Thytronic Thytronic SME-O Modbus RTU template

Thytronic SME-O

Fault detector for medium voltage substations with directional earth fault, overcurrent and voltage detection.

The Thytronic SME-O is a fault detector for remote controlled medium voltage secondary substations that detects short circuits and earth faults on the line and signals them to the control centre. This Modbus RTU template reads the phase voltages and currents, residual and sequence values, the earth fault angle and the fault records, and lets you change thresholds, times and modes from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
91, read and write
Key readings
Phase voltages · Phase currents · Residual voltage and current · Sequence voltages · Earth fault angle · Current loop output · Fault and event records
Available commands
Directional earth fault settings · Overcurrent thresholds · Voltage thresholds · Operating mode · Sensor calibration · Store, reset and test commands
Compatible models
SME-O · SMEO
Last updated

Registers (91)

86 read, 64 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Phase Voltage V4%Read
Phase Voltage V8%Read
Phase Voltage V12%Read
Phase Current I4ARead
Phase Current I8ARead
Phase Current I12ARead
Residual Voltage%Read
Residual CurrentARead
Positive Sequence Voltage%Read
Negative Sequence Voltage%Read
Earth Fault Angle Theta°Read
Phase Angle Phi 4°Read
Phase Angle Phi 8°Read
Phase Angle Phi 12°Read
Current Loop OutputmARead
Input INVRead
Self-Test LevelRead
Oscillography Recorder StateRead
Faults StoredRead
Settings CommandWrite
Reset CommandWrite
Test CommandWrite
Restart CommandWrite
Recorded Data Default CommandWrite
Operating ModeRead and write
Nominal VoltagekVRead and write
Nominal FrequencyHzRead and write
LED Reset EnableRead and write
67N1 EnableRead and write
67N2 EnableRead and write
67N Voltage SelectionRead and write
67N Voltage Threshold%Read and write
67N Residual Current ThresholdARead and write
67N1 Operating Time ModeRead and write
67N1 Extended Operating TimemsRead and write
67N2 Operating Time ModeRead and write
67N2 Extended Operating TimemsRead and write
51 EnableRead and write
51 ThresholdARead and write
51 Operating Time ModeRead and write
51 Extended Operating TimemsRead and write
51N EnableRead and write
51N ThresholdARead and write
51N Operating Time ModeRead and write
51N Extended Operating TimemsRead and write
59 Vo EnableRead and write
59 Vo Threshold%Read and write
59 Vo Operating TimemsRead and write
59 Vi EnableRead and write
59 Vi Threshold%Read and write
59 Vi Operating TimemsRead and write
27 Vd EnableRead and write
27 Vd Threshold%Read and write
27 Vd Operating TimemsRead and write
59 Vss EnableRead and write
59 Vss Threshold%Read and write
59 Vss Operating TimesRead and write
Voltage Monitor Pulse TimemsRead and write
Voltage Monitor Delay TimemsRead and write
Endesa T1 TimemsRead and write
Endesa T2 TimesRead and write
Endesa T3 TimeminRead and write
Relay 51 Normal StateRead and write
Relay 59 Normal StateRead and write
Relay 67 Normal StateRead and write
Current Loop ModeRead and write
Current Loop Full Scale MonoARead and write
Current Loop Full Scale BiARead and write
Theta Correction°Read and write
V4 Gain CalibrationRead and write
V4 Phase Calibration°Read and write
V8 Gain CalibrationRead and write
V8 Phase Calibration°Read and write
V12 Gain CalibrationRead and write
V12 Phase Calibration°Read and write
I4 Gain CalibrationRead and write
I4 Phase Calibration°Read and write
I8 Gain CalibrationRead and write
I8 Phase Calibration°Read and write
I12 Gain CalibrationRead and write
I12 Phase Calibration°Read and write
Fault Record SelectRead and write
Event Record SelectRead and write
Oscillography Pre-TriggerRead
Selected Fault NumberRead
Events StoredRead
Selected Event NumberRead
Oscillography Records StoredRead
Clock YearRead
Device IdentificationRead
Product CodeRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the phase voltages and currents of each substation on a dashboard and keep a year of history per value.
  • Send an e-mail or webhook alert when the residual voltage or current rises above a threshold.
  • Follow the number of stored faults to see how often a line sees short circuits or earth faults.
  • Check the earth fault and overcurrent thresholds remotely and adjust them during commissioning.
  • Get an alert when a phase voltage drops, for example after a line interruption.

Installation

  1. Connect the RS232 port of the SME-O through an RS232 to RS485 converter to the RS485 port of the ModbusCloud Gateway, and terminate the RS485 bus at both ends with 120 Ω.

  2. Check the Modbus address of the SME-O, for example with ThyVisor; the port works at 9600 baud without parity.

  3. In ModbusCloud, add a Modbus device on the RS485 port of the Gateway with that address, 9600 baud, 8 data bits, no parity and 1 stop bit.

  4. Import the Thytronic SMEO template and check that the phase voltages and currents come in.

  5. Compare the voltages with the rated voltage set on the device and the currents with the line load.

Things to watch for

The Gateway gets no answer from the SME-O. What should I check?

The SME-O has an RS232 port, so it needs an RS232 to RS485 converter between the device and the Gateway. Check the converter wiring and power, the Modbus address of the device, 9600 baud and no parity in ModbusCloud, and that A and B on the RS485 side are not swapped.

Why are the voltages shown in percent?

The SME-O reports the phase, residual and sequence voltages as a percentage of the rated voltage in Nominal Voltage, and the currents in amps. If the values look off, check Nominal Voltage, Nominal Frequency and the gain and phase calibration of the sensor inputs.

I wrote a new threshold, but it is gone after a restart. Why?

The SME-O keeps changed settings in temporary memory until it receives the store command. After writing new values, write Store to the Settings Command register, or Clear to discard the changes. Read a setting first before you write it, so you know the current value.

Some values stay empty while the voltages come in. Is that normal?

The clock, the identification and the fault and event records are part of larger messages that the device may only send as a whole. The template fits SME-O devices with identification code 111; earlier versions place the measurements at other addresses.

Can a test command reach the control centre?

Yes. The test command switches output relay 51, 67 or 59 or drives the current loop to 20 mA, and the remote control unit sees that as a real signal. Warn the control centre first and end the test with Test off.

Want to see how it works?