-NVRead
Voltage L-L Avg ElementVRead
Voltage L1-L2VRead
Voltage L2-L3VRead
Voltage L3-L1VRead
Line FrequencyHzRead
Power Sum ElementkWRead
Power CH1kWRead
Power CH2kWRead
Power CH3kWRead
VA Sum ElementkVARead
VA CH1kVARead
VA CH2kVARead
VA CH3kVARead
VAR Sum ElementkvarRead
VAR CH1kvarRead
VAR CH2kvarRead
VAR CH3kvarRead
Apparent PF Avg ElementRead
Apparent PF CH1Read
Apparent PF CH2Read
Apparent PF CH3Read
Exported Energy Sum ElementkWhRead
Exported Energy CH1kWhRead
Exported Energy CH2kWhRead
Exported Energy CH3kWhRead
Imported Energy Sum ElementkWhRead
Imported Energy CH1kWhRead
Imported Energy CH2kWhRead
Imported Energy CH3kWhRead
Exported VAh Sum ElementkVAhRead
Exported VAh CH1kVAhRead
Exported VAh CH2kVAhRead
Exported VAh CH3kVAhRead
Imported VAh Sum ElementkVAhRead
Imported VAh CH1kVAhRead
Imported VAh CH2kVAhRead
Imported VAh CH3kVAhRead
Imported VARh Q1 Sum ElementkvarhRead
Imported VARh Q1 CH1kvarhRead
Imported VARh Q1 CH2kvarhRead
Imported VARh Q1 CH3kvarhRead
Imported VARh Q2 Sum ElementkvarhRead
Imported VARh Q2 CH1kvarhRead
Imported VARh Q2 CH2kvarhRead
Imported VARh Q2 CH3kvarhRead
Exported VARh Q3 Sum ElementkvarhRead
Exported VARh Q3 CH1kvarhRead
Exported VARh Q3 CH2kvarhRead
Exported VARh Q3 CH3kvarhRead
Exported VARh Q4 Sum ElementkvarhRead
Exported VARh Q4 CH1kvarhRead
Exported VARh Q4 CH2kvarhRead
Exported VARh Q4 CH3kvarhRead
Active Energy Net Sum ElementkWhRead
Active Energy Net CH1kWhRead
Active Energy Net CH2kWhRead
Active Energy Net CH3kWhRead
Apparent Energy Net Sum ElementkVAhRead
Apparent Energy Net CH1kVAhRead
Apparent Energy Net CH2kVAhRead
Apparent Energy Net CH3kVAhRead
Reactive Energy Net Sum ElementkvarhRead
Reactive Energy Net CH1kvarhRead
Reactive Energy Net CH2kvarhRead
Reactive Energy Net CH3kvarhRead
Watt Peak Demand ElementkWRead
Watt Demand This Interval ElementkWRead
VA Peak Demand ElementkVARead
VA Demand This Interval ElementkVARead
Displacement PF Avg ElementRead
Displacement PF CH1Read
Displacement PF CH2Read
Displacement PF CH3Read
Apparent PF ElementRead
Apparent PF CH1 DuplicateRead
Apparent PF CH2 DuplicateRead
Apparent PF CH3 DuplicateRead
Distortion PF Avg ElementRead
Distortion PF CH1Read
Distortion PF CH2Read
Distortion PF CH3Read
THD Avg Element%Read
THD CH1%Read
THD CH2%Read
THD CH3%Read
Theta CH1°Read
Theta CH2°Read
Theta CH3°Read
Theta Element°Read
Pulse Input 1 AccumulatorRead
Pulse Input 2 AccumulatorRead
Pulse Input 3 AccumulatorRead
Pulse Input 4 AccumulatorRead
Time Since ResetsRead
EventsRead
Phase Check System StatusRead
Phase Check Element StatusRead
Alarm Output StatusRead and write
Voltage Vin1 Alarm Status UnderRead
Voltage Vin2 Alarm Status UnderRead
Reset ProcessorWrite
Clear Accumulated Measurements AllWrite
Clear Accumulated Measurements ElementWrite
Clear Peak Demand ElementWrite
Clear Peak Demand AllWrite
Reset to User DefaultsWrite
Pulse Input 1 Accumulator ClearWrite
Pulse Input 2 Accumulator ClearWrite
Pulse Input 3 Accumulator ClearWrite
Pulse Input 4 Accumulator ClearWrite
Demand Window TypeRead
Demand WindowminRead
Volt Multiplier VINPUT1Read and write
Volt Multiplier VINPUT2Read and write
Service Type ElementRead and write
Millivolt Snap Threshold%Read and write
RoCoil Snap Threshold%Read and write
Voltage Snap ThresholdVRead and write
Communications ModeRead
RoCoil Millivolt per KiloampRead and write
Voltage Input ElementRead and write
CH1 CT Full Scale RatingARead and write
CH1 CT Voltage ReferenceRead and write
CH1 CT MultiplierRead and write
CH1 CT TypeRead and write
CH1 CT Phase Shift°Read and write
CH1 CT SignRead and write
CH2 CT Full Scale RatingARead and write
CH2 CT Voltage ReferenceRead and write
CH2 CT MultiplierRead and write
CH2 CT TypeRead and write
CH2 CT Phase Shift°Read and write
CH2 CT SignRead and write
CH3 CT Full Scale RatingARead and write
CH3 CT Voltage ReferenceRead and write
CH3 CT MultiplierRead and write
CH3 CT TypeRead and write
CH3 CT Phase Shift°Read and write
CH3 CT SignRead and write
PF Sign ConventionRead and write
Communication Inactivity TimeoutminRead and write
User ConfigRead and write
Pulse Input 1 EnableRead and write
Pulse Input 1 Scale FactorRead and write
Pulse Input 1 UnitsRead and write
Pulse Input 2 EnableRead and write
Pulse Input 2 Scale FactorRead and write
Pulse Input 2 UnitsRead and write
Pulse Input 3 EnableRead and write
Pulse Input 3 Scale FactorRead and write
Pulse Input 3 UnitsRead and write
Pulse Input 4 EnableRead and write
Pulse Input 4 Scale FactorRead and write
Pulse Input 4 UnitsRead and write
Voltage Alarm Vin1 MaskRead and write
Voltage Alarm Vin2 MaskRead and write
Voltage Alarm Vin1 L1N UnderVRead and write
Voltage Alarm Vin1 L2N UnderVRead and write
Voltage Alarm Vin1 L3N UnderVRead and write
Voltage Alarm Vin1 L1L2 UnderVRead and write
Voltage Alarm Vin1 L2L3 UnderVRead and write
Voltage Alarm Vin1 L3L1 UnderVRead and write
Voltage Alarm Vin2 L1N UnderVRead and write
Voltage Alarm Vin2 L2N UnderVRead and write
Voltage Alarm Vin2 L3N UnderVRead and write
Voltage Alarm Vin2 L1L2 UnderVRead and write
Voltage Alarm Vin2 L2L3 UnderVRead and write
Voltage Alarm Vin2 L3L1 UnderVRead and write
Voltage Alarm PersistencesRead and write
Real Time ClocksRead and write
System DescriptionRead and write
Element DescriptionRead and write
BACnet DescriptionRead
Modbus Device AddressRead and write
DHCP Static ConfigRead and write
NTP DNS ControlRead and write
IP AddressRead and write
NetmaskRead and write
IP GatewayRead and write
DNS1 AddressRead and write
DNS2 AddressRead and write
MAC AddressRead
Link ControlRead
Serial Interface NameRead and write
Serial Baud RateRead and write
Serial Data BitsRead and write
Serial ParityRead and write
Serial DuplexRead and write
Serial Flow ControlRead and write
Serial Interface TypeRead
Serial Protocol SelectionRead
Modbus TCP PortRead
BACnet UDP PortRead and write
BACnet Vendor IDRead
BACnet Device IDRead and write
BACnet Max Info FramesRead and write
BACnet Max MastersRead and write
BBMD IP AddressRead and write
LCD WebApp Read PasswordRead and write
LCD WebApp Read Write PasswordRead and write
ManufacturerRead
ModelRead
OptionsRead
Firmware VersionRead
Serial NumberRead
Network Interface NameRead
SunSpec IDRead
SunSpec Common Model IDRead
SunSpec Common Model LengthRead
Common Model PadRead
SunSpec Network Model IDRead
SunSpec Network Model LengthRead
Network Model PadRead
SunSpec Serial Model IDRead
SunSpec Serial Model LengthRead
SunSpec Meter Model IDRead
SunSpec Meter Model LengthRead
SunSpec End MarkerRead
SunSpec End LengthRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show live kW, current and voltage per circuit on a ModbusCloud dashboard, on a computer or in the browser on a phone.
  • Keep 12 months of kWh history per circuit and compare tenants, floors or machines in Trends.
  • Email a scheduled PDF report with imported, exported and net kWh per element.
  • Get an email alarm when 15 minute demand or a channel current passes a threshold you set.
  • Get notified when the voltage alarm status or phase check status of the meter changes.
  • Clear peak demand or energy totals remotely at the start of a billing period.

