Thytronic Thytronic NC020 Modbus RTU template

Thytronic NC020

Protection relay for capacitor banks and harmonic filters with unbalance, peak overvoltage and overcurrent protection.

The Thytronic NC020 is a protection relay for capacitor banks and harmonic filters that guards against overcurrent, earth faults, unbalance from failed capacitor elements and capacitor peak overvoltage. This Modbus RTU template reads the phase currents, unbalance current, capacitor peak voltages, breaker position, trip flags and counters, and lets you change thresholds and send store, reset and compensation commands from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
153, read and write
Key readings
Phase currents · RMS phase currents · Unbalance current · Capacitor peak voltages · Breaker position · Trip flags · Start and trip counters · Remaining discharge time
Available commands
Protection thresholds · Time curves and operate times · Unbalance compensation · Discharge time · Breaker open and close · Store, reset and test commands
Compatible models
NC020
Last updated

Registers (153)

147 read, 90 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Phase Current L1ARead
Phase Current L2ARead
Phase Current L3ARead
Phase Current L1 RMSARead
Phase Current L2 RMSARead
Phase Current L3 RMSARead
Unbalance CurrentARead
Compensated Unbalance CurrentARead
Unbalance Current Angle°Read
Residual Current (Calculated)ARead
Capacitor Peak Voltage L1 (x Un)Read
Capacitor Peak Voltage L2 (x Un)Read
Capacitor Peak Voltage L3 (x Un)Read
Remaining Discharge TimesRead
Protection Trip FlagsRead
Breaker PositionRead
Input IN1 (52b)Read
Input IN2 (52a)Read
Input IN3 (Reset)Read
Self-Test LevelRead
Oscillography Recorder StateRead
Unbalance Compensation MagnitudeARead
Settings CommandWrite
Reset CommandWrite
Breaker CommandWrite
Unbalance Compensation CommandWrite
Test CommandWrite
Recorded Data Default CommandWrite
Modbus AddressRead and write
RS485 Baud RateRead and write
Measurement Reading ModeRead and write
Phase CT Primary CurrentARead
Unbalance CT Primary CurrