Thytronic Thytronic SVF5740 Modbus RTU template

Thytronic SVF5740

Interface protection relay with voltage, frequency, rate of change and vector jump protection to ENEL DK5740.

The Thytronic SVF5740 is an interface protection relay that disconnects generators running in parallel with the medium voltage network on abnormal voltage or frequency, to ENEL DK5740 and CEI 11-20. This Modbus RTU template reads the phase and residual voltages, frequency, trip flags and thresholds, and lets you send store, reset, test and remote trip commands from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
61, read and write
Key readings
Phase voltages · Residual voltage · Frequency · Rate of change of frequency · Trip flags · Protection thresholds · Self-test status · Undervoltage start and trip counts
Available commands
Rated frequency · Reading mode · Breaker failure time · Store and reset commands · Protection test · Remote trip
Compatible models
SVF5740
Last updated

Registers (61)

56 read, 15 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Voltage L1VRead
Voltage L2VRead
Voltage L3VRead
Residual VoltageVRead
FrequencyHzRead
Rate of Change of FrequencyRead
Protection Trip FlagsRead
Digital Input DIGIN1Read
Digital Input DIGIN2Read
Relay ModelRead
Self-Test LevelRead
U< Pickup (x Un)Read
U<< Pickup (x Un)Read
3U< Pickup (x Un)Read
U> Pickup (x Un)Read
U>> Pickup (x Un)Read
3U> Pickup (x Un)Read
3U>> Pickup (x Un)Read
UE> Pickup (x UEn)Read
f< Pickup (x fn)Read
f<< Pickup (x fn)Read
f> Pickup (x fn)Read
f>> Pickup (x fn)Read
df/dt Pickup (Hz/s)Read
Vector Jump Pickup°Read
Frequency Inhibit Voltage (x Un)Read
Breaker Failure TimesRead and write
Breaker Contact TypeRead and write
Rated FrequencyHzRead and write
Measurement Reading ModeRead and write
Voltage Input ModeRead
Keypad Setting AccessRead and write
Rated Voltage UnVRead
Rated Residual Voltage UEnVRead
Relay K1 FunctionsRead
Relay K1 Timer tTR1msRead and write
Relay K2 FunctionsRead
Relay K2 Timer tTR2msRead and write
Relay K3 FunctionsRead
Relay K3 Timer tTR3msRead and write
Relay K4 FunctionsRead
Relay K4 Timer tTR4msRead and write
Settings CommandWrite
Reset CommandWrite
Test CommandWrite
Remote Trip CommandWrite
Recorded Data Default CommandWrite
Modbus AddressRead and write
RS485 Baud RateRead
Enable TX DelaymsRead
Start Count U<Read
Trip Count U<Read
Events StoredRead
Event 1 Reading ModeRead
Event 2 Reading ModeRead
Event 3 Reading ModeRead
Event 4 Reading ModeRead
Clock YearRead
Set Clock YearRead
Device IdentificationRead
Mean Cycle TimeRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the phase voltages and the frequency of the grid connection on a dashboard and keep a year of history per value.
  • Send an e-mail or webhook alert as soon as the trip flags rise above zero.
  • Watch the rate of change of frequency and the residual voltage to see how close the grid gets to the trip thresholds.
  • Check the voltage and frequency thresholds remotely before an inspection of the interface protection.
  • Watch the self-test status to spot relay or breaker failures early.

Installation

  1. Wire the rear RS485 terminals A and B of the SVF5740 to the RS485 port of the ModbusCloud Gateway, and terminate the bus at both ends with 120 Ω.

  2. On the relay, check the Modbus address, baud rate, parity and stop bits with the keypad or ThySetter (default 1, 9600 baud, no parity, 1 stop bit).

  3. In ModbusCloud, add a Modbus device on the RS485 port of the Gateway with the same address, 9600 baud, 8 data bits, no parity and 1 stop bit.

  4. Import the Thytronic SVF5740 template and check that the voltages and the frequency come in and that Device Identification shows 9. With 22, use the Thytronic DMC5740 template.

  5. Compare the voltages with the relay display or ThySetter, and set the VT primary voltage on the relay if you read primary volts.

Things to watch for

The Gateway gets no answer from the SVF5740. What should I check?

Check that the address, baud rate, parity and stop bits on the relay match the device in ModbusCloud, and that A and B are not swapped. Terminate the bus with 120 Ω at both ends. The front RS232 port is only for a PC with ThySetter.

The voltages do not match the relay display. Why?

With the default Reading Direct the relay reports primary volts, calculated from the VT primary voltage set under Set, Base. With Reading Relative it reports multiples of Un and, for the residual voltage, of UEn. Check the reading mode and the rated values on the relay and compare again.

I changed a setting, but it is gone after a restart. Why?

The SVF5740 keeps changed settings in temporary memory until it receives the store command. Write Store to the Settings Command register, or Clear to discard the changes, and read a setting first before you write it. The thresholds and their delays are written as one message, so change those with the keypad or ThySetter.

Some values stay empty while the voltages come in. Is that normal?

The clock, the identification, the event records, the counters, the thresholds and the output relay functions are part of larger messages that the relay may only send as a whole. When one of those stays empty, the voltages, frequency and trip flags are still read as normal.

Can a command from ModbusCloud disconnect the generator?

Yes. The remote trip command and a test with trip operate the output relays and open the interface breaker, so the generator disconnects. Only use these commands during commissioning or maintenance, with the plant in a safe state.

Want to see how it works?

Electrician working in an open distribution board