Siemens SENTRON PAC3220

Power monitor for distribution boards: voltage, current, power, energy per tariff and power quality.

The Siemens SENTRON PAC3220 is a power monitoring device that measures voltage, current, power, energy and power quality in low-voltage distribution boards. This Modbus TCP template reads all live values, demand values and energy counters, and lets you set transformer ratios, limits and outputs from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
918, read and write
Brand
Siemens
Key readings
Voltage L-N and L-L · Current per phase and neutral · Active power · Reactive and apparent power · Power factor · Frequency · Active energy import and export · THD voltage and current
Available commands
Current transformer ratio · Voltage transformer ratio · Limit values · Digital output functions · Energy counter reset · Tariff switchover
Compatible models
SENTRON PAC3220 · SENTRON PAC3120 · 7KM3220-0BA01-1DA0 · 7KM3220-1BA01-1EA0 · 7KM3120-0BA01-1DA0 · 7KM3120-1BA01-1EA0
Last updated

Registers (918)

908 read, 236 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Voltage L1-NVRead
Voltage L2-NVRead
Voltage L3-NVRead
Voltage L1-L2VRead
Voltage L2-L3VRead
Voltage L3-L1VRead
Current L1ARead
Current L2ARead
Current L3ARead
Current NARead
Active Power L1WRead
Active Power L2WRead
Active Power L3WRead
Total Active PowerWRead
Total Apparent PowerVARead
Total Reactive PowervarRead
Apparent Power L1VARead
Apparent Power L2VARead
Apparent Power L3VARead
Reactive Power L1varRead
Reactive Power L2varRead
Reactive Power L3varRead
Power Factor L1Read
Power Factor L2Read
Power Factor L3Read
Total Power FactorRead
FrequencyHzRead
Average Voltage UL-NVRead
Average Voltage UL-LVRead
Average CurrentARead
THD-R Voltage L1%Read
THD-R Voltage L2%Read
THD-R Voltage L3%Read
THD-R Current L1%Read
THD-R Current L2%Read
THD-R Current L3%Read
Amplitude Unbalance Voltage%Read
Amplitude Unbalance Current%Read
Total Active Energy Import Tariff 1WhRead and write
Total Active Energy Import Tariff 2WhRead and write
Total Active Energy Export Tariff 1Read and write
Total Active Energy Export Tariff 2Read and write
Total Reactive Energy Import Tariff 1Read and write
Total Reactive Energy Import Tariff 2Read and write
Total Reactive Energy Export Tariff 1varhRead and write
Total Reactive Energy Export Tariff 2varhRead and write
Total Apparent Energy Tariff 1VAhRead and write
Total Apparent Energy Tariff 2VAhRead and write
Maximum Voltage L1-NVRead
Maximum Voltage L2-NVRead
Maximum Voltage L3-NVRead
Maximum Voltage L1-L2VRead
Maximum Voltage L2-L1VRead
Maximum Voltage L3-L1VRead
Maximum Current L1ARead
Maximum Current L2ARead
Maximum Current L3ARead
Maximum Apparent Power L1VARead
Maximum Apparent Power L2VARead
Maximum Apparent Power L3VARead
Maximum Active Power L1WRead
Maximum Active Power L2WRead
Maximum Active Power L3WRead
Maximum Reactive Power L1varRead
Maximum Reactive Power L2varRead
Maximum Reactive Power L3varRead
Maximum Power Factor L1Read
Maximum Power Factor L2Read
Maximum Power Factor L3Read
Maximum THD-R Voltage L1-L2%Read
Maximum THD-R Voltage L2-L3%Read
Maximum THD-R Voltage L3-L1%Read
Maximum THD-R Current L1%Read
Maximum THD-R Current L2%Read
Maximum THD-R Current L3%Read
Maximum FrequencyRead
Maximum Average Voltage UL-NVRead
Maximum Average Voltage UL-LVRead
Maximum Average CurrentARead
Maximum Total Apparent PowerVARead
Maximum Total Active PowerWRead
Maximum Total Reactive PowervarRead
Maximum Total Power FactorRead
Minimum Voltage L1-NVRead
Minimum Voltage L2-NVRead
Minimum Voltage L3-NVRead
Minimum Voltage L1-L2VRead
Minimum Voltage L2-L1VRead
Minimum Voltage L3-L1VRead
Minimum Current L1ARead
Minimum Current L2ARead
Minimum Current L3ARead
Minimum Apparent Power L1VARead
Minimum Apparent Power L2VARead
Minimum Apparent Power L3VARead
Minimum Active Power L1WRead
Minimum Active Power L2WRead
Minimum Active Power L3WRead
Minimum Reactive Power L1varRead
Minimum Reactive Power L2varRead
Minimum Reactive Power L3varRead
Minimum Power Factor L1Read
Minimum Power Factor L2Read
Minimum Power Factor L3Read
Minimum FrequencyHzRead
Minimum Average Voltage UL-NVRead
Minimum Average Voltage UL-LVRead
Minimum Average CurrentARead
Minimum Total Apparent PowerVARead
Minimum Total Active PowerWRead
Minimum Total Reactive PowervarRead
Minimum Total Power FactorRead
Limit ViolationsRead
PMD Diagnostics and StatusRead
Digital Outputs StatusRead
Digital Inputs StatusRead
Active TariffRead
Operating Hours CountersRead and write
Counter (configurable)Read and write
Counter Basic Parameter ChangesRead
Counter All Parameter ChangesRead
Counter Limit Value ChangesRead
Maximum Current NARead
Minimum Current NARead
Configurable Energy CounterRead
Status Digital Outputs Module 1Read
Status Digital Inputs Module 1Read
Status Digital Outputs Module 2Read
Status Digital Inputs Module 2Read
Limit 0Read
Limit 1Read
Limit 2Read
Limit 3Read
Limit 4Read
Limit 5Read
Limit LogicRead
Stored Relevant Parameter ChangesRead
Stored Upper or Lower Limit ViolationRead
Stored Maximum Pulse Rate ExceededRead
Stored Restart of the DeviceRead
Stored Resetting of Energy Counters by UserRead
Module Slot 1 StatusRead
Module Maximum Pulse Rate ExceededRead
Module Slot 2 StatusRead
Waiting for User InputRead
Status No Synchronization PulseRead
Status Device Configuration Menu Is ActiveRead
Status Voltage OverloadRead
Status Current OverloadRead
Status Date/time of Device Not SecureRead
Status Device Update in ProgressRead
Status Hardware Write Protection Is ActiveRead
Status Modbus Communication Password ProtectedRead
Digital Input 0.0Read
Digital Input 0.1Read
Digital Input 4.0Read
Digital Input 4.1Read
Digital Input 4.2Read
Digital Input 4.3Read
Digital Input 8.0Read
Digital Input 8.1Read
Digital Input 8.2Read
Digital Input 8.3Read
Digital Output 0.0Read
Digital Output 0.1Read
Digital Output 4.0Read
Digital Output 4.1Read
Digital Output 8.0Read
Digital Output 8.1Read
Cumulated Average Active Power ImportWRead
Cumulated Average Reactive Power ImportvarRead
Cumulated Average Active Power ExportWRead
Cumulated Average Reactive Power ExportvarRead
Maximum Active Power in Demand PeriodWRead
Minimum Active Power in Demand PeriodWRead
Maximum Reactive Power in Demand PeriodvarRead
Minimum Reactive Power in Demand PeriodvarRead
Demand Period LengthsRead
Time Since Start of Demand PeriodsRead
Date/timeRead and write
L1 Active Energy Import Tariff 1WhRead and write
L1 Active Energy Import Tariff 2WhRead and write
L1 Active Energy Export Tariff 1Read and write
L1 Active Energy Export Tariff 2Read and write
L1 Reactive Energy Import Tariff 1Read and write
L1 Reactive Energy Import Tariff 2Read and write
L1 Reactive Energy Export Tariff 1varhRead and write
L1 Reactive Energy Export Tariff 2varhRead and write
L1 Apparent Energy Tariff 1VAhRead and write
L1 Apparent Energy Tariff 2VAhRead and write
L2 Active Energy Import Tariff 1WhRead and write
L2 Active Energy Import Tariff 2WhRead and write
L2 Active Energy Export Tariff 1Read and write
L2 Active Energy Export Tariff 2Read and write
L2 Reactive Energy Import Tariff 1Read and write
L2 Reactive Energy Import Tariff 2Read and write
L2 Reactive Energy Export Tariff 1varhRead and write
L2 Reactive Energy Export Tariff 2varhRead and write
L2 Apparent Energy Tariff 1VAhRead and write
L2 Apparent Energy Tariff 2VAhRead and write
L3 Active Energy Import Tariff 1WhRead and write
L3 Active Energy Import Tariff 2WhRead and write
L3 Active Energy Export Tariff 1Read and write
L3 Active Energy Export Tariff 2Read and write
L3 Reactive Energy Import Tariff 1Read and write
L3 Reactive Energy Import Tariff 2Read and write
L3 Reactive Energy Export Tariff 1varhRead and write
L3 Reactive Energy Export Tariff 2varhRead and write
L3 Apparent Energy Tariff 1VAhRead and write
L3 Apparent Energy Tariff 2VAhRead and write
Reset to Factory SettingsWrite
Device ResetWrite
Reset Maximum ValuesWrite
Reset Minimum ValuesWrite
Reset Energy CountersWrite
Synchronize Demand PeriodminWrite
Tariff SwitchoverWrite
Acknowledge Diagnostics BitsWrite
Switch OutputsWrite
Switch Vector GroupWrite
Connection TypeRead and write
Voltage Transformer UsedRead and write
Primary VoltageVRead and write
Secondary VoltageVRead and write
Primary CurrentARead and write
Secondary CurrentARead and write
Zero Point Suppression Level%Read and write
Demand PeriodminRead and write
SynchronizationRead and write
DI 0.0 Type of Use (32-bit)Read and write
DI 0.0 Index (32-bit)Read and write
DI 0.0 Pulses per Unit (32-bit)Read and write
DO 0.0 Vector Group Assignment (32-bit)Read and write
DO 0.0 Type of Use (32-bit)Read and write
DO 0.0 Limit Value (32-bit)Read and write
DO 0.0 Index (32-bit)Read and write
DO 0.0 Pulses per kWh/kvarh (32-bit)Read and write
DO 0.0 Pulse Length (32-bit)Read and write
Dialog LanguageRead and write
Phase Labels EU/USRead and write
Configurable Counter SourceRead and write
Display Refresh CycleRead and write
Display ContrastRead and write
Display Backlight LevelRead and write
Display Backlight DimmedRead and write
Display Time Until DimmedminRead and write
Limit 0 On/OffRead and write
Limit 0 Hysteresis%Read and write
Limit 0 DelaysRead and write
Limit 0 Index LogicRead and write
Limit 0 Data List IndexRead and write
Limit 0 SourceRead and write
Limit 0 Comparison TypeRead and write
Limit 1 On/OffRead and write
Limit 1 Hysteresis%Read and write
Limit 1 DelaysRead and write
Limit 1 Index LogicRead and write
Limit 1 Data List IndexRead and write
Limit 1 SourceRead and write
Limit 1 Comparison TypeRead and write
Limit 2 On/OffRead and write
Limit 2 Hysteresis%Read and write
Limit 2 DelaysRead and write
Limit 2 Index LogicRead and write
Limit 2 Data List IndexRead and write
Limit 2 SourceRead and write
Limit 2 Comparison TypeRead and write
Limit 3 On/OffRead and write
Limit 3 Hysteresis%Read and write
Limit 3 DelaysRead and write
Limit 3 Index LogicRead and write
Limit 3 Data List IndexRead and write
Limit 3 SourceRead and write
Limit 3 Comparison TypeRead and write
Limit 4 On/OffRead and write
Limit 4 Hysteresis%Read and write
Limit 4 DelaysRead and write
Limit 4 Index LogicRead and write
Limit 4 Data List IndexRead and write
Limit 4 SourceRead and write
Limit 4 Comparison TypeRead and write
Limit 5 On/OffRead and write
Limit 5 Hysteresis%Read and write
Limit 5 DelaysRead and write
Limit 5 Index LogicRead and write
Limit 5 Data List IndexRead and write
Limit 5 SourceRead and write
Limit 5 Comparison TypeRead and write
DO 0.0 Timeout (32-bit)sRead and write
Default Menu No.Read and write
Timeout Return to Default MenusRead and write
Date FormatRead and write
Daylight SavingRead and write
Time ZoneminRead and write
DO 0.0 Pulse Divider (32-bit)Read and write
DI 0.0 Pulse Divider (32-bit)Read and write
Current Direction L1 Yes/NoRead and write
Current Direction L2 Yes/NoRead and write
Current Direction L3 Yes/NoRead and write
DI 0.0 Type of UseRead and write
DI 0.0 IndexRead and write
DI 0.0 Pulses per kWh/kvarhRead and write
DI 0.0 Pulse DividerRead and write
DI 0.1 Type of UseRead and write
DI 0.1 IndexRead and write
DI 0.1 Pulses per kWh/kvarhRead and write
DI 0.1 Pulse DividerRead and write
DI 4.0 Type of UseRead and write
DI 4.0 IndexRead and write
DI 4.0 Pulses per kWh/kvarhRead and write
DI 4.0 Pulse DividerRead and write
DI 4.1 Type of UseRead and write
DI 4.1 IndexRead and write
DI 4.1 Pulses per kWh/kvarhRead and write
DI 4.1 Pulse DividerRead and write
DI 4.2 Type of UseRead and write
DI 4.2 IndexRead and write
DI 4.2 Pulses per kWh/kvarhRead and write
DI 4.2 Pulse DividerRead and write
DI 4.3 Type of UseRead and write
DI 4.3 IndexRead and write
DI 4.3 Pulses per kWh/kvarhRead and write
DI 4.3 Pulse DividerRead and write
DI 8.0 Type of UseRead and write
DI 8.0 IndexRead and write
DI 8.0 Pulses per kWh/kvarhRead and write
DI 8.0 Pulse DividerRead and write
DI 8.1 Type of UseRead and write
DI 8.1 IndexRead and write
DI 8.1 Pulses per kWh/kvarhRead and write
DI 8.1 Pulse DividerRead and write
DI 8.2 Type of UseRead and write
DI 8.2 IndexRead and write
DI 8.2 Pulses per kWh/kvarhRead and write
DI 8.2 Pulse DividerRead and write
DI 8.3 Type of UseRead and write
DI 8.3 IndexRead and write
DI 8.3 Pulses per kWh/kvarhRead and write
DI 8.3 Pulse DividerRead and write
DO 0.0 Group AssignmentRead and write
DO 0.0 Type of UseRead and write
DO 0.0 Limit Value IndexRead and write
DO 0.0 IndexRead and write
DO 0.0 Pulses per kWh/kvarhRead and write
DO 0.0 Pulse LengthRead and write
DO 0.0 TimeoutsRead and write
DO 0.0 Pulse DividerRead and write
DO 0.1 Group AssignmentRead and write
DO 0.1 Type of UseRead and write
DO 0.1 Limit Value IndexRead and write
DO 0.1 IndexRead and write
DO 0.1 Pulses per kWh/kvarhRead and write
DO 0.1 Pulse LengthRead and write
DO 0.1 TimeoutsRead and write
DO 0.1 Pulse DividerRead and write
DO 4.0 Group AssignmentRead and write
DO 4.0 Type of UseRead and write
DO 4.0 Limit Value IndexRead and write
DO 4.0 IndexRead and write
DO 4.0 Pulses per kWh/kvarhRead and write
DO 4.0 Pulse LengthRead and write
DO 4.0 TimeoutsRead and write
DO 4.0 Pulse DividerRead and write
DO 4.1 Group AssignmentRead and write
DO 4.1 Type of UseRead and write
DO 4.1 Limit Value IndexRead and write
DO 4.1 IndexRead and write
