SolarEdge Synergy Inverter (3 units)
Three-phase Synergy PV inverter: reads production, each Synergy unit and up to three energy meters.
The SolarEdge Synergy inverter is a three-phase PV inverter for commercial roofs, built from separate Synergy units under one manager. This Modbus TCP template reads AC and DC power, lifetime energy, each Synergy unit and up to three connected energy meters from ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 330, read only
- Brand
- SolarEdge
- Key readings
- AC power · Lifetime energy · DC power per unit · Operating state · Grid import and export · Synergy unit temperature
- Compatible models
- SolarEdge three phase inverters with Synergy technology and three Synergy units · SolarEdge Modbus Meter (meter 1 to 3 via the inverter)
- Last updated
Registers (330)
330 read, 0 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| AC Power | W | Read | 40083 | FC03 | int16 |
| AC Power Scale Factor | Read | 40084 | FC03 | int16 | |
| AC Lifetime Energy | Wh | Read | 40093 | FC03 | uint32 |
| AC Energy Scale Factor | Read | 40095 | FC03 | uint16 | |
| DC Power | W | Read | 40100 | FC03 | int16 |
| DC Power Scale Factor | Read | ||||
| Operating State | Read | ||||
| Vendor Status | Read | ||||
| Vendor Status Extended | Read | ||||
| AC Current | A | Read | |||
| AC Current Phase A | A | Read | |||
| AC Current Phase B | A | Read | |||
| AC Current Phase C | A | Read | |||
| AC Current Scale Factor | Read | ||||
| AC Voltage AB | V | Read | |||
| AC Voltage BC | V | Read | |||
| AC Voltage CA | V | Read | |||
| AC Voltage A-N | V | Read | |||
| AC Voltage B-N | V | Read | |||
| AC Voltage C-N | V | Read | |||
| AC Voltage Scale Factor | Read | ||||
| AC Frequency | Hz | Read | |||
| AC Frequency Scale Factor | Read | ||||
| AC Apparent Power | VA | Read | |||
| AC Apparent Power Scale Factor | Read | ||||
| AC Reactive Power | var | Read | |||
| AC Reactive Power Scale Factor | Read | ||||
| AC Power Factor | % | Read | |||
| AC Power Factor Scale Factor | Read | ||||
| DC Current | A | Read | |||
| DC Current Scale Factor | Read | ||||
| DC Voltage | V | Read | |||
| DC Voltage Scale Factor | Read | ||||
| Heat Sink Temperature | °C | Read | |||
| Temperature Scale Factor | Read | ||||
| Inverter Model ID | Read | ||||
| Inverter Model Length | Read | ||||
| SunSpec ID | Read | ||||
| Common Model ID | Read | ||||
| Common Model Length | Read | ||||
| Manufacturer | Read | ||||
| Model | Read | ||||
| Firmware Version | Read | ||||
| Serial Number | Read | ||||
| Device Address | Read | ||||
| Meter 1 Power | W | Read | |||
| Meter 1 Exported Energy | Wh | Read | |||
| Meter 1 Imported Energy | Wh | Read | |||
| Meter 1 Current | A | Read | |||
| Meter 1 Current Phase A | A | Read | |||
| Meter 1 Current Phase B | A | Read | |||
| Meter 1 Current Phase C | A | Read | |||
| Meter 1 Current Scale Factor | Read | ||||
| Meter 1 Voltage L-N | V | Read | |||
| Meter 1 Voltage A-N | V | Read | |||
| Meter 1 Voltage B-N | V | Read | |||
| Meter 1 Voltage C-N | V | Read | |||
| Meter 1 Voltage L-L | V | Read | |||
| Meter 1 Voltage AB | V | Read | |||
| Meter 1 Voltage BC | V | Read | |||
| Meter 1 Voltage CA | V | Read | |||
| Meter 1 Voltage Scale Factor | Read | ||||
| Meter 1 Frequency | Hz | Read | |||
| Meter 1 Frequency Scale Factor | Read | ||||
| Meter 1 Power Phase A | W | Read | |||
| Meter 1 Power Phase B | W | Read | |||
| Meter 1 Power Phase C | W | Read | |||
| Meter 1 Power Scale Factor | Read | ||||
| Meter 1 Apparent Power | VA | Read | |||
| Meter 1 Apparent Power Phase A | VA | Read | |||
| Meter 1 Apparent Power Phase B | VA | Read | |||
| Meter 1 Apparent Power Phase C | VA | Read | |||
| Meter 1 Apparent Power Scale Factor | Read | ||||
| Meter 1 Reactive Power | var | Read | |||
| Meter 1 Reactive Power Phase A | var | Read | |||
| Meter 1 Reactive Power Phase B | var | Read | |||
| Meter 1 Reactive Power Phase C | var | Read | |||
| Meter 1 Reactive Power Scale Factor | Read | ||||
| Meter 1 Power Factor | % | Read | |||
| Meter 1 Power Factor Phase A | % | Read | |||
| Meter 1 Power Factor Phase B | % | Read | |||
| Meter 1 Power Factor Phase C | % | Read | |||
| Meter 1 Power Factor Scale Factor | Read | ||||
| Meter 1 Exported Energy Phase A | Wh | Read | |||
| Meter 1 Exported Energy Phase B | Wh | Read | |||
| Meter 1 Exported Energy Phase C | Wh | Read | |||
| Meter 1 Imported Energy Phase A | Wh | Read | |||
| Meter 1 Imported Energy Phase B | Wh | Read | |||
| Meter 1 Imported Energy Phase C | Wh | Read | |||
| Meter 1 Real Energy Scale Factor | Read | ||||
| Meter 1 Exported Apparent Energy | VAh | Read | |||
| Meter 1 Exported Apparent Energy A | VAh | Read | |||
| Meter 1 Exported Apparent Energy B | VAh | Read | |||
| Meter 1 Exported Apparent Energy C | VAh | Read | |||
| Meter 1 Imported Apparent Energy | VAh | Read | |||
| Meter 1 Imported Apparent Energy A | VAh | Read | |||
| Meter 1 Imported Apparent Energy B | VAh | Read | |||
| Meter 1 Imported Apparent Energy C | VAh | Read | |||
| Meter 1 Apparent Energy Scale Factor | Read | ||||
| Meter 1 Reactive Energy Q1 | varh | Read | |||
| Meter 1 Reactive Energy Q1 A | varh | Read | |||
| Meter 1 Reactive Energy Q1 B | varh | Read | |||
| Meter 1 Reactive Energy Q1 C | varh | Read | |||
| Meter 1 Reactive Energy Q2 | varh | Read | |||
| Meter 1 Reactive Energy Q2 A | varh | Read | |||
| Meter 1 Reactive Energy Q2 B | varh | Read | |||
| Meter 1 Reactive Energy Q2 C | varh | Read | |||
| Meter 1 Reactive Energy Q3 | varh | Read | |||
| Meter 1 Reactive Energy Q3 A | varh | Read | |||
| Meter 1 Reactive Energy Q3 B | varh | Read | |||
| Meter 1 Reactive Energy Q3 C | varh | Read | |||
| Meter 1 Reactive Energy Q4 | varh | Read | |||
| Meter 1 Reactive Energy Q4 A | varh | Read | |||
| Meter 1 Reactive Energy Q4 B | varh | Read | |||
| Meter 1 Reactive Energy Q4 C | varh | Read | |||
| Meter 1 Reactive Energy Scale Factor | Read | ||||
| Meter 1 Events | Read | ||||
| Meter 1 Meter Model ID | Read | ||||
| Meter 1 Meter Model Length | Read | ||||
| Meter 1 Common Model ID | Read | ||||
| Meter 1 Common Model Length | Read | ||||
| Meter 1 Manufacturer | Read | ||||
| Meter 1 Model | Read | ||||
| Meter 1 Function | Read | ||||
| Meter 1 Version | Read | ||||
| Meter 1 Serial Number | Read | ||||
| Meter 1 Device Address | Read | ||||
| Meter 2 Power | W | Read | |||
| Meter 2 Exported Energy | Wh | Read | |||
| Meter 2 Imported Energy | Wh | Read | |||
| Meter 2 Current | A | Read | |||
| Meter 2 Current Phase A | A | Read | |||
| Meter 2 Current Phase B | A | Read | |||
| Meter 2 Current Phase C | A | Read | |||
| Meter 2 Current Scale Factor | Read | ||||
| Meter 2 Voltage L-N | V | Read | |||
| Meter 2 Voltage A-N | V | Read | |||
| Meter 2 Voltage B-N | V | Read | |||
| Meter 2 Voltage C-N | V | Read | |||
| Meter 2 Voltage L-L | V | Read | |||
| Meter 2 Voltage AB | V | Read | |||
| Meter 2 Voltage BC | V | Read | |||
| Meter 2 Voltage CA | V | Read | |||
| Meter 2 Voltage Scale Factor | Read | ||||
| Meter 2 Frequency | Hz | Read | |||
| Meter 2 Frequency Scale Factor | Read | ||||
