Thytronic Thytronic NA011 Modbus RTU template

Thytronic NA011

Feeder protection relay with phase and residual overcurrent, automatic reclosing and breaker failure protection.

The Thytronic NA011 is a feeder protection relay that guards medium voltage lines and transformers against phase and earth faults, with automatic reclosing and breaker failure protection. This Modbus RTU template reads the phase and residual currents, breaker position, trip flags and counters, and lets you change protection settings, operate the breaker and send store and reset commands from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
106, read and write
Key readings
Phase currents · Residual current · Breaker position · Trip flags · Autoreclose state · Start, trip and reclose counters · Self-test status
Available commands
Overcurrent thresholds · Time curves and operate times · Cold load pickup · Breaker open and close · Autoreclose on and off · Store, reset and test commands
Compatible models
NA011
Last updated

Registers (106)

100 read, 60 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Phase Current L1ARead
Phase Current L2ARead
Phase Current L3ARead
Residual CurrentARead
Protection Trip FlagsRead
Breaker PositionRead
Input IN1Read
Input IN2Read
Input IN3Read
Autoreclose ActiveRead
Self-Test LevelRead
Oscillography Recorder StateRead
Settings CommandWrite
Reset CommandWrite
Breaker CommandWrite
Autoreclose CommandWrite
Test CommandWrite
Recorded Data Default CommandWrite
Modbus AddressRead and write
RS485 ProtocolRead and write
RS485 Baud RateRead and write
Measurement Reading ModeRead and write
Phase CT Primary CurrentARead
Residual CT Primary CurrentARead
Fault Record SelectRead and write
Event Record SelectRead and write
I> Time CurveRead and write
I> Inverse Pickup (x In)Read and write
t> Inverse Time SettingsRead and write
I> Definite Pickup (x In)Read and write
t> Definite Operate TimesRead and write
t> Reset TimemsRead and write
I> Cold Load ModeRead and write
I> Cold Load TimesRead and write
I> Definite Cold Load Pickup (x In)Read and write
I> Inverse Cold Load Pickup (x In)Read and write
I>> Pickup (x In)Read and write
t>> Operate TimesRead and write
t>> Reset TimemsRead and write
I>> Cold Load ModeRead and write
I>> Cold Load TimesRead and write
I>> Cold Load Pickup (x In)Read and write
I>>> Pickup (x In)Read and write
t>>> Operate TimesRead and write
t>>> Reset TimemsRead and write
I>>> Cold Load ModeRead and write
I>>> Cold Load TimesRead and write
I>>> Cold Load Pickup (x In)Read and write
IE> Time CurveRead and write
IE> Inverse Pickup (x IEn)Read and write
tE> Inverse Time SettingsRead and write
IE> Definite Pickup (x IEn)Read and write
tE> Definite Operate TimesRead and write
tE> Reset TimemsRead and write
IE> Cold Load ModeRead and write
IE> Cold Load TimesRead and write
IE> Definite Cold Load Pickup (x IEn)Read and write
IE> Inverse Cold Load Pickup (x IEn)Read and write
IE>> Time CurveRead and write
IE>> Inverse Pickup (x IEn)Read and write
tE>> Inverse Time SettingsRead and write
IE>> Definite Pickup (x IEn)Read and write
tE>> Definite Operate TimesRead and write
tE>> Reset TimemsRead and write
IE>> Cold Load ModeRead and write
IE>> Cold Load TimesRead and write
IE>> Definite Cold Load Pickup (x IEn)Read and write
IE>> Inverse Cold Load Pickup (x IEn)Read and write
Breaker Failure TriggersRead and write
Breaker Failure TimesRead and write
Input IN1 FunctionRead and write
Input IN2 FunctionRead and write
Input IN3 FunctionRead and write
Autoreclose EnableRead
Autoreclose TriggersRead and write
Relay K1 FunctionsRead
Relay K2 FunctionsRead
Relay K3 FunctionsRead
Relay K4 FunctionsRead
Enable TX DelaymsRead
Oscillography Pre-TriggerRead
Start Count I>Read
Start Count I>>Read
Start Count I>>>Read
Start Count IE>Read
Start Count IE>>Read
Trip Count I>Read
Trip Count I>>Read
Trip Count I>>>Read
Trip Count IE>Read
Trip Count IE>>Read
Trip Count ExternalRead
Rapid Reclose CountRead
Slow Reclose CountRead
Delayed Reclose CountRead
Failed Reclose Count PhaseRead
Failed Reclose Count EarthRead
Failed Reclose Count ExternalRead
Faults StoredRead
Selected Fault NumberRead
Events StoredRead
Selected Event NumberRead
Oscillography Records StoredRead
Clock YearRead
Device IdentificationRead
Product CodeRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the phase and residual currents of each feeder on a dashboard and keep a year of history per value.
  • Send an e-mail or webhook alert as soon as the trip flags rise above zero.
  • Follow the reclose and failed reclose counters to see how often a line sees transient or lasting faults.
  • Check the overcurrent thresholds and curves remotely and adjust them during commissioning.
  • Get an alert when the breaker position changes to alarm or the self-test reports a problem.

Installation

  1. Wire the rear RS485 port of the NA011 to the RS485 port of the ModbusCloud Gateway, A to A and B to B, and terminate the bus at both ends with 120 Ω.

  2. On the relay, open the Communication menu, set the RS485 protocol to Modbus and note the address and baud rate (default 1 and 9600 baud).

  3. In ModbusCloud, add a Modbus device on the RS485 port of the Gateway with the same address, 9600 baud, 8 data bits, no parity and 1 stop bit.

  4. Import the Thytronic NA011 template and check that the phase currents and the breaker position come in.

  5. Compare the currents with the relay display, and set the CT primary currents on the relay if you read primary amps.

Things to watch for

The Gateway gets no answer from the NA011. What should I check?

Check that the RS485 protocol on the relay is set to Modbus and not IEC 60870-5-103, that the address and baud rate match the device in ModbusCloud, and that A and B are not swapped. Terminate the bus with 120 Ω at both ends.

The currents do not match the relay display. Why?

With the default Reading Direct the relay reports primary amps, calculated from the phase and residual CT primary currents set under Set, Base. With Reading Relative it reports multiples of the rated current. Check both settings on the relay and compare again.

I wrote a new threshold, but it is gone after a restart. Why?

The NA011 keeps changed settings in temporary memory until it receives the store command. After writing new values, write Store to the Settings Command register, or Clear to discard the changes. Read a setting first before you write it, so you know the current value.

Some values stay empty while the currents come in. Is that normal?

The clock, the identification, the autoreclose state and the fault and event records are part of larger messages that the relay may only send as a whole. The template fits NA011 relays with identification code 105 or 106; older relays with codes 101 to 104 use a different layout.

Can a command from ModbusCloud open the circuit breaker?

Yes. Breaker Command opens or closes the breaker through the output relays assigned to CB Open and CB Close, and a test with trip operates the output relays. Only use them during commissioning or maintenance with the feeder in a safe state.