Schneider Electric Altivar ATV340 history, parameter sets and safety module
Fault history, parameter sets and safety module status of an Altivar ATV340 drive.
The Schneider Electric Altivar ATV340 is a variable speed drive for machines that stores a record of the conditions at each recent fault. This Modbus RTU template reads that fault history, the active parameter set and the safety module status, and lets you set up parameter sets from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 421, read and write
- Brand
- Schneider Electric
- Key readings
- Fault code per fault record · Motor current at fault · Motor frequency at fault · DC bus voltage at fault · Fault date and time · Active parameter set · Safety module status
- Available commands
- Parameter set selection · Parameter set addresses · Parameter set values
- Compatible models
- Altivar Machine ATV340 (ATV340U07N4 to ATV340D75N4, including E versions) · Schneider Electric Altivar Machine ATV340 variable speed drive
- Last updated
Registers (421)
421 read, 65 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Fault Code On Last Fault (DP0) | Read | 7200 | FC03 | uint16 | |
| DC Bus Voltage (ULP0) | V | Read | 7270 | FC03 | uint16 |
| Motor Current (LCP0) | Read | 7240 | FC03 | int16 | |
| Output Frequency (RFP0) | Hz | Read | 7250 | FC03 | int16 |
| Motor Thermal State (THP0) | % | Read | 7280 | FC03 | uint16 |
| State Word (EP0) | Read | ||||
| ETI State Word (IP0) | Read | ||||
| Cmd Word (CMP0) | Read | ||||
| Command Channel (DCC0) | Read | ||||
| Channel For Reference Frequency (DRC0) | Read | ||||
| Channels Active On Last Fault (CRP0) | Read | ||||
| Run Elapsed Time (RTP0) | h | Read | |||
| Motor Torque (OTP0) | % | Read | |||
| Drive Thermal State (TDP0) | % | Read | |||
| IGBT Junction Temp (TJP0) | °C | Read | |||
| Switching Frequency (SFP0) | Hz | Read | |||
| Fault Code On Fault n-1 (DP1) | Read | ||||
| DC Bus Voltage (ULP1) | V | Read | |||
| Motor Current (LCP1) | Read | ||||
| Output Frequency (RFP1) | Hz | Read | |||
| Motor Thermal State (THP1) | % | Read | |||
| Status Of Last Error 1 (EP1) | Read | ||||
| ETI State Word (IP1) | Read | ||||
| Cmd Word (CMP1) | Read | ||||
| Command Channel (DCC1) | Read | ||||
| Channel For Reference Frequency (DRC1) | Read | ||||
| Active Channels On Fault n-1 (CRP1) | Read | ||||
| Run Elapsed Time (RTP1) | h | Read | |||
| Motor Torque (OTP1) | % | Read | |||
| Drive Thermal State (TDP1) | % | Read | |||
| IGBT Junction Temp (TJP1) | °C | Read | |||
| Switching Frequency (SFP1) | Hz | Read | |||
| Fault Code On Fault n-2 (DP2) | Read | ||||
| DC Bus Voltage (ULP2) | V | Read | |||
| Motor Current (LCP2) | Read | ||||
| Output Frequency (RFP2) | Hz | Read | |||
| Motor Thermal State (THP2) | % | Read | |||
| Status Of Last Error 2 (EP2) | Read | ||||
| ETI State Word (IP2) | Read | ||||
| Cmd Word (CMP2) | Read | ||||
| Command Channel (DCC2) | Read | ||||
| Channel For Reference Frequency (DRC2) | Read | ||||
| Active Channels On Fault n-2 (CRP2) | Read | ||||
| Run Elapsed Time (RTP2) | h | Read | |||
| Motor Torque (OTP2) | % | Read | |||
| Drive Thermal State (TDP2) | % | Read | |||
| IGBT Junction Temp (TJP2) | °C | Read | |||
| Switching Frequency (SFP2) | Hz | Read | |||
| Fault Code On Fault n-3 (DP3) | Read | ||||
