Thytronic Thytronic NA016 Modbus RTU template

Thytronic NA016

Feeder protection relay with phase and residual overcurrent protection and breaker monitoring.

The Thytronic NA016 is a feeder protection relay that guards medium voltage lines and transformers against phase and earth faults and supervises the trip circuit and circuit breaker. This Modbus RTU template reads the phase and residual currents, breaker position, trip flags and counters, and lets you change protection thresholds and send store and reset commands from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
68, read and write
Key readings
Phase currents · Residual current · Breaker position · Trip flags · Start and trip counters · Self-test status
Available commands
Overcurrent thresholds · Operate and reset times · Inverse time curve · Store and reset commands · Protection test
Compatible models
NA016
Last updated

Registers (68)

64 read, 28 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Phase Current L1ARead
Phase Current L2ARead
Phase Current L3ARead
Residual CurrentARead
Protection Trip FlagsRead
Breaker PositionRead
Trip Circuit SupervisionRead
Input IN1 (52b)Read
Input IN2 (52a)Read
Input IN3 (TCS)Read
Self-Test LevelRead
Oscillography Recorder StateRead
Start Count I>Read
Start Count I>>Read
Start Count I>>>Read
Start Count IE>Read
Start Count IE>>Read
Trip Count I>Read
Trip Count I>>Read
Trip Count I>>>Read
Trip Count IE>Read
Trip Count IE>>Read
Device IdentificationRead
Product CodeRead
Clock YearRead
Oscillography Records StoredRead
Faults StoredRead
Selected Fault NumberRead
Events StoredRead
Selected Event NumberRead
Setting Changes StoredRead
Selected Setting Change NumberRead
Settings CommandWrite
Recorded Data Default CommandWrite
Reset CommandWrite
Test CommandWrite
Modbus AddressRead and write
RS485 ProtocolRead and write
RS485 Baud RateRead and write
Fault Record SelectRead and write
Event Record SelectRead and write
Setting Record SelectRead and write
Measurement Reading ModeRead and write
I> Inverse Time CurveRead and write
I> Pickup (x In)Read and write
t> Inverse Time SettingsRead and write
I>> Pickup (x In)Read and write
t>> Operate TimesRead and write
t>> Reset TimemsRead and write
I>>> Pickup (x In)Read and write
t>>> Operate TimesRead and write
t>>> Reset TimemsRead and write
IE> Pickup (x IEn)Read and write
tE> Operate TimesRead and write
tE> Reset TimemsRead and write
IE>> Pickup (x IEn)Read and write
tE>> Operate TimesRead and write
tE>> Reset TimemsRead and write
Breaker DiagnosticRead and write
Trip Circuit Supervision EnableRead and write
Enable TX DelaymsRead
Oscillography Pre-TriggerRead
Phase CT Primary CurrentARead
Residual CT Primary CurrentARead
Relay K1 FunctionsRead
Relay K2 FunctionsRead
Relay K3 FunctionsRead
Relay K4 FunctionsRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the phase and residual currents of each feeder on a dashboard and keep a year of history per value.
  • Send an e-mail or webhook alert as soon as the trip flags rise above zero.
  • Follow the start and trip counters per threshold to see how often a feeder sees faults.
  • Check the overcurrent thresholds and operate times remotely and adjust them during commissioning.
  • Watch the self-test status and the trip circuit supervision to spot relay or wiring problems early.

Installation

  1. Wire the rear RS485 terminals A+ and B- of the NA016 to the RS485 port of the ModbusCloud Gateway, and terminate the bus at both ends with 120 Ω.

  2. On the relay, open the Communication menu, set the RS485 protocol to Modbus and note the address and baud rate (default 1 and 9600 baud).

  3. In ModbusCloud, add a Modbus device on the RS485 port of the Gateway with the same address, 9600 baud, 8 data bits, no parity and 1 stop bit.

  4. Import the Thytronic NA016 template and check that the phase currents and the breaker position come in.

  5. Compare the currents with the relay display, and set the CT primary currents on the relay if you read primary amps.

Things to watch for

The Gateway gets no answer from the NA016. What should I check?

Check that the RS485 protocol on the relay is set to Modbus and not IEC 60870-5-103, that the address and baud rate match the device in ModbusCloud, and that A+ and B- are not swapped. Terminate the bus with 120 Ω at both ends.

The currents do not match the relay display. Why?

With the default Reading Direct the relay reports primary amps, calculated from the phase and residual CT primary currents set under Set, Base. With Reading Relative it reports multiples of the rated current. Check both settings on the relay and compare again.

I wrote a new threshold, but it is gone after a restart. Why?

The NA016 keeps changed settings in temporary memory until it receives the store command. After writing new values, write Store to the Settings Command register, or Clear to discard the changes. Read a setting first before you write it, so you know the current value.

Some values stay empty while the currents come in. Is that normal?

The clock, the identification and the fault, event and setting records are part of larger messages that the relay may only send as a whole. When one of those stays empty, the currents, inputs, breaker position and counters are still read as normal.

Can a test command trip the circuit breaker?

Yes. The test command runs each protection element with or without operating the output relays. A test with trip opens the circuit breaker, so only use it during commissioning or maintenance with the feeder in a safe state.

Want to see how it works?