| Meter 2 Power Phase A | W | Read | |||
| Meter 2 Power Phase B | W | Read | |||
| Meter 2 Power Phase C | W | Read | |||
| Meter 2 Power Scale Factor | Read | ||||
| Meter 2 Apparent Power | VA | Read | |||
| Meter 2 Apparent Power Phase A | VA | Read | |||
| Meter 2 Apparent Power Phase B | VA | Read | |||
| Meter 2 Apparent Power Phase C | VA | Read | |||
| Meter 2 Apparent Power Scale Factor | Read | ||||
| Meter 2 Reactive Power | var | Read | |||
| Meter 2 Reactive Power Phase A | var | Read | |||
| Meter 2 Reactive Power Phase B | var | Read | |||
| Meter 2 Reactive Power Phase C | var | Read | |||
| Meter 2 Reactive Power Scale Factor | Read | ||||
| Meter 2 Power Factor | % | Read | |||
| Meter 2 Power Factor Phase A | % | Read | |||
| Meter 2 Power Factor Phase B | % | Read | |||
| Meter 2 Power Factor Phase C | % | Read | |||
| Meter 2 Power Factor Scale Factor | Read | ||||
| Meter 2 Exported Energy Phase A | Wh | Read | |||
| Meter 2 Exported Energy Phase B | Wh | Read | |||
| Meter 2 Exported Energy Phase C | Wh | Read | |||
| Meter 2 Imported Energy Phase A | Wh | Read | |||
| Meter 2 Imported Energy Phase B | Wh | Read | |||
| Meter 2 Imported Energy Phase C | Wh | Read | |||
| Meter 2 Real Energy Scale Factor | Read | ||||
| Meter 2 Exported Apparent Energy | VAh | Read | |||
| Meter 2 Exported Apparent Energy A | VAh | Read | |||
| Meter 2 Exported Apparent Energy B | VAh | Read | |||
| Meter 2 Exported Apparent Energy C | VAh | Read | |||
| Meter 2 Imported Apparent Energy | VAh | Read | |||
| Meter 2 Imported Apparent Energy A | VAh | Read | |||
| Meter 2 Imported Apparent Energy B | VAh | Read | |||
| Meter 2 Imported Apparent Energy C | VAh | Read | |||
| Meter 2 Apparent Energy Scale Factor | Read | ||||
| Meter 2 Reactive Energy Q1 | varh | Read | |||
| Meter 2 Reactive Energy Q1 A | varh | Read | |||
| Meter 2 Reactive Energy Q1 B | varh | Read | |||
| Meter 2 Reactive Energy Q1 C | varh | Read | |||
| Meter 2 Reactive Energy Q2 | varh | Read | |||
| Meter 2 Reactive Energy Q2 A | varh | Read | |||
| Meter 2 Reactive Energy Q2 B | varh | Read | |||
| Meter 2 Reactive Energy Q2 C | varh | Read | |||
| Meter 2 Reactive Energy Q3 | varh | Read | |||
| Meter 2 Reactive Energy Q3 A | varh | Read | |||
| Meter 2 Reactive Energy Q3 B | varh | Read | |||
| Meter 2 Reactive Energy Q3 C | varh | Read | |||
| Meter 2 Reactive Energy Q4 | varh | Read | |||
| Meter 2 Reactive Energy Q4 A | varh | Read | |||
| Meter 2 Reactive Energy Q4 B | varh | Read | |||
| Meter 2 Reactive Energy Q4 C | varh | Read | |||
| Meter 2 Reactive Energy Scale Factor | Read | ||||
| Meter 2 Events | Read | ||||
| Meter 2 Meter Model ID | Read | ||||
| Meter 2 Meter Model Length | Read | ||||
| Meter 2 Common Model ID | Read | ||||
| Meter 2 Common Model Length | Read | ||||
| Meter 2 Manufacturer | Read | ||||
| Meter 2 Model | Read | ||||
| Meter 2 Function | Read | ||||
| Meter 2 Version | Read | ||||
| Meter 2 Serial Number | Read | ||||
| Meter 2 Device Address | Read | ||||
| Meter 3 Power | W | Read | |||
| Meter 3 Exported Energy | Wh | Read | |||
| Meter 3 Imported Energy | Wh | Read | |||
| Meter 3 Current | A | Read | |||
| Meter 3 Current Phase A | A | Read | |||
| Meter 3 Current Phase B | A | Read | |||
| Meter 3 Current Phase C | A | Read | |||
| Meter 3 Current Scale Factor | Read | ||||
| Meter 3 Voltage L-N | V | Read | |||
| Meter 3 Voltage A-N | V | Read | |||
| Meter 3 Voltage B-N | V | Read | |||
| Meter 3 Voltage C-N | V | Read | |||
| Meter 3 Voltage L-L | V | Read | |||
| Meter 3 Voltage AB | V | Read | |||