| DC Bus Voltage (ULP3) | V | Read | |||
| Motor Current (LCP3) | Read | ||||
| Output Frequency (RFP3) | Hz | Read | |||
| Motor Thermal State (THP3) | % | Read | |||
| Status Of Last Error 3 (EP3) | Read | ||||
| ETI State Word (IP3) | Read | ||||
| Cmd Word (CMP3) | Read | ||||
| Command Channel (DCC3) | Read | ||||
| Channel For Reference Frequency (DRC3) | Read | ||||
| Active Channels On Fault n-3 (CRP3) | Read | ||||
| Run Elapsed Time (RTP3) | h | Read | |||
| Motor Torque (OTP3) | % | Read | |||
| Drive Thermal State (TDP3) | % | Read | |||
| IGBT Junction Temp (TJP3) | °C | Read | |||
| Switching Frequency (SFP3) | Hz | Read | |||
| Fault Code On Fault n-4 (DP4) | Read | ||||
| DC Bus Voltage (ULP4) | V | Read | |||
| Motor Current (LCP4) | Read | ||||
| Output Frequency (RFP4) | Hz | Read | |||
| Motor Thermal State (THP4) | % | Read | |||
| Status Of Last Error 4 (EP4) | Read | ||||
| ETI State Word (IP4) | Read | ||||
| Cmd Word (CMP4) | Read | ||||
| Command Channel (DCC4) | Read | ||||
| Channel For Reference Frequency (DRC4) | Read | ||||
| Active Channels On Fault n-4 (CRP4) | Read | ||||
| Run Elapsed Time (RTP4) | h | Read | |||
| Motor Torque (OTP4) | % | Read | |||
| Drive Thermal State (TDP4) | % | Read | |||
| IGBT Junction Temp (TJP4) | °C | Read | |||
| Switching Frequency (SFP4) | Hz | Read | |||
| Fault Code On Fault n-5 (DP5) | Read | ||||
| DC Bus Voltage (ULP5) | V | Read | |||
| Motor Current (LCP5) | Read | ||||
| Output Frequency (RFP5) | Hz | Read | |||
| Motor Thermal State (THP5) | % | Read | |||
| State Word (EP5) | Read | ||||
| ETI State Word (IP5) | Read | ||||
| Cmd Word (CMP5) | Read | ||||
| Command Channel (DCC5) | Read | ||||
| Channel For Reference Frequency (DRC5) | Read | ||||
| Active Channels On Fault n-5 (CRP5) | Read | ||||
| Run Elapsed Time (RTP5) | h | Read | |||
| Motor Torque (OTP5) | % | Read | |||
| Drive Thermal State (TDP5) | % | Read | |||
| IGBT Junction Temp (TJP5) | °C | Read | |||
| Switching Frequency (SFP5) | Hz | Read | |||
| Fault Code On Fault n-6 (DP6) | Read | ||||
| DC Bus Voltage (ULP6) | V | Read | |||
| Motor Current (LCP6) | Read | ||||
| Output Frequency (RFP6) | Hz | Read | |||
| Motor Thermal State (THP6) | % | Read | |||
| State Word (EP6) | Read | ||||
| ETI State Word (IP6) | Read | ||||
| Cmd Word (CMP6) | Read | ||||
| Command Channel (DCC6) | Read | ||||
| Channel For Reference Frequency (DRC6) | Read | ||||
| Active Channels On Fault n-6 (CRP6) | Read | ||||
| Run Elapsed Time (RTP6) | h | Read | |||
| Motor Torque (OTP6) | % | Read | |||
| Drive Thermal State (TDP6) | % | Read | |||
| IGBT Junction Temp (TJP6) | °C | Read | |||
| Switching Frequency (SFP6) | Hz | Read | |||
| Fault Code On Fault n-7 (DP7) | Read | ||||
| DC Bus Voltage (ULP7) | V | Read | |||
| Motor Current (LCP7) | Read | ||||
| Output Frequency (RFP7) | Hz | Read | |||
| Motor Thermal State (THP7) | % | Read | |||
| State Word (EP7) | Read | ||||
| ETI State Word (IP7) | Read | ||||
| Cmd Word (CMP7) | Read | ||||
| Command Channel (DCC7) | Read | ||||
| Channel For Reference Frequency (DRC7) | Read | ||||
| Active Channels On Fault n-7 (CRP7) | Read | ||||
| Run Elapsed Time (RTP7) | h | Read | |||
| Motor Torque (OTP7) | % | Read | |||
| Drive Thermal State (TDP7) | % | Read | |||
