Schneider Electric Schneider Electric Altivar ATV340 history, parameter sets and safety module Modbus RTU template

Schneider Electric Altivar ATV340 history, parameter sets and safety module

Fault history, parameter sets and safety module status of an Altivar ATV340 drive.

The Schneider Electric Altivar ATV340 is a variable speed drive for machines that stores a record of the conditions at each recent fault. This Modbus RTU template reads that fault history, the active parameter set and the safety module status, and lets you set up parameter sets from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
421, read and write
Key readings
Fault code per fault record · Motor current at fault · Motor frequency at fault · DC bus voltage at fault · Fault date and time · Active parameter set · Safety module status
Available commands
Parameter set selection · Parameter set addresses · Parameter set values
Compatible models
Altivar Machine ATV340 (ATV340U07N4 to ATV340D75N4, including E versions) · Schneider Electric Altivar Machine ATV340 variable speed drive
Last updated

Registers (421)

421 read, 65 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Fault Code On Last Fault (DP0)Read7200FC03uint16
DC Bus Voltage (ULP0)VRead7270FC03uint16
Motor Current (LCP0)Read7240FC03int16
Output Frequency (RFP0)HzRead7250FC03int16
Motor Thermal State (THP0)%Read7280FC03uint16
State Word (EP0)Read
ETI State Word (IP0)Read
Cmd Word (CMP0)Read
Command Channel (DCC0)Read
Channel For Reference Frequency (DRC0)Read
Channels Active On Last Fault (CRP0)Read
Run Elapsed Time (RTP0)hRead
Motor Torque (OTP0)%Read
Drive Thermal State (TDP0)%Read
IGBT Junction Temp (TJP0)°CRead
Switching Frequency (SFP0)HzRead
Fault Code On Fault n-1 (DP1)Read
DC Bus Voltage (ULP1)VRead
Motor Current (LCP1)Read
Output Frequency (RFP1)HzRead
Motor Thermal State (THP1)%Read
Status Of Last Error 1 (EP1)Read
ETI State Word (IP1)Read
Cmd Word (CMP1)Read
Command Channel (DCC1)Read
Channel For Reference Frequency (DRC1)Read
Active Channels On Fault n-1 (CRP1)Read
Run Elapsed Time (RTP1)hRead
Motor Torque (OTP1)%Read
Drive Thermal State (TDP1)%Read
IGBT Junction Temp (TJP1)°CRead
Switching Frequency (SFP1)HzRead
Fault Code On Fault n-2 (DP2)Read
DC Bus Voltage (ULP2)VRead
Motor Current (LCP2)Read
Output Frequency (RFP2)HzRead
Motor Thermal State (THP2)%Read
Status Of Last Error 2 (EP2)Read
ETI State Word (IP2)Read
Cmd Word (CMP2)Read
Command Channel (DCC2)Read
Channel For Reference Frequency (DRC2)Read
Active Channels On Fault n-2 (CRP2)Read
Run Elapsed Time (RTP2)hRead
Motor Torque (OTP2)%Read
Drive Thermal State (TDP2)%Read
IGBT Junction Temp (TJP2)°CRead
Switching Frequency (SFP2)HzRead
Fault Code On Fault n-3 (DP3)Read
DC Bus Voltage (ULP3)VRead
Motor Current (LCP3)Read
Output Frequency (RFP3)HzRead
Motor Thermal State (THP3)%Read
Status Of Last Error 3 (EP3)Read
ETI State Word (IP3)Read
Cmd Word (CMP3)Read
Command Channel (DCC3)Read
Channel For Reference Frequency (DRC3)Read
Active Channels On Fault n-3 (CRP3)Read
Run Elapsed Time (RTP3)hRead
Motor Torque (OTP3)%Read
Drive Thermal State (TDP3)%Read
IGBT Junction Temp (TJP3)°CRead
Switching Frequency (SFP3)HzRead
Fault Code On Fault n-4 (DP4)Read
DC Bus Voltage (ULP4)VRead
Motor Current (LCP4)Read
Output Frequency (RFP4)HzRead
Motor Thermal State (THP4)%Read
Status Of Last Error 4 (EP4)Read
ETI State Word (IP4)Read
Cmd Word (CMP4)Read
Command Channel (DCC4)Read
Channel For Reference Frequency (DRC4)Read
Active Channels On Fault n-4 (CRP4)Read
Run Elapsed Time (RTP4)hRead
Motor Torque (OTP4)%Read
Drive Thermal State (TDP4)%Read
IGBT Junction Temp (TJP4)°CRead
Switching Frequency (SFP4)HzRead
Fault Code On Fault n-5 (DP5)Read
DC Bus Voltage (ULP5)VRead
Motor Current (LCP5)Read
Output Frequency (RFP5)HzRead
Motor Thermal State (THP5)%Read
State Word (EP5)Read
ETI State Word (IP5)Read
Cmd Word (CMP5)Read
Command Channel (DCC5)Read
Channel For Reference Frequency (DRC5)Read
Active Channels On Fault n-5 (CRP5)Read
Run Elapsed Time (RTP5)hRead
Motor Torque (OTP5)%Read
Drive Thermal State (TDP5)%Read
IGBT Junction Temp (TJP5)°CRead
Switching Frequency (SFP5)HzRead
Fault Code On Fault n-6 (DP6)Read
DC Bus Voltage (ULP6)VRead
Motor Current (LCP6)Read
Output Frequency (RFP6)HzRead
Motor Thermal State (THP6)%Read
State Word (EP6)Read
ETI State Word (IP6)Read
Cmd Word (CMP6)Read
Command Channel (DCC6)Read
Channel For Reference Frequency (DRC6)Read
Active Channels On Fault n-6 (CRP6)Read
Run Elapsed Time (RTP6)hRead
Motor Torque (OTP6)%Read
Drive Thermal State (TDP6)%Read
IGBT Junction Temp (TJP6)°CRead
Switching Frequency (SFP6)HzRead
Fault Code On Fault n-7 (DP7)Read
DC Bus Voltage (ULP7)VRead
Motor Current (LCP7)Read
Output Frequency (RFP7)HzRead
Motor Thermal State (THP7)%Read
State Word (EP7)Read
ETI State Word (IP7)Read
Cmd Word (CMP7)Read
Command Channel (DCC7)Read
Channel For Reference Frequency (DRC7)Read
Active Channels On Fault n-7 (CRP7)Read
Run Elapsed Time (RTP7)hRead
Motor Torque (OTP7)%Read
Drive Thermal State (TDP7)%Read
IGBT Junction Temp (TJP7)°CRead
Switching Frequency (SFP7)HzRead
Fault Code On Fault n-8 (DP8)Read
DC Bus Voltage (ULP8)VRead
Motor Current (LCP8)Read
Output Frequency (RFP8)HzRead
Motor Thermal State (THP8)%Read
State Word (EP8)Read
ETI State Word (IP8)Read
Cmd Word (CMP8)Read
Command Channel (DCC8)Read
Channel For Reference Frequency (DRC8)Read
Active Channels On Fault n-8 (CRP8)Read
Run Elapsed Time (RTP8)hRead
Motor Torque (OTP8)%Read
Drive Thermal State (TDP8)%Read
IGBT Junction Temp (TJP8)°CRead
Switching Frequency (SFP8)HzRead
Parameter Set Sel 1 (CHA1)Read and write
Parameter Set Sel 2 (CHA2)Read and write
Used Parameter Set (CFPS)Read
Load Parameter Set Command (VAL)Read and write
Parameter Set Address 1 (AD01)Read and write
Parameter Set Address 2 (AD02)Read and write
Parameter Set Address 3 (AD03)Read and write
Parameter Set Address 4 (AD04)Read and write
Parameter Set Address 5 (AD05)Read and write
Parameter Set Address 6 (AD06)Read and write
Parameter Set Address 7 (AD07)Read and write
Parameter Set Address 8 (AD08)Read and write
Parameter Set Address 9 (AD09)Read and write
Parameter Set Address 10 (AD10)Read and write
Parameter Set Address 11 (AD11)Read and write
Parameter Set Address 12 (AD12)Read and write
Parameter Set Address 13 (AD13)Read and write
Parameter Set Address 14 (AD14)Read and write
Parameter Set Address 15 (AD15)Read and write
Parameter Set 1 Value 1 (S101)Read and write
Parameter Set 1 Value 2 (S102)Read and write
Parameter Set 1 Value 3 (S103)Read and write
Parameter Set 1 Value 4 (S104)Read and write
Parameter Set 1 Value 5 (S105)Read and write
Parameter Set 1 Value 6 (S106)Read and write
Parameter Set 1 Value 7 (S107)Read and write
Parameter Set 1 Value 8 (S108)Read and write
Parameter Set 1 Value 9 (S109)Read and write
Parameter Set 1 Value 10 (S110)Read and write
Parameter Set 1 Value 11 (S111)Read and write
Parameter Set 1 Value 12 (S112)Read and write
Parameter Set 1 Value 13 (S113)Read and write
Parameter Set 1 Value 14 (S114)Read and write
Parameter Set 1 Value 15 (S115)Read and write
Parameter Set 2 Value 1 (S201)Read and write
Parameter Set 2 Value 2 (S202)Read and write
Parameter Set 2 Value 3 (S203)Read and write
Parameter Set 2 Value 4 (S204)Read and write
Parameter Set 2 Value 5 (S205)Read and write
Parameter Set 2 Value 6 (S206)Read and write
Parameter Set 2 Value 7 (S207)Read and write
Parameter Set 2 Value 8 (S208)Read and write
Parameter Set 2 Value 9 (S209)Read and write
Parameter Set 2 Value 10 (S210)Read and write
Parameter Set 2 Value 11 (S211)Read and write
Parameter Set 2 Value 12 (S212)Read and write
Parameter Set 2 Value 13 (S213)Read and write
Parameter Set 2 Value 14 (S214)Read and write
Parameter Set 2 Value 15 (S215)Read and write
Parameter Set 3 Value 1 (S301)Read and write
Parameter Set 3 Value 2 (S302)Read and write
Parameter Set 3 Value 3 (S303)Read and write
Parameter Set 3 Value 4 (S304)Read and write
Parameter Set 3 Value 5 (S305)Read and write