| Meter 3 Voltage BC | V | Read | |||
| Meter 3 Voltage CA | V | Read | |||
| Meter 3 Voltage Scale Factor | Read | ||||
| Meter 3 Frequency | Hz | Read | |||
| Meter 3 Frequency Scale Factor | Read | ||||
| Meter 3 Power Phase A | W | Read | |||
| Meter 3 Power Phase B | W | Read | |||
| Meter 3 Power Phase C | W | Read | |||
| Meter 3 Power Scale Factor | Read | ||||
| Meter 3 Apparent Power | VA | Read | |||
| Meter 3 Apparent Power Phase A | VA | Read | |||
| Meter 3 Apparent Power Phase B | VA | Read | |||
| Meter 3 Apparent Power Phase C | VA | Read | |||
| Meter 3 Apparent Power Scale Factor | Read | ||||
| Meter 3 Reactive Power | var | Read | |||
| Meter 3 Reactive Power Phase A | var | Read | |||
| Meter 3 Reactive Power Phase B | var | Read | |||
| Meter 3 Reactive Power Phase C | var | Read | |||
| Meter 3 Reactive Power Scale Factor | Read | ||||
| Meter 3 Power Factor | % | Read | |||
| Meter 3 Power Factor Phase A | % | Read | |||
| Meter 3 Power Factor Phase B | % | Read | |||
| Meter 3 Power Factor Phase C | % | Read | |||
| Meter 3 Power Factor Scale Factor | Read | ||||
| Meter 3 Exported Energy Phase A | Wh | Read | |||
| Meter 3 Exported Energy Phase B | Wh | Read | |||
| Meter 3 Exported Energy Phase C | Wh | Read | |||
| Meter 3 Imported Energy Phase A | Wh | Read | |||
| Meter 3 Imported Energy Phase B | Wh | Read | |||
| Meter 3 Imported Energy Phase C | Wh | Read | |||
| Meter 3 Real Energy Scale Factor | Read | ||||
| Meter 3 Exported Apparent Energy | VAh | Read | |||
| Meter 3 Exported Apparent Energy A | VAh | Read | |||
| Meter 3 Exported Apparent Energy B | VAh | Read | |||
| Meter 3 Exported Apparent Energy C | VAh | Read | |||
| Meter 3 Imported Apparent Energy | VAh | Read | |||
| Meter 3 Imported Apparent Energy A | VAh | Read | |||
| Meter 3 Imported Apparent Energy B | VAh | Read | |||
| Meter 3 Imported Apparent Energy C | VAh | Read | |||
| Meter 3 Apparent Energy Scale Factor | Read | ||||
| Meter 3 Reactive Energy Q1 | varh | Read | |||
| Meter 3 Reactive Energy Q1 A | varh | Read | |||
| Meter 3 Reactive Energy Q1 B | varh | Read | |||
| Meter 3 Reactive Energy Q1 C | varh | Read | |||
| Meter 3 Reactive Energy Q2 | varh | Read | |||
| Meter 3 Reactive Energy Q2 A | varh | Read | |||
| Meter 3 Reactive Energy Q2 B | varh | Read | |||
| Meter 3 Reactive Energy Q2 C | varh | Read | |||
| Meter 3 Reactive Energy Q3 | varh | Read | |||
| Meter 3 Reactive Energy Q3 A | varh | Read | |||
| Meter 3 Reactive Energy Q3 B | varh | Read | |||
| Meter 3 Reactive Energy Q3 C | varh | Read | |||
| Meter 3 Reactive Energy Q4 | varh | Read | |||
| Meter 3 Reactive Energy Q4 A | varh | Read | |||
| Meter 3 Reactive Energy Q4 B | varh | Read | |||
| Meter 3 Reactive Energy Q4 C | varh | Read | |||
| Meter 3 Reactive Energy Scale Factor | Read | ||||
| Meter 3 Events | Read | ||||
| Meter 3 Meter Model ID | Read | ||||
| Meter 3 Meter Model Length | Read | ||||
| Meter 3 Common Model ID | Read | ||||
| Meter 3 Common Model Length | Read | ||||
| Meter 3 Manufacturer | Read | ||||
| Meter 3 Model | Read | ||||
| Meter 3 Function | Read | ||||
| Meter 3 Version | Read | ||||
| Meter 3 Serial Number | Read | ||||
| Meter 3 Device Address | Read | ||||
| MPPT Model ID | Read | ||||
| MPPT Model Length | Read | ||||
| MPPT Current Scale Factor | Read | ||||
| MPPT Voltage Scale Factor | Read | ||||
| MPPT Power Scale Factor | Read | ||||
| MPPT Energy Scale Factor | Read | ||||
| MPPT Events | Read | ||||
| Synergy Unit Count | Read | ||||
| MPPT Timestamp Period | Read | ||||
| Synergy Unit 0 ID | Read | ||||