| IGBT Junction Temp (TJP7) | °C | Read | |||
| Switching Frequency (SFP7) | Hz | Read | |||
| Fault Code On Fault n-8 (DP8) | Read | ||||
| DC Bus Voltage (ULP8) | V | Read | |||
| Motor Current (LCP8) | Read | ||||
| Output Frequency (RFP8) | Hz | Read | |||
| Motor Thermal State (THP8) | % | Read | |||
| State Word (EP8) | Read | ||||
| ETI State Word (IP8) | Read | ||||
| Cmd Word (CMP8) | Read | ||||
| Command Channel (DCC8) | Read | ||||
| Channel For Reference Frequency (DRC8) | Read | ||||
| Active Channels On Fault n-8 (CRP8) | Read | ||||
| Run Elapsed Time (RTP8) | h | Read | |||
| Motor Torque (OTP8) | % | Read | |||
| Drive Thermal State (TDP8) | % | Read | |||
| IGBT Junction Temp (TJP8) | °C | Read | |||
| Switching Frequency (SFP8) | Hz | Read | |||
| Parameter Set Sel 1 (CHA1) | Read and write | ||||
| Parameter Set Sel 2 (CHA2) | Read and write | ||||
| Used Parameter Set (CFPS) | Read | ||||
| Load Parameter Set Command (VAL) | Read and write | ||||
| Parameter Set Address 1 (AD01) | Read and write | ||||
| Parameter Set Address 2 (AD02) | Read and write | ||||
| Parameter Set Address 3 (AD03) | Read and write | ||||
| Parameter Set Address 4 (AD04) | Read and write | ||||
| Parameter Set Address 5 (AD05) | Read and write | ||||
| Parameter Set Address 6 (AD06) | Read and write | ||||
| Parameter Set Address 7 (AD07) | Read and write | ||||
| Parameter Set Address 8 (AD08) | Read and write | ||||
| Parameter Set Address 9 (AD09) | Read and write | ||||
| Parameter Set Address 10 (AD10) | Read and write | ||||
| Parameter Set Address 11 (AD11) | Read and write | ||||
| Parameter Set Address 12 (AD12) | Read and write | ||||
| Parameter Set Address 13 (AD13) | Read and write | ||||
| Parameter Set Address 14 (AD14) | Read and write | ||||
| Parameter Set Address 15 (AD15) | Read and write | ||||
| Parameter Set 1 Value 1 (S101) | Read and write | ||||
| Parameter Set 1 Value 2 (S102) | Read and write | ||||
| Parameter Set 1 Value 3 (S103) | Read and write | ||||
| Parameter Set 1 Value 4 (S104) | Read and write | ||||
| Parameter Set 1 Value 5 (S105) | Read and write | ||||
| Parameter Set 1 Value 6 (S106) | Read and write | ||||
| Parameter Set 1 Value 7 (S107) | Read and write | ||||
| Parameter Set 1 Value 8 (S108) | Read and write | ||||
| Parameter Set 1 Value 9 (S109) | Read and write | ||||
| Parameter Set 1 Value 10 (S110) | Read and write | ||||
| Parameter Set 1 Value 11 (S111) | Read and write | ||||
| Parameter Set 1 Value 12 (S112) | Read and write | ||||
| Parameter Set 1 Value 13 (S113) | Read and write | ||||
| Parameter Set 1 Value 14 (S114) | Read and write | ||||
| Parameter Set 1 Value 15 (S115) | Read and write | ||||
| Parameter Set 2 Value 1 (S201) | Read and write | ||||
| Parameter Set 2 Value 2 (S202) | Read and write | ||||
| Parameter Set 2 Value 3 (S203) | Read and write | ||||
| Parameter Set 2 Value 4 (S204) | Read and write | ||||
| Parameter Set 2 Value 5 (S205) | Read and write | ||||
| Parameter Set 2 Value 6 (S206) | Read and write | ||||
| Parameter Set 2 Value 7 (S207) | Read and write | ||||
| Parameter Set 2 Value 8 (S208) | Read and write | ||||
| Parameter Set 2 Value 9 (S209) | Read and write | ||||
| Parameter Set 2 Value 10 (S210) | Read and write | ||||
| Parameter Set 2 Value 11 (S211) | Read and write | ||||
| Parameter Set 2 Value 12 (S212) | Read and write | ||||
| Parameter Set 2 Value 13 (S213) | Read and write | ||||
| Parameter Set 2 Value 14 (S214) | Read and write | ||||
| Parameter Set 2 Value 15 (S215) | Read and write | ||||
| Parameter Set 3 Value 1 (S301) | Read and write | ||||
| Parameter Set 3 Value 2 (S302) | Read and write | ||||
| Parameter Set 3 Value 3 (S303) | Read and write | ||||
| Parameter Set 3 Value 4 (S304) | Read and write | ||||
| Parameter Set 3 Value 5 (S305) | Read and write | ||||
| Parameter Set 3 Value 6 (S306) | Read and write | ||||
| Parameter Set 3 Value 7 (S307) | Read and write | ||||
| Parameter Set 3 Value 8 (S308) | Read and write | ||||
| Parameter Set 3 Value 9 (S309) | Read and write | ||||
| Parameter Set 3 Value 10 (S310) | Read and write | ||||
| Parameter Set 3 Value 11 (S311) | Read and write | ||||
| Parameter Set 3 Value 12 (S312) | Read and write | ||||
| Parameter Set 3 Value 13 (S313) | Read and write | ||||
| Parameter Set 3 Value 14 (S314) | Read and write | ||||
| Parameter Set 3 Value 15 (S315) | Read and write | ||||
| Cmd Word (CMP9) | Read | ||||
| Cmd Word (CMPA) | Read | ||||
| Cmd Word (CMPB) | Read | ||||
| CMD Command Word (CMPC) | Read | ||||
| CMD Command Word (CMPD) | Read | ||||
| CMD Command Word (CMPE) | Read | ||||
| CMD Command Word (CMPF) | Read | ||||
| Active Channels On Error n-9 (CRP9) | Read | ||||
| Active Channels On Error n-10 (CRPA) | Read | ||||
| Active Channels On Error n-11 (CRPB) | Read | ||||
| Active Channels On Error n-12 (CRPC) | Read | ||||
| Active Channels On Error n-13 (CRPD) | Read | ||||
| Active Channels On Error n-14 (CRPE) | Read | ||||
| Active Channels On Error n-15 (CRPF) | Read | ||||
| Hour And Minute Of Actual Fault (DM0) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM1) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM2) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM3) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM4) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM5) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM6) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM7) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM8) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DM9) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DMA) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DMB) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DMC) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DMD) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DME) | Read | ||||
| Hour And Minute Of Fault Record X (1 Is Last) (DMF) | Read | ||||
| Last Error 9 (DP9) | Read | ||||
| Last Error 10 (DPA) | Read | ||||
| Last Error 11 (DPB) | Read | ||||
| Last Error 12 (DPC) | Read | ||||
| Last Error 13 (DPD) | Read | ||||
| Last Error 14 (DPE) | Read | ||||
| Last Error 15 (DPF) | Read | ||||
| State Word (EP9) | Read | ||||
| State Word (EPA) | Read | ||||
| State Word (EPB) | Read | ||||
| State Word (EPC) | Read | ||||
| State Word (EPD) | Read | ||||
| State Word (EPE) | Read | ||||
| State Word (EPF) | Read | ||||
| Device State (HS9) | Read | ||||
| Device State (HSA) | Read | ||||
| Device State (HSB) | Read | ||||
| Device State (HSC) | Read | ||||
| Device State (HSD) | Read | ||||