DO 4.1 Pulses per kWh/kvarhRead and write
DO 4.1 Pulse LengthRead and write
DO 4.1 TimeoutsRead and write
DO 4.1 Pulse DividerRead and write
DO 8.0 Group AssignmentRead and write
DO 8.0 Type of UseRead and write
DO 8.0 Limit Value IndexRead and write
DO 8.0 IndexRead and write
DO 8.0 Pulses per kWh/kvarhRead and write
DO 8.0 Pulse LengthRead and write
DO 8.0 TimeoutsRead and write
DO 8.0 Pulse DividerRead and write
DO 8.1 Group AssignmentRead and write
DO 8.1 Type of UseRead and write
DO 8.1 Limit Value IndexRead and write
DO 8.1 IndexRead and write
DO 8.1 Pulses per kWh/kvarhRead and write
DO 8.1 Pulse LengthRead and write
DO 8.1 TimeoutsRead and write
DO 8.1 Pulse DividerRead and write
Aggregation File 1 Period LengthRead and write
Aggregation File 1 MethodRead and write
Aggregation File 2 Period LengthRead and write
Aggregation File 2 MethodRead and write
DHCPRead and write
SNTP Server IP AddressRead and write
SNTP ModeRead and write
Modbus TCP PortRead and write
IP AddressRead and write
Subnet MaskRead and write
Default GatewayRead and write
RS485 Module Modbus AddressRead and write
RS485 Module Baud RateRead and write
RS485 Module Data FormatRead and write
RS485 Module Response TimeRead and write
Stage 1 Mean Block TimestampsRead
Stage 1 Mean Block FlagsRead
Stage 1 Voltage L1-NVRead
Stage 1 Voltage L2-NVRead
Stage 1 Voltage L3-NVRead
Stage 1 Voltage L1-L2VRead
Stage 1 Voltage L2-L3VRead
Stage 1 Voltage L3-L1VRead
Stage 1 Current L1ARead
Stage 1 Current L2ARead
Stage 1 Current L3ARead
Stage 1 Apparent Power L1VARead
Stage 1 Apparent Power L2VARead
Stage 1 Apparent Power L3VARead
Stage 1 Active Power L1WRead
Stage 1 Active Power L2WRead
Stage 1 Active Power L3WRead
Stage 1 Reactive Power Q1 L1varRead
Stage 1 Reactive Power Q1 L2varRead
Stage 1 Reactive Power Q1 L3varRead
Stage 1 Power Factor L1Read
Stage 1 Power Factor L2Read
Stage 1 Power Factor L3Read
Stage 1 THD-R Voltage L1%Read
Stage 1 THD-R Voltage L2%Read
Stage 1 THD-R Voltage L3%Read
Stage 1 THD-R Current L1%Read
Stage 1 THD-R Current L2%Read
Stage 1 THD-R Current L3%Read
Stage 1 FrequencyHzRead
Stage 1 Average Voltage L-NVRead
Stage 1 Average Voltage L-LVRead
Stage 1 Average CurrentARead
Stage 1 Total Apparent PowerVARead
Stage 1 Total Active PowerWRead
Stage 1 Total Reactive Power Q1varRead
Stage 1 Total Power FactorRead
Stage 1 Voltage Unbalance%Read
Stage 1 Current Unbalance%Read
Stage 1 Neutral CurrentARead
Stage 1 Max Block TimestampsRead
Stage 1 Max Block FlagsRead
Stage 1 Max Voltage L1-NVRead
Stage 1 Max Voltage L2-NVRead
Stage 1 Max Voltage L3-NVRead
Stage 1 Max Voltage L1-L2VRead
Stage 1 Max Voltage L2-L3VRead
Stage 1 Max Voltage L3-L1VRead
Stage 1 Max Current L1ARead
Stage 1 Max Current L2ARead
Stage 1 Max Current L3ARead
Stage 1 Max Apparent Power L1VARead
Stage 1 Max Apparent Power L2VARead
Stage 1 Max Apparent Power L3VARead
Stage 1 Max Active Power L1WRead
Stage 1 Max Active Power L2WRead
Stage 1 Max Active Power L3WRead
Stage 1 Max Reactive Power Q1 L1varRead
Stage 1 Max Reactive Power Q1 L2varRead
Stage 1 Max Reactive Power Q1 L3varRead
Stage 1 Max Power Factor L1Read
Stage 1 Max Power Factor L2Read
Stage 1 Max Power Factor L3Read
Stage 1 Max THD-R Voltage L1%Read
Stage 1 Max THD-R Voltage L2%Read
Stage 1 Max THD-R Voltage L3%Read
Stage 1 Max THD-R Current L1%Read
Stage 1 Max THD-R Current L2%Read
Stage 1 Max THD-R Current L3%Read
Stage 1 Max FrequencyHzRead
Stage 1 Max Average Voltage L-NVRead
Stage 1 Max Average Voltage L-LVRead
Stage 1 Max Average CurrentARead
Stage 1 Max Total Apparent PowerVARead
Stage 1 Max Total Active PowerWRead
Stage 1 Max Total Reactive Power Q1varRead
Stage 1 Max Total Power FactorRead
Stage 1 Max Voltage Unbalance%Read
Stage 1 Max Current Unbalance%Read
Stage 1 Max Neutral CurrentARead
Stage 1 Min Block TimestampsRead
Stage 1 Min Block FlagsRead
Stage 1 Min Voltage L1-NVRead
Stage 1 Min Voltage L2-NVRead
Stage 1 Min Voltage L3-NVRead
Stage 1 Min Voltage L1-L2VRead
Stage 1 Min Voltage L2-L3VRead
Stage 1 Min Voltage L3-L1VRead
Stage 1 Min Current L1ARead
Stage 1 Min Current L2ARead
Stage 1 Min Current L3ARead
Stage 1 Min Apparent Power L1VARead
Stage 1 Min Apparent Power L2VARead
Stage 1 Min Apparent Power L3VARead
Stage 1 Min Active Power L1WRead
Stage 1 Min Active Power L2WRead
Stage 1 Min Active Power L3WRead
Stage 1 Min Reactive Power Q1 L1varRead
Stage 1 Min Reactive Power Q1 L2varRead
Stage 1 Min Reactive Power Q1 L3varRead