Installation

  1. Connect the ModbusCloud Gateway to the same local network as the Ethernet port of the PowerScout 12 HD.

  2. Give the meter a fixed IP address. It uses DHCP by default; set a static address on the display, in the web app or with ViewPoint HD.

  3. In ModbusCloud, add a Modbus device with the IP address of the meter, port 502 and unit ID 1 for element A, and import this template.

  4. Repeat for every element in use: unit ID 2 for element B, 3 for C and 4 for D.

  5. Check that current, voltage and kWh come in and match the values on the meter display or in the web app.

Things to watch for

The meter does not answer on Modbus TCP. What should I check?

Check that the ModbusCloud Gateway and the meter are in the same subnet and that the IP address is right. With DHCP the address can change after a power cycle, so give the meter a static address. The Modbus port is fixed at 502 and element A answers on unit ID 1.

Why do I only see the values of three channels?

Each element of three channels has its own Modbus address. Unit ID 1 is element A, 2 is B, 3 is C and 4 is D. Add a Modbus device per element with this template. Pulse inputs, network settings and identification are the same on every address.

A channel shows negative power. What is wrong?

The CT is probably mounted the wrong way round or paired with the wrong voltage. Turn the CT around or set CT Sign to Reversed for that channel, and check CT Voltage Reference. The phase check status values show the result of the meter's own phase check per CT.

Can I change CT settings or clear totals from ModbusCloud?

Yes. CT, service type, pulse input and alarm settings are writable, and the clear commands take the value 1234. Network and serial changes only take effect after you write 1234 to Reset Processor. Write CT settings with care: they change every reading of that channel.

The energy totals suddenly dropped to zero. Why?

The accumulators were cleared with a clear command, ViewPoint HD or the web app. Time Since Reset shows how many seconds ago that happened. The history from before the reset stays in ModbusCloud.

More TCP templates