Oxycom Oxycom adiabatic cooling intercool Modbus TCP template

Oxycom adiabatic cooling intercool

Monitors and controls Oxycom adiabatic cooling systems via Modbus TCP

This template connects Oxycom IntrCooll adiabatic cooling systems to ModbusCloud via Modbus TCP. It reads temperatures, water consumption, energy data, fan status, damper positions, and alarms. It also allows control of thermostat settings, fan speed, operation modes, and cooling or heating enable.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
58, read and write
Brand
Oxycom
Key readings
Outdoor and supply temperatures · Water consumption (m3 and liters) · Energy meter (kWh and Watt) · Water conductivity and level · Damper ventilation position · Alarm registers (1 to 13)
Available commands
Unit and thermostat on/off · Operation mode selection · Fan speed / temp setpoint · Cooling and heating enable
Compatible models
Oxycom IntrCooll
Last updated

Registers (58)

42 read, 24 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
244 WATER_CONSUMPTION_COUNTER_CUBICm³Read
245 WATER_CONSUMPTION_COUNTER_LITERlRead
246 WATER_FLOW_CURRENTlRead
249 ENERGY_METER_KWHKW/HRead
251 ENERGY_METER_WATTKW/HRead
700 R_OPERATION_MODERead
701 R_OUTDOOR_TEMPERATURE_SENSOR°CRead
703 R_INTRCOOLL_SUPPLY_TEMPERATURE_SENSOR°CRead
702 R_HEAT_RECLAIM_SUPPLY_TEMP°CRead
705 R_WATER_LEVELstepRead
713 R_DAMPER_VENTILATION%Read
720 R_WATER_CONDUCTIVITYuS/cmRead
733 R_WATER_MANAGMENT_MODERead
218 ALARM_ACTIVERead
219 ALARM_1Read
220 ALARM_2Read
221 ALARM_3Read
222 ALARM_4Read
223 ALARM_5Read
224 ALARM_6Read
225 ALARM_7Read
226 ALARM_8Read
227 ALARM_9Read
228 ALARM_10Read
229 ALARM_11Read
230 ALARM_12Read
231 ALARM_13Read
722 R_PUMPRead
723 R_WATER_DISINFECTIONRead
724 R_SUPPLY_SOLENOIDRead
725 R_DRAIN_VALVERead
726 R_FREEZE_PROTECTION_VALVERead
100 THERMOSTAT_ON_OFFRead and write
525 C_HYGIENE_ON_OFFRead and write
103 THERMOSTAT_P_FAN_SPEED_OR_THERMOSTAT_NP_TEMP_SETPOINT%Read and write
111 THERMOSTAT_ACTUAL_OPERATION_MODERead and write
110 THERMOSTAT_SELECTED_OPERATION_MODERead and write
292 UNIT_ON_OFFRead and write
731 Baromatic presurePaRead
307 Minimum ExcaustRead and write
801 Manual mode selectionRead and write
716 Suply fanRead
203 DIGITAL_INPUT_J12_FUNCTIONWrite
308 H_MAXIMUM_EXHAUST_VENTILATION%Write
401 FC_RELEASE_TEMERATURE°CWrite
501 C_RELEASE_TEMPERATURE°CWrite
502 C_FAN_1_MINIMUM_SPEED%Write
503 C_FAN_1_MAXIMUM_SPEED%Write
515 C_MAX_CONDUCTIVITYus/cmWrite
526 C_HYGIENE_START_TIMEWrite
530 C_WINTER_STARTWrite
531 C_WINTER_ENDWrite
239 ALARM_RESETWrite
300 H_ENABLEWrite
400 FC_ENABLEWrite
500 C_ENABLEWrite
529 C_WINTER_MODEWrite
100 THERMOSTAT_ON_OFF holdingWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor outdoor and supply air temperatures on a live dashboard to verify cooling performance.
  • Track water consumption and energy usage over time to report on sustainability metrics.
  • Create an alert when any of the 13 alarm registers activates, so you can respond to faults quickly.
  • Remotely adjust fan speed and temperature setpoints to optimize comfort without a site visit.
  • Switch between cooling and heating enable modes remotely when seasonal conditions change.
  • Log energy meter data in kWh to generate monthly efficiency reports for your customer.

Installation

  1. Connect the ModbusCloud Gateway to the same local network as the Oxycom IntrCooll Modbus board.

  2. Configure the Oxycom Modbus board using the configuration layout provided by Oxycom, ensuring register mapping matches the template.

  3. Set the correct IP address of the Oxycom unit in the ModbusCloud gateway configuration and verify Modbus TCP communication on port 502.

  4. Import the Oxycom IntrCooll template from the ModbusCloud template library and assign it to the gateway.

  5. Verify that key readings such as outdoor temperature, energy meter, and alarm registers appear correctly on the ModbusCloud dashboard.

  6. Note that register 227 (ALARM_9) may return a Modbus error over Ethernet, which can be safely ignored.

Things to watch for

Why does register 227 (ALARM_9) return a Modbus error?

This is a known issue when communicating via Ethernet Modbus TCP. The error on register 227 can be safely ignored and does not affect other registers or system operation.

How do I configure the Oxycom Modbus board correctly?

Use the configuration layout provided by Oxycom to set up the Modbus board. Ensure the register mapping matches the template before connecting the gateway.

What baud rate or network settings do I need for Modbus TCP?

Modbus TCP does not use a baud rate setting. Ensure the Oxycom unit and the ModbusCloud gateway are on the same network and that TCP port 502 is accessible.

Can I control the unit remotely or is this template read-only?

The template supports both reading and writing. You can control thermostat on/off, fan speed, temperature setpoints, operation mode, and cooling or heating enable directly from the ModbusCloud dashboard.

More TCP templates