| Synergy Unit 0 ID String | Read | ||||
| Synergy Unit 0 DC Current | A | Read | |||
| Synergy Unit 0 DC Voltage | V | Read | |||
| Synergy Unit 0 DC Power | W | Read | |||
| Synergy Unit 0 DC Energy | Wh | Read | |||
| Synergy Unit 0 Timestamp | s | Read | |||
| Synergy Unit 0 Temperature | °C | Read | |||
| Synergy Unit 0 Operating State | Read | ||||
| Synergy Unit 0 Events | Read | ||||
| Synergy Unit 1 ID | Read | ||||
| Synergy Unit 1 ID String | Read | ||||
| Synergy Unit 1 DC Current | A | Read | |||
| Synergy Unit 1 DC Voltage | V | Read | |||
| Synergy Unit 1 DC Power | W | Read | |||
| Synergy Unit 1 DC Energy | Wh | Read | |||
| Synergy Unit 1 Timestamp | s | Read | |||
| Synergy Unit 1 Temperature | °C | Read | |||
| Synergy Unit 1 Operating State | Read | ||||
| Synergy Unit 1 Events | Read | ||||
| Synergy Unit 2 ID | Read | ||||
| Synergy Unit 2 ID String | Read | ||||
| Synergy Unit 2 DC Current | A | Read | |||
| Synergy Unit 2 DC Voltage | V | Read | |||
| Synergy Unit 2 DC Power | W | Read | |||
| Synergy Unit 2 DC Energy | Wh | Read | |||
| Synergy Unit 2 Timestamp | s | Read | |||
| Synergy Unit 2 Temperature | °C | Read | |||
| Synergy Unit 2 Operating State | Read | ||||
| Synergy Unit 2 Events | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show solar production, grid import and grid export side by side on one ModbusCloud dashboard.
- Compare the DC power of the three Synergy units to spot a unit or string that falls behind.
- Send an email when the operating state changes to Fault so you can act before the customer calls.
- Alert when a Synergy unit temperature stays high, a sign of blocked airflow.
- Track imported and exported energy per phase in the history for the energy report.
Installation
Connect the inverter to the same network as the ModbusCloud Gateway with an Ethernet cable.
In SetApp or on the inverter display, open Site Communication, Modbus TCP and enable it. Note the port (1502 by default) and the device ID (1).
In ModbusCloud, add a Modbus TCP device with the IP address of the inverter, port 1502 and unit ID 1, and import the SolarEdge Synergy Inverter (3 units) template.
Check that the operating state and AC power come in, and that the meter values appear for each meter configured on the inverter.
Things to watch for
The inverter does not answer on port 502. What is wrong?
SolarEdge uses port 1502 by default, not 502, and Modbus TCP is disabled until you enable it in SetApp or on the display. Check the port in the Modbus TCP menu and enter the same port in ModbusCloud.
Why are the values a factor 10 or 100 too high or too low?
SolarEdge sends each value as a whole number with a separate scale factor register, for example AC Power and AC Power Scale Factor. The real value is the raw value times 10 to the power of the scale factor. Read both and combine them, or check the scale factor once and set a fixed multiplier.
The connection drops when another system also reads the inverter.
The inverter accepts only one Modbus TCP client at a time. If a home energy manager or another logger already polls it, one of them loses the connection. Let one system read the inverter and share the values from there.
Synergy Unit Count shows 2, or the meter values look wrong.
This template is for Synergy inverters with three units. With two units the meter blocks start 20 registers earlier, so the meter values do not match. Check Synergy Unit Count: with 2, use a template for two Synergy units instead.
Knowledge base articles for this device
Want to see how it works?