Parameter Set 3 Value 6 (S306)Read and write
Parameter Set 3 Value 7 (S307)Read and write
Parameter Set 3 Value 8 (S308)Read and write
Parameter Set 3 Value 9 (S309)Read and write
Parameter Set 3 Value 10 (S310)Read and write
Parameter Set 3 Value 11 (S311)Read and write
Parameter Set 3 Value 12 (S312)Read and write
Parameter Set 3 Value 13 (S313)Read and write
Parameter Set 3 Value 14 (S314)Read and write
Parameter Set 3 Value 15 (S315)Read and write
Cmd Word (CMP9)Read
Cmd Word (CMPA)Read
Cmd Word (CMPB)Read
CMD Command Word (CMPC)Read
CMD Command Word (CMPD)Read
CMD Command Word (CMPE)Read
CMD Command Word (CMPF)Read
Active Channels On Error n-9 (CRP9)Read
Active Channels On Error n-10 (CRPA)Read
Active Channels On Error n-11 (CRPB)Read
Active Channels On Error n-12 (CRPC)Read
Active Channels On Error n-13 (CRPD)Read
Active Channels On Error n-14 (CRPE)Read
Active Channels On Error n-15 (CRPF)Read
Hour And Minute Of Actual Fault (DM0)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM1)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM2)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM3)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM4)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM5)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM6)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM7)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM8)Read
Hour And Minute Of Fault Record X (1 Is Last) (DM9)Read
Hour And Minute Of Fault Record X (1 Is Last) (DMA)Read
Hour And Minute Of Fault Record X (1 Is Last) (DMB)Read
Hour And Minute Of Fault Record X (1 Is Last) (DMC)Read
Hour And Minute Of Fault Record X (1 Is Last) (DMD)Read
Hour And Minute Of Fault Record X (1 Is Last) (DME)Read
Hour And Minute Of Fault Record X (1 Is Last) (DMF)Read
Last Error 9 (DP9)Read
Last Error 10 (DPA)Read
Last Error 11 (DPB)Read
Last Error 12 (DPC)Read
Last Error 13 (DPD)Read
Last Error 14 (DPE)Read
Last Error 15 (DPF)Read
State Word (EP9)Read
State Word (EPA)Read
State Word (EPB)Read
State Word (EPC)Read
State Word (EPD)Read
State Word (EPE)Read
State Word (EPF)Read
Device State (HS9)Read
Device State (HSA)Read
Device State (HSB)Read
Device State (HSC)Read
Device State (HSD)Read
Device State (HSE)Read
Device State (HSF)Read
ETI State Word (IP9)Read
ETI State Word (IPA)Read
ETI State Word (IPB)Read
ETI State Word (IPC)Read
ETI State Word (IPD)Read
ETI State Word (IPE)Read
ETI State Word (IPF)Read
Motor Current (LCP9)Read
Motor Current (LCPA)Read
Motor Current (LCPB)Read
Motor Current (LCPC)Read
Motor Current (LCPD)Read
Motor Current (LCPE)Read
Motor Current (LCPF)Read
Year, Month And Day Of Actual Fault (MD0)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD1)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD2)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD3)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD4)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD5)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD6)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD7)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD8)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MD9)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MDA)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MDB)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MDC)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MDD)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MDE)Read
Year, Month And Day Of Fault Record X (1 Is Last) (MDF)Read
Motor Torque (OTP9)%Read
Motor Torque (OTPA)%Read
Motor Torque (OTPB)%Read
Motor Torque (OTPC)%Read
Motor Torque (OTPD)%Read
Motor Torque (OTPE)%Read
Motor Torque (OTPF)%Read
Motor Frequency (RFP9)HzRead
Motor Frequency (RFPA)HzRead
Motor Frequency (RFPB)HzRead
Motor Frequency (RFPC)HzRead
Motor Frequency (RFPD)HzRead
Motor Frequency (RFPE)HzRead
Motor Frequency (RFPF)HzRead
Run Elapsed Time (RTP9)hRead
Run Elapsed Time (RTPA)hRead
Run Elapsed Time (RTPB)hRead
Run Elapsed Time (RTPC)hRead