Stage 1 Min Power Factor L1Read
Stage 1 Min Power Factor L2Read
Stage 1 Min Power Factor L3Read
Stage 1 Min THD-R Voltage L1%Read
Stage 1 Min THD-R Voltage L2%Read
Stage 1 Min THD-R Voltage L3%Read
Stage 1 Min THD-R Current L1%Read
Stage 1 Min THD-R Current L2%Read
Stage 1 Min THD-R Current L3%Read
Stage 1 Min FrequencyHzRead
Stage 1 Min Average Voltage L-NVRead
Stage 1 Min Average Voltage L-LVRead
Stage 1 Min Average CurrentARead
Stage 1 Min Total Apparent PowerVARead
Stage 1 Min Total Active PowerWRead
Stage 1 Min Total Reactive Power Q1varRead
Stage 1 Min Total Power FactorRead
Stage 1 Min Voltage Unbalance%Read
Stage 1 Min Current Unbalance%Read
Stage 1 Min Neutral CurrentARead
Stage 2 Mean Block TimestampsRead
Stage 2 Mean Block FlagsRead
Stage 2 Voltage L1-NVRead
Stage 2 Voltage L2-NVRead
Stage 2 Voltage L3-NVRead
Stage 2 Voltage L1-L2VRead
Stage 2 Voltage L2-L3VRead
Stage 2 Voltage L3-L1VRead
Stage 2 Current L1ARead
Stage 2 Current L2ARead
Stage 2 Current L3ARead
Stage 2 Apparent Power L1VARead
Stage 2 Apparent Power L2VARead
Stage 2 Apparent Power L3VARead
Stage 2 Active Power L1WRead
Stage 2 Active Power L2WRead
Stage 2 Active Power L3WRead
Stage 2 Reactive Power Q1 L1varRead
Stage 2 Reactive Power Q1 L2varRead
Stage 2 Reactive Power Q1 L3varRead
Stage 2 Power Factor L1Read
Stage 2 Power Factor L2Read
Stage 2 Power Factor L3Read
Stage 2 THD-R Voltage L1%Read
Stage 2 THD-R Voltage L2%Read
Stage 2 THD-R Voltage L3%Read
Stage 2 THD-R Current L1%Read
Stage 2 THD-R Current L2%Read
Stage 2 THD-R Current L3%Read
Stage 2 FrequencyHzRead
Stage 2 Average Voltage L-NVRead
Stage 2 Average Voltage L-LVRead
Stage 2 Average CurrentARead
Stage 2 Total Apparent PowerVARead
Stage 2 Total Active PowerWRead
Stage 2 Total Reactive Power Q1varRead
Stage 2 Total Power FactorRead
Stage 2 Voltage Unbalance%Read
Stage 2 Current Unbalance%Read
Stage 2 Neutral CurrentARead
Stage 2 Max Block TimestampsRead
Stage 2 Max Block FlagsRead
Stage 2 Max Voltage L1-NVRead
Stage 2 Max Voltage L2-NVRead
Stage 2 Max Voltage L3-NVRead
Stage 2 Max Voltage L1-L2VRead
Stage 2 Max Voltage L2-L3VRead
Stage 2 Max Voltage L3-L1VRead
Stage 2 Max Current L1ARead
Stage 2 Max Current L2ARead
Stage 2 Max Current L3ARead
Stage 2 Max Apparent Power L1VARead
Stage 2 Max Apparent Power L2VARead
Stage 2 Max Apparent Power L3VARead
Stage 2 Max Active Power L1WRead
Stage 2 Max Active Power L2WRead
Stage 2 Max Active Power L3WRead
Stage 2 Max Reactive Power Q1 L1varRead
Stage 2 Max Reactive Power Q1 L2varRead
Stage 2 Max Reactive Power Q1 L3varRead
Stage 2 Max Power Factor L1Read
Stage 2 Max Power Factor L2Read
Stage 2 Max Power Factor L3Read
Stage 2 Max THD-R Voltage L1%Read
Stage 2 Max THD-R Voltage L2%Read
Stage 2 Max THD-R Voltage L3%Read
Stage 2 Max THD-R Current L1%Read
Stage 2 Max THD-R Current L2%Read
Stage 2 Max THD-R Current L3%Read
Stage 2 Max FrequencyHzRead
Stage 2 Max Average Voltage L-NVRead
Stage 2 Max Average Voltage L-LVRead
Stage 2 Max Average CurrentARead
Stage 2 Max Total Apparent PowerVARead
Stage 2 Max Total Active PowerWRead
Stage 2 Max Total Reactive Power Q1varRead
Stage 2 Max Total Power FactorRead
Stage 2 Max Voltage Unbalance%Read
Stage 2 Max Current Unbalance%Read
Stage 2 Max Neutral CurrentARead
Stage 2 Min Block TimestampsRead
Stage 2 Min Block FlagsRead
Stage 2 Min Voltage L1-NVRead
Stage 2 Min Voltage L2-NVRead
Stage 2 Min Voltage L3-NVRead
Stage 2 Min Voltage L1-L2VRead
Stage 2 Min Voltage L2-L3VRead
Stage 2 Min Voltage L3-L1VRead
Stage 2 Min Current L1ARead
Stage 2 Min Current L2ARead
Stage 2 Min Current L3ARead
Stage 2 Min Apparent Power L1VARead
Stage 2 Min Apparent Power L2VARead
Stage 2 Min Apparent Power L3VARead
Stage 2 Min Active Power L1WRead
Stage 2 Min Active Power L2WRead
Stage 2 Min Active Power L3WRead
Stage 2 Min Reactive Power Q1 L1varRead
Stage 2 Min Reactive Power Q1 L2varRead
Stage 2 Min Reactive Power Q1 L3varRead
Stage 2 Min Power Factor L1Read
Stage 2 Min Power Factor L2Read
Stage 2 Min Power Factor L3Read
Stage 2 Min THD-R Voltage L1%Read
Stage 2 Min THD-R Voltage L2%Read
Stage 2 Min THD-R Voltage L3%Read
Stage 2 Min THD-R Current L1%Read
Stage 2 Min THD-R Current L2%Read
Stage 2 Min THD-R Current L3%Read
Stage 2 Min FrequencyHzRead
Stage 2 Min Average Voltage L-NVRead
Stage 2 Min Average Voltage L-LVRead
Stage 2 Min Average CurrentARead
Stage 2 Min Total Apparent PowerVARead
Stage 2 Min Total Active PowerWRead