| Device State (HSE) | Read | ||||
| Device State (HSF) | Read | ||||
| ETI State Word (IP9) | Read | ||||
| ETI State Word (IPA) | Read | ||||
| ETI State Word (IPB) | Read | ||||
| ETI State Word (IPC) | Read | ||||
| ETI State Word (IPD) | Read | ||||
| ETI State Word (IPE) | Read | ||||
| ETI State Word (IPF) | Read | ||||
| Motor Current (LCP9) | Read | ||||
| Motor Current (LCPA) | Read | ||||
| Motor Current (LCPB) | Read | ||||
| Motor Current (LCPC) | Read | ||||
| Motor Current (LCPD) | Read | ||||
| Motor Current (LCPE) | Read | ||||
| Motor Current (LCPF) | Read | ||||
| Year, Month And Day Of Actual Fault (MD0) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD1) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD2) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD3) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD4) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD5) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD6) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD7) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD8) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MD9) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MDA) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MDB) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MDC) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MDD) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MDE) | Read | ||||
| Year, Month And Day Of Fault Record X (1 Is Last) (MDF) | Read | ||||
| Motor Torque (OTP9) | % | Read | |||
| Motor Torque (OTPA) | % | Read | |||
| Motor Torque (OTPB) | % | Read | |||
| Motor Torque (OTPC) | % | Read | |||
| Motor Torque (OTPD) | % | Read | |||
| Motor Torque (OTPE) | % | Read | |||
| Motor Torque (OTPF) | % | Read | |||
| Motor Frequency (RFP9) | Hz | Read | |||
| Motor Frequency (RFPA) | Hz | Read | |||
| Motor Frequency (RFPB) | Hz | Read | |||
| Motor Frequency (RFPC) | Hz | Read | |||
| Motor Frequency (RFPD) | Hz | Read | |||
| Motor Frequency (RFPE) | Hz | Read | |||
| Motor Frequency (RFPF) | Hz | Read | |||
| Run Elapsed Time (RTP9) | h | Read | |||
| Run Elapsed Time (RTPA) | h | Read | |||
| Run Elapsed Time (RTPB) | h | Read | |||
| Run Elapsed Time (RTPC) | h | Read | |||
| Run Elapsed Time (RTPD) | h | Read | |||
| Run Elapsed Time (RTPE) | h | Read | |||
| Run Elapsed Time (RTPF) | h | Read | |||
| Switching Frequency (SFP9) | Hz | Read | |||
| Switching Frequency (SFPA) | Hz | Read | |||
| Switching Frequency (SFPB) | Hz | Read | |||
| Switching Frequency (SFPC) | Hz | Read | |||
| Switching Frequency (SFPD) | Hz | Read | |||
| Switching Frequency (SFPE) | Hz | Read | |||
| Switching Frequency (SFPF) | Hz | Read | |||
| Drive Thermal State (TDP9) | % | Read | |||
| Drive Thermal State (TDPA) | % | Read | |||
| Drive Thermal State (TDPB) | % | Read | |||
| Drive Thermal State (TDPC) | % | Read | |||
| Drive Thermal State (TDPD) | % | Read | |||
| Drive Thermal State (TDPE) | % | Read | |||
| Drive Thermal State (TDPF) | % | Read | |||
| Motor Thermal State (THP9) | % | Read | |||
| Motor Thermal State (THPA) | % | Read | |||
| Motor Thermal State (THPB) | % | Read | |||
| Motor Thermal State (THPC) | % | Read | |||
| Motor Thermal State (THPD) | % | Read | |||
| Motor Thermal State (THPE) | % | Read | |||
| Motor Thermal State (THPF) | % | Read | |||
| IGBT Junction Temp (TJP9) | °C | Read | |||
| IGBT Junction Temp (TJPA) | °C | Read | |||
| IGBT Junction Temp (TJPB) | °C | Read | |||
| IGBT Junction Temp (TJPC) | °C | Read | |||
| IGBT Junction Temp (TJPD) | °C | Read | |||
| IGBT Junction Temp (TJPE) | °C | Read | |||
| IGBT Junction Temp (TJPF) | °C | Read | |||
| DC Bus Voltage (ULP9) | V | Read | |||
| DC Bus Voltage (ULPA) | V | Read | |||
| DC Bus Voltage (ULPB) | V | Read | |||
| DC Bus Voltage (ULPC) | V | Read | |||
| DC Bus Voltage (ULPD) | V | Read | |||
| DC Bus Voltage (ULPE) | V | Read | |||
| DC Bus Voltage (ULPF) | V | Read | |||
| Channel For Reference Frequency (DRC9) | Read | ||||
| Channel For Reference Frequency (DRCA) | Read | ||||
| Channel For Reference Frequency (DRCB) | Read | ||||
| Channel For Reference Frequency (DRCC) | Read | ||||
| Channel For Reference Frequency (DRCD) | Read | ||||
| Channel For Reference Frequency (DRCE) | Read | ||||
| Channel For Reference Frequency (DRCF) | Read | ||||
| Command Channel (DCC9) | Read | ||||
| Command Channel (DCCA) | Read | ||||
| Command Channel (DCCB) | Read | ||||
| Command Channel (DCCZ) | Read | ||||
| Command Channel (DCCD) | Read | ||||
| Command Channel (DCCE) | Read | ||||
| Command Channel (DCCF) | Read | ||||
| Internal Error 6 (Module Identification Error) Informati (INF6) | Read | ||||
| Internal Error 19 (Encoder) (INFJ) | Read | ||||
| Encoder Feedback Error Number (ENCE) | Read | ||||
| HMI Status (HS1) | Read | ||||
| HMI Status (HS2) | Read | ||||
| HMI Status (HS3) | Read | ||||
| HMI Status (HS4) | Read | ||||
| HMI Status (HS5) | Read | ||||
| HMI Status (HS6) | Read | ||||
| HMI Status (HS7) | Read | ||||
| HMI Status (HS8) | Read | ||||
| Safety Module Status (SSTA) | Read | ||||
| Safety Configuration Status (SCNA) | Read | ||||
| Active Safety Function (SFCA) | Read | ||||
| Safety Input Word A (SIWA) | Read | ||||
| Safety Output Word A (SQWA) | Read | ||||
| Test Command Activation (FSCA) | Read and write | ||||
| Test Ramp Command (FSRC) | Read and write | ||||
| Safety Input Word B (SIWB) | Read | ||||
| Safety Output Word B (SQWB) | Read | ||||
| Safety Module Error (SMLE) | Read | ||||
| Safety Module Error 0 (SME0) | Read | ||||
| Safety Module Error 1 (SME1) | Read | ||||
| Safety Module Error 2 (SME2) | Read | ||||
| Safety Module Error 3 (SME3) | Read | ||||
| Safety Module Error 4 (SME4) | Read | ||||
| Safety Module Error 5 (SME5) | Read | ||||
| Safety Module Error 6 (SME6) | Read | ||||
| Safety Module Error 7 (SME7) | Read | ||||
| Safety Module Error 8 (SME8) | Read | ||||
| Safety Module Error 9 (SME9) | Read | ||||
| Safety Fast Monitoring Parameter 0 (SFM0) | Read | ||||
| Safety Fast Monitoring Parameter 1 (SFM1) | Read | ||||
| Safety Fast Monitoring Parameter 2 (SFM2) | Read | ||||
| Safety Fast Monitoring Parameter 3 (SFM3) | Read | ||||
| Safety Fast Monitoring Parameter 4 (SFM4) | Read | ||||
| Safety Fast Monitoring Parameter 5 (SFM5) | Read | ||||
| Safety Fast Monitoring Parameter 6 (SFM6) | Read | ||||
| Safety Fast Monitoring Parameter 7 (SFM7) | Read | ||||
| Safety Fast Monitoring Parameter 8 (SFM8) | Read | ||||
| Safety Supervisor Object Status (SSM0) | Read | ||||
| PROFIsafe Communication State (SSM1) | Read | ||||
| Safety Slow Monitoring Parameter 2 (SSM2) | Read | ||||
| Safety Slow Monitoring Parameter 3 (SSM3) | Read | ||||
| Safety Slow Monitoring Parameter 4 (SSM4) | Read | ||||
| Safety Slow Monitoring Parameter 5 (SSM5) | Read | ||||
| Safety Slow Monitoring Parameter 6 (SSM6) | Read | ||||
| Safety Slow Monitoring Parameter 7 (SSM7) | Read | ||||
| Safety Status Word Bytes 1-0 (SSW0) | Read | ||||
| Safety Status Word Bytes 3-2 (SSW1) | Read | ||||
| Safety Status Word Bytes 5-4 (SSW2) | Read | ||||
| Safety Status Word Bytes 7-6 (SSW3) | Read | ||||
| Safety Status Word Bytes 9-8 (SSW4) | Read | ||||
| Safety Status Word Bytes 11-10 (SSW5) | Read | ||||
| Safety Status Word Bytes 13-12 (SSW6) | Read | ||||
| Safety Command Word Bytes 1-0 (SCW0) | Read | ||||
| Safety Command Word Bytes 3-2 (SCW1) | Read | ||||
| Safety Command Word Bytes 5-4 (SCW2) | Read | ||||
| Safety Command Word Bytes 7-6 (SCW3) | Read | ||||
| Safety Command Word Bytes 9-8 (SCW4) | Read | ||||
| Safety Command Word Bytes 11-10 (SCW5) | Read | ||||
| Safety Command Word Bytes 13-12 (SCW6) | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Read the fault code and motor conditions of the last trips to find out why a drive stopped.
- Keep a 365-day history of fault records to spot drives that trip on overcurrent or overheating more often.
- Set an alert when the fault code on last fault changes, so you hear by email about a new trip.
- Check which parameter set is active on a machine that switches between products or modes.
- Watch safety module errors and the active safety function on a dashboard for each drive.
Installation
Connect the RJ45 Modbus port of the ATV340 to RS485 A and B of the ModbusCloud Gateway and terminate the bus at both ends.
On the drive, set Modbus Address (1 to 247), baud rate and format; the factory setting is 19200 baud, 8E1, address OFF.
In ModbusCloud, add a Modbus device with the same settings, or use the device of the core ATV340 template, and import this template.
Check that Fault Code On Last Fault (DP0) and the fault date match the fault history on the drive display.
Things to watch for
How do I read the fault code as text?
The fault code is a number from the ATV340 fault list, the same list the drive display uses for its fault history. Look it up in the programming manual or the communication parameter list of the drive. A value of 0 means no fault stored in that record.
Why does motor current show an odd value?
Motor current and a few power values have a scale that depends on the drive rating, so the template reads them raw. Compare one value with the drive display once and apply the factor you find in the programming manual for your rating.
The drive does not answer at all. What should I check?
The Modbus address is OFF from the factory, so the drive stays silent until you set it. Then check baud rate and format (default 19200, 8E1), swap A and B if needed and terminate the bus at both ends.
Can I change parameter sets from ModbusCloud?
Yes, the parameter set addresses and values are writable, and the selection inputs too, but those only accept a new value with the motor stopped. A wrong parameter address changes the wrong setting, so write one value at a time, check it on the drive and agree changes with whoever runs the machine.