Siemens Siemens Sentron PAC 2200 Modbus TCP template

Siemens Sentron PAC 2200

Monitors three-phase energy metering via Modbus TCP on Siemens Sentron PAC 2200.

Template for the Siemens Sentron PAC 2200 three-phase energy meter over Modbus TCP. It reads per-phase voltage, current, apparent power, active power, and reactive power, as well as total power values. No control functions are included.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
18, read only
Brand
Siemens
Key readings
Voltage L1-N, L2-N, L3-N · Voltage L1-L2, L2-L3, L3-L1 · Current L1 to L3 · Apparent Power L1 to L3 · Active Power L1 to L3 · Total Active, Apparent, Reactive Power
Compatible models
Sentron PAC 2200
Last updated

Registers (18)

18 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Voltage L1-NVRead
Voltage L2-NVRead
Voltage L3-NVRead
Voltage L1-L2VRead
Voltage L2-L3VRead
Voltage L3-L1VRead
Current L1ARead
Current L2ARead
Current L3ARead
Apparent Power L1VARead
Apparent Power L2VARead
Apparent Power L3VARead
Active Power L1WRead
Active Power L2WRead
Active Power L3WRead
Total Apparent PowerVARead
Total Active PowerWRead
Total Reactive PowervarRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor per-phase voltage, current, and power readings on a live cloud dashboard for remote energy oversight.
  • Create alerts when total active power exceeds a contractual demand limit to avoid penalty charges.
  • Track energy consumption trends per building section or tenant using historical data exports.
  • Compare line-to-line voltages across phases to detect voltage imbalance issues early.
  • Generate periodic energy reports for facility managers without requiring on-site meter readings.
  • Verify power factor by reviewing active and reactive power values on the dashboard.

Installation

  1. Connect the Siemens Sentron PAC 2200 to the local Ethernet network and verify it has a valid IP address.

  2. Configure the Modbus TCP port (default 502) and unit ID on the PAC 2200 using the front-panel menu or Siemens software.

  3. Connect the ModbusCloud Gateway to the same local network as the PAC 2200.

  4. In the ModbusCloud platform, add a new device and select the Siemens Sentron PAC 2200 template from the library.

  5. Enter the IP address and Modbus unit ID of the PAC 2200 in the device configuration screen.

  6. Confirm that live readings appear on the dashboard, then configure any desired alerts or data logging intervals.

Things to watch for

I see zero or incorrect values for all registers. What should I check?

Verify the IP address and Modbus unit ID match the settings on the PAC 2200. Also confirm that Modbus TCP is enabled on the meter and that no firewall is blocking port 502.

Do I need to configure float32 byte order manually?

No. The template is preconfigured with the correct float32 register mapping for the PAC 2200. Each value spans two consecutive registers, and the template handles the byte order automatically.

The template does not include all PAC 2200 registers. Can I add more?

Yes. You can extend the template by adding custom registers using the PAC 2200 Modbus register documentation from Siemens. Use float32 as the data type for additional registers.

Can I connect multiple PAC 2200 meters to one ModbusCloud gateway?

Yes. Assign each PAC 2200 a unique IP address or unique Modbus unit ID, then add each meter as a separate device in the ModbusCloud platform using the same template.

Want to see how it works?

Electrician working in an open distribution board