Stage 2 Min Total Reactive Power Q1varRead
Stage 2 Min Total Power FactorRead
Stage 2 Min Voltage Unbalance%Read
Stage 2 Min Current Unbalance%Read
Stage 2 Min Neutral CurrentARead
Day History Error StateRead
Day History Current Period TimestampsRead
Today Active Energy Tariff 1Read
Today Active Energy Tariff 2Read
Day -1 TimestampsRead
Day -1 Active Energy Tariff 1Read
Day -1 Active Energy Tariff 2Read
Day -2 TimestampsRead
Day -2 Active Energy Tariff 1Read
Day -2 Active Energy Tariff 2Read
Day -3 TimestampsRead
Day -3 Active Energy Tariff 1Read
Day -3 Active Energy Tariff 2Read
Day -4 TimestampsRead
Day -4 Active Energy Tariff 1Read
Day -4 Active Energy Tariff 2Read
Day -5 TimestampsRead
Day -5 Active Energy Tariff 1Read
Day -5 Active Energy Tariff 2Read
Day -6 TimestampsRead
Day -6 Active Energy Tariff 1Read
Day -6 Active Energy Tariff 2Read
Day -7 TimestampsRead
Day -7 Active Energy Tariff 1Read
Day -7 Active Energy Tariff 2Read
Day -8 TimestampsRead
Day -8 Active Energy Tariff 1Read
Day -8 Active Energy Tariff 2Read
Day -9 TimestampsRead
Day -9 Active Energy Tariff 1Read
Day -9 Active Energy Tariff 2Read
Day -10 TimestampsRead
Day -10 Active Energy Tariff 1Read
Day -10 Active Energy Tariff 2Read
Day -11 TimestampsRead
Day -11 Active Energy Tariff 1Read
Day -11 Active Energy Tariff 2Read
Day -12 TimestampsRead
Day -12 Active Energy Tariff 1Read
Day -12 Active Energy Tariff 2Read
Day -13 TimestampsRead
Day -13 Active Energy Tariff 1Read
Day -13 Active Energy Tariff 2Read
Day -14 TimestampsRead
Day -14 Active Energy Tariff 1Read
Day -14 Active Energy Tariff 2Read
Day -15 TimestampsRead
Day -15 Active Energy Tariff 1Read
Day -15 Active Energy Tariff 2Read
Day -16 TimestampsRead
Day -16 Active Energy Tariff 1Read
Day -16 Active Energy Tariff 2Read
Day -17 TimestampsRead
Day -17 Active Energy Tariff 1Read
Day -17 Active Energy Tariff 2Read
Day -18 TimestampsRead
Day -18 Active Energy Tariff 1Read
Day -18 Active Energy Tariff 2Read
Day -19 TimestampsRead
Day -19 Active Energy Tariff 1Read
Day -19 Active Energy Tariff 2Read
Day -20 TimestampsRead
Day -20 Active Energy Tariff 1Read
Day -20 Active Energy Tariff 2Read
Day -21 TimestampsRead
Day -21 Active Energy Tariff 1Read
Day -21 Active Energy Tariff 2Read
Day -22 TimestampsRead
Day -22 Active Energy Tariff 1Read
Day -22 Active Energy Tariff 2Read
Day -23 TimestampsRead
Day -23 Active Energy Tariff 1Read
Day -23 Active Energy Tariff 2Read
Day -24 TimestampsRead
Day -24 Active Energy Tariff 1Read
Day -24 Active Energy Tariff 2Read
Day -25 TimestampsRead
Day -25 Active Energy Tariff 1Read
Day -25 Active Energy Tariff 2Read
Day -26 TimestampsRead
Day -26 Active Energy Tariff 1Read
Day -26 Active Energy Tariff 2Read
Day -27 TimestampsRead
Day -27 Active Energy Tariff 1Read
Day -27 Active Energy Tariff 2Read
Day -28 TimestampsRead
Day -28 Active Energy Tariff 1Read
Day -28 Active Energy Tariff 2Read
Day -29 TimestampsRead
Day -29 Active Energy Tariff 1Read
Day -29 Active Energy Tariff 2Read
Day -30 TimestampsRead
Day -30 Active Energy Tariff 1Read
Day -30 Active Energy Tariff 2Read
Day -31 TimestampsRead
Day -31 Active Energy Tariff 1Read
Day -31 Active Energy Tariff 2Read
Day -32 TimestampsRead
Day -32 Active Energy Tariff 1Read
Day -32 Active Energy Tariff 2Read
Day -33 TimestampsRead
Day -33 Active Energy Tariff 1Read
Day -33 Active Energy Tariff 2Read
Day -34 TimestampsRead
Day -34 Active Energy Tariff 1Read
Day -34 Active Energy Tariff 2Read
Day -35 TimestampsRead
Day -35 Active Energy Tariff 1Read
Day -35 Active Energy Tariff 2Read
Day -36 TimestampsRead
Day -36 Active Energy Tariff 1Read
Day -36 Active Energy Tariff 2Read
Day -37 TimestampsRead
Day -37 Active Energy Tariff 1Read
Day -37 Active Energy Tariff 2Read
Day -38 TimestampsRead
Day -38 Active Energy Tariff 1Read
Day -38 Active Energy Tariff 2Read
Day -39 TimestampsRead
Day -39 Active Energy Tariff 1Read
Day -39 Active Energy Tariff 2Read
Day -40 TimestampsRead
Day -40 Active Energy Tariff 1Read
Day -40 Active Energy Tariff 2Read
Day -41 TimestampsRead
Day -41 Active Energy Tariff 1Read
Day -41 Active Energy Tariff 2Read
Day -42 TimestampsRead
Day -42 Active Energy Tariff 1Read
Day -42 Active Energy Tariff 2Read
Day -43 TimestampsRead
Day -43 Active Energy Tariff 1Read
Day -43 Active Energy Tariff 2Read
Day -44 TimestampsRead
Day -44 Active Energy Tariff 1Read
Day -44 Active Energy Tariff 2Read
Day -45 TimestampsRead
Day -45 Active Energy Tariff 1Read
