EnerCharge EnerCharge DC-Supercharger Modbus TCP template

EnerCharge DC-Supercharger

Monitors and controls an EnerCharge DC supercharger e-charging station via Modbus TCP.

This template integrates the EnerCharge DC-Supercharger e-charging station via Modbus TCP. It reads charging status, power, SOC, voltage, current, and remaining charge times. It also allows setting power limits and emergency power limits.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
16, read and write
Key readings
Actual Total Power · Charging State · Plug State · SOC · Resttime 80/100 · AC/DC Voltage and Current L1
Available commands
Setvalue Powerlimit · Setvalue Emergency Powerlimit
Compatible models
EnerCharge DC-Supercharger
Last updated

Registers (16)

16 read, 2 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Maximum system performanceRead
Actual_Total_PowerWRead
Minimum system performanceRead
Readback value for power limitationWRead
ChargingStateRead
Max_Power_CarWRead
Plug_StateRead
Present_EnergyWhRead
SOC%Read
Resttime_80minRead
Resttime_100minRead
PowerWRead
AC/DC Voltage_L1VRead
AC/DC Current_L1ARead
Setvalue_PowerlimitWRead and write
Setvalue_Emergency_PowerlimitWRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time charging power and state of charge on a live dashboard for site operators.
  • Set dynamic power limits to align EV charging with peak shaving or load management strategies.
  • Create an alert when plug state changes unexpectedly or charging state indicates a fault.
  • Track remaining charge times to 80% and 100% for fleet scheduling and availability planning.
  • Configure an emergency power limit as a fallback when the control system loses communication.
  • Log AC and DC voltage and current values over time for energy reporting and billing verification.

Installation

  1. Activate the complex control mode and Modbus TCP port on the EnerCharge DC-Supercharger through the station's local configuration interface.

  2. Connect the ModbusCloud Gateway to the same local network as the charging station and ensure IP connectivity.

  3. Note the IP address and Modbus TCP port of the EnerCharge DC-Supercharger and enter these in the ModbusCloud gateway configuration.

  4. Import the EnerCharge DC-Supercharger template from the ModbusCloud template library and assign it to the configured connection.

  5. Verify communication by checking that live values such as Charging State and Actual Total Power appear in the ModbusCloud dashboard.

Things to watch for

The gateway cannot connect to the EnerCharge DC-Supercharger. What should I check?

Verify that the complex control mode and the Modbus TCP port are both enabled on the charging station. Also confirm that the gateway and charger are on the same network and that no firewall is blocking the configured TCP port.

Power limit values do not seem to take effect on the charger.

Ensure that the complex control mode is active. In standard operating mode, the charger may ignore external setpoints. Also verify you are writing the correct data format and unit expected by the charger.

SOC and Resttime registers show zero even though a vehicle is charging.

Some values are only populated once a charging session is actively underway and the vehicle provides SOC data. Not all vehicles transmit SOC information to the charger, which may result in zero values.

What happens if the ModbusCloud gateway loses connection to the charger?

The EnerCharge DC-Supercharger can fall back to the configured Emergency Powerlimit value. Make sure this value is set appropriately so the station continues to operate safely without active control.