Run Elapsed Time (RTPD)hRead
Run Elapsed Time (RTPE)hRead
Run Elapsed Time (RTPF)hRead
Switching Frequency (SFP9)HzRead
Switching Frequency (SFPA)HzRead
Switching Frequency (SFPB)HzRead
Switching Frequency (SFPC)HzRead
Switching Frequency (SFPD)HzRead
Switching Frequency (SFPE)HzRead
Switching Frequency (SFPF)HzRead
Drive Thermal State (TDP9)%Read
Drive Thermal State (TDPA)%Read
Drive Thermal State (TDPB)%Read
Drive Thermal State (TDPC)%Read
Drive Thermal State (TDPD)%Read
Drive Thermal State (TDPE)%Read
Drive Thermal State (TDPF)%Read
Motor Thermal State (THP9)%Read
Motor Thermal State (THPA)%Read
Motor Thermal State (THPB)%Read
Motor Thermal State (THPC)%Read
Motor Thermal State (THPD)%Read
Motor Thermal State (THPE)%Read
Motor Thermal State (THPF)%Read
IGBT Junction Temp (TJP9)°CRead
IGBT Junction Temp (TJPA)°CRead
IGBT Junction Temp (TJPB)°CRead
IGBT Junction Temp (TJPC)°CRead
IGBT Junction Temp (TJPD)°CRead
IGBT Junction Temp (TJPE)°CRead
IGBT Junction Temp (TJPF)°CRead
DC Bus Voltage (ULP9)VRead
DC Bus Voltage (ULPA)VRead
DC Bus Voltage (ULPB)VRead
DC Bus Voltage (ULPC)VRead
DC Bus Voltage (ULPD)VRead
DC Bus Voltage (ULPE)VRead
DC Bus Voltage (ULPF)VRead
Channel For Reference Frequency (DRC9)Read
Channel For Reference Frequency (DRCA)Read
Channel For Reference Frequency (DRCB)Read
Channel For Reference Frequency (DRCC)Read
Channel For Reference Frequency (DRCD)Read
Channel For Reference Frequency (DRCE)Read
Channel For Reference Frequency (DRCF)Read
Command Channel (DCC9)Read
Command Channel (DCCA)Read
Command Channel (DCCB)Read
Command Channel (DCCZ)Read
Command Channel (DCCD)Read
Command Channel (DCCE)Read
Command Channel (DCCF)Read
Internal Error 6 (Module Identification Error) Informati (INF6)Read
Internal Error 19 (Encoder) (INFJ)Read
Encoder Feedback Error Number (ENCE)Read
HMI Status (HS1)Read
HMI Status (HS2)Read
HMI Status (HS3)Read
HMI Status (HS4)Read
HMI Status (HS5)Read
HMI Status (HS6)Read
HMI Status (HS7)Read
HMI Status (HS8)Read
Safety Module Status (SSTA)Read
Safety Configuration Status (SCNA)Read
Active Safety Function (SFCA)Read
Safety Input Word A (SIWA)Read
Safety Output Word A (SQWA)Read
Test Command Activation (FSCA)Read and write
Test Ramp Command (FSRC)Read and write
Safety Input Word B (SIWB)Read
Safety Output Word B (SQWB)Read
Safety Module Error (SMLE)Read
Safety Module Error 0 (SME0)Read
Safety Module Error 1 (SME1)Read
Safety Module Error 2 (SME2)Read
Safety Module Error 3 (SME3)Read
Safety Module Error 4 (SME4)Read
Safety Module Error 5 (SME5)Read
Safety Module Error 6 (SME6)Read
Safety Module Error 7 (SME7)Read
Safety Module Error 8 (SME8)Read
Safety Module Error 9 (SME9)Read
Safety Fast Monitoring Parameter 0 (SFM0)Read
Safety Fast Monitoring Parameter 1 (SFM1)Read
Safety Fast Monitoring Parameter 2 (SFM2)Read
Safety Fast Monitoring Parameter 3 (SFM3)Read
Safety Fast Monitoring Parameter 4 (SFM4)Read
Safety Fast Monitoring Parameter 5 (SFM5)Read
Safety Fast Monitoring Parameter 6 (SFM6)Read
Safety Fast Monitoring Parameter 7 (SFM7)Read
Safety Fast Monitoring Parameter 8 (SFM8)Read
Safety Supervisor Object Status (SSM0)Read
PROFIsafe Communication State (SSM1)Read
Safety Slow Monitoring Parameter 2 (SSM2)Read
Safety Slow Monitoring Parameter 3 (SSM3)Read
Safety Slow Monitoring Parameter 4 (SSM4)Read
Safety Slow Monitoring Parameter 5 (SSM5)Read
Safety Slow Monitoring Parameter 6 (SSM6)Read
Safety Slow Monitoring Parameter 7 (SSM7)Read
Safety Status Word Bytes 1-0 (SSW0)Read
Safety Status Word Bytes 3-2 (SSW1)Read
Safety Status Word Bytes 5-4 (SSW2)Read
Safety Status Word Bytes 7-6 (SSW3)Read
Safety Status Word Bytes 9-8 (SSW4)Read
Safety Status Word Bytes 11-10 (SSW5)Read
Safety Status Word Bytes 13-12 (SSW6)Read
Safety Command Word Bytes 1-0 (SCW0)Read
Safety Command Word Bytes 3-2 (SCW1)Read
Safety Command Word Bytes 5-4 (SCW2)Read
Safety Command Word Bytes 7-6 (SCW3)Read
Safety Command Word Bytes 9-8 (SCW4)Read
Safety Command Word Bytes 11-10 (SCW5)Read
Safety Command Word Bytes 13-12 (SCW6)Read

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Read the fault code and motor conditions of the last trips to find out why a drive stopped.
  • Keep a 365-day history of fault records to spot drives that trip on overcurrent or overheating more often.
  • Set an alert when the fault code on last fault changes, so you hear by email about a new trip.
  • Check which parameter set is active on a machine that switches between products or modes.
  • Watch safety module errors and the active safety function on a dashboard for each drive.

Installation

  1. Connect the RJ45 Modbus port of the ATV340 to RS485 A and B of the ModbusCloud Gateway and terminate the bus at both ends.

  2. On the drive, set Modbus Address (1 to 247), baud rate and format; the factory setting is 19200 baud, 8E1, address OFF.

  3. In ModbusCloud, add a Modbus device with the same settings, or use the device of the core ATV340 template, and import this template.

  4. Check that Fault Code On Last Fault (DP0) and the fault date match the fault history on the drive display.

Things to watch for

How do I read the fault code as text?

The fault code is a number from the ATV340 fault list, the same list the drive display uses for its fault history. Look it up in the programming manual or the communication parameter list of the drive. A value of 0 means no fault stored in that record.

Why does motor current show an odd value?

Motor current and a few power values have a scale that depends on the drive rating, so the template reads them raw. Compare one value with the drive display once and apply the factor you find in the programming manual for your rating.

The drive does not answer at all. What should I check?

The Modbus address is OFF from the factory, so the drive stays silent until you set it. Then check baud rate and format (default 19200, 8E1), swap A and B if needed and terminate the bus at both ends.

Can I change parameter sets from ModbusCloud?

Yes, the parameter set addresses and values are writable, and the selection inputs too, but those only accept a new value with the motor stopped. A wrong parameter address changes the wrong setting, so write one value at a time, check it on the drive and agree changes with whoever runs the machine.

Want to see how it works?