Day -45 Active Energy Tariff 2Read
Day -46 TimestampsRead
Day -46 Active Energy Tariff 1Read
Day -46 Active Energy Tariff 2Read
Day -47 TimestampsRead
Day -47 Active Energy Tariff 1Read
Day -47 Active Energy Tariff 2Read
Day -48 TimestampsRead
Day -48 Active Energy Tariff 1Read
Day -48 Active Energy Tariff 2Read
Day -49 TimestampsRead
Day -49 Active Energy Tariff 1Read
Day -49 Active Energy Tariff 2Read
Day -50 TimestampsRead
Day -50 Active Energy Tariff 1Read
Day -50 Active Energy Tariff 2Read
Day -51 TimestampsRead
Day -51 Active Energy Tariff 1Read
Day -51 Active Energy Tariff 2Read
Day -52 TimestampsRead
Day -52 Active Energy Tariff 1Read
Day -52 Active Energy Tariff 2Read
Day -53 TimestampsRead
Day -53 Active Energy Tariff 1Read
Day -53 Active Energy Tariff 2Read
Day -54 TimestampsRead
Day -54 Active Energy Tariff 1Read
Day -54 Active Energy Tariff 2Read
Day -55 TimestampsRead
Day -55 Active Energy Tariff 1Read
Day -55 Active Energy Tariff 2Read
Day -56 TimestampsRead
Day -56 Active Energy Tariff 1Read
Day -56 Active Energy Tariff 2Read
Day -57 TimestampsRead
Day -57 Active Energy Tariff 1Read
Day -57 Active Energy Tariff 2Read
Day -58 TimestampsRead
Day -58 Active Energy Tariff 1Read
Day -58 Active Energy Tariff 2Read
Day -59 TimestampsRead
Day -59 Active Energy Tariff 1Read
Day -59 Active Energy Tariff 2Read
Day -60 TimestampsRead
Day -60 Active Energy Tariff 1Read
Day -60 Active Energy Tariff 2Read
Day -61 TimestampsRead
Day -61 Active Energy Tariff 1Read
Day -61 Active Energy Tariff 2Read
Day -62 TimestampsRead
Day -62 Active Energy Tariff 1Read
Day -62 Active Energy Tariff 2Read
Day -63 TimestampsRead
Day -63 Active Energy Tariff 1Read
Day -63 Active Energy Tariff 2Read
Day -64 TimestampsRead
Day -64 Active Energy Tariff 1Read
Day -64 Active Energy Tariff 2Read
Month History Error StateRead
Month History Current Period TimestampsRead
This Month Active Energy Tariff 1Read
This Month Active Energy Tariff 2Read
Month -1 TimestampsRead
Month -1 Active Energy Tariff 1Read
Month -1 Active Energy Tariff 2Read
Month -2 TimestampsRead
Month -2 Active Energy Tariff 1Read
Month -2 Active Energy Tariff 2Read
Month -3 TimestampsRead
Month -3 Active Energy Tariff 1Read
Month -3 Active Energy Tariff 2Read
Month -4 TimestampsRead
Month -4 Active Energy Tariff 1Read
Month -4 Active Energy Tariff 2Read
Month -5 TimestampsRead
Month -5 Active Energy Tariff 1Read
Month -5 Active Energy Tariff 2Read
Month -6 TimestampsRead
Month -6 Active Energy Tariff 1Read
Month -6 Active Energy Tariff 2Read
Month -7 TimestampsRead
Month -7 Active Energy Tariff 1Read
Month -7 Active Energy Tariff 2Read
Month -8 TimestampsRead
Month -8 Active Energy Tariff 1Read
Month -8 Active Energy Tariff 2Read
Month -9 TimestampsRead
Month -9 Active Energy Tariff 1Read
Month -9 Active Energy Tariff 2Read
Month -10 TimestampsRead
Month -10 Active Energy Tariff 1Read
Month -10 Active Energy Tariff 2Read
Month -11 TimestampsRead
Month -11 Active Energy Tariff 1Read
Month -11 Active Energy Tariff 2Read
Month -12 TimestampsRead
Month -12 Active Energy Tariff 1Read
Month -12 Active Energy Tariff 2Read
Month -13 TimestampsRead
Month -13 Active Energy Tariff 1Read
Month -13 Active Energy Tariff 2Read
Month -14 TimestampsRead
Month -14 Active Energy Tariff 1Read
Month -14 Active Energy Tariff 2Read
Month -15 TimestampsRead
Month -15 Active Energy Tariff 1Read
Month -15 Active Energy Tariff 2Read
Month -16 TimestampsRead
Month -16 Active Energy Tariff 1Read
Month -16 Active Energy Tariff 2Read
Month -17 TimestampsRead
Month -17 Active Energy Tariff 1Read
Month -17 Active Energy Tariff 2Read
Month -18 TimestampsRead
Month -18 Active Energy Tariff 1Read
Month -18 Active Energy Tariff 2Read
Month -19 TimestampsRead
Month -19 Active Energy Tariff 1Read
Month -19 Active Energy Tariff 2Read
Month -20 TimestampsRead
Month -20 Active Energy Tariff 1Read
Month -20 Active Energy Tariff 2Read
Month -21 TimestampsRead
Month -21 Active Energy Tariff 1Read
Month -21 Active Energy Tariff 2Read
Month -22 TimestampsRead
Month -22 Active Energy Tariff 1Read
Month -22 Active Energy Tariff 2Read
Month -23 TimestampsRead
Month -23 Active Energy Tariff 1Read
Month -23 Active Energy Tariff 2Read
Month -24 TimestampsRead
Month -24 Active Energy Tariff 1Read
Month -24 Active Energy Tariff 2Read
I&M 0 DataRead
I&M 1 to 4 DataRead and write
I&M Data Module Interface 1Read
I&M Data Module Interface 2Read

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show voltage, current and power per phase of a distribution board on a ModbusCloud dashboard.
  • Send an email alert when the current on one phase or the neutral current passes a threshold.
  • Compare daily active energy per tariff in the history to find standby consumption at night.
  • Watch THD and voltage unbalance over a year to spot power quality problems early.
  • Correct the current transformer ratio remotely after a transformer swap on site.

Installation

  1. Connect the Ethernet port of the PAC3220 to the same network as the ModbusCloud Gateway, or to the LAN port of the Gateway.

  2. On the meter, open the communication settings, switch DHCP off and set a fixed IP address and subnet. Leave the Modbus port at 502.

  3. In ModbusCloud, add a Modbus TCP device with the IP address of the meter, port 502 and unit ID 1, and import this template.

  4. Check that voltage L1-N and frequency show plausible values. If they stay empty, check the IP address and whether the Modbus port is 0.

  5. Before you write settings, check that password protection for communication and the hardware write protection are off on the meter.

Things to watch for

The Gateway cannot reach the meter. What should I check?

Check that the meter and the Gateway are in the same subnet and that the IP address on the display matches the one in ModbusCloud. A Modbus port of 0 switches the Modbus TCP server off. With the IP filter on, only write commands from the own subnet are accepted.

Why does the export energy counter show no unit?

The export and reactive import counters are read as plain numbers. Compare the value with the energy menu on the display to see in which unit the meter counts, and set the unit of the register in ModbusCloud if you need it on a dashboard.

My write to a setting is refused. Why?

The meter rejects writes while password protection for communication or the hardware write protection is active. Switch both off on the device, then write again. Read the register first so you know the current value, and change one setting at a time.

Can I read several PAC meters through one Gateway?

Yes. Give each meter its own fixed IP address and add each one as its own Modbus TCP device in ModbusCloud with this template. PAC3120 meters on RS485 each need a unique Modbus address on the bus.

Why are the history values zero right after installation?

The daily and monthly energy history fills up over time. Days and months before the meter was installed, or before its clock was set, stay at zero. Set the date and time on the meter so the history timestamps are correct.

Want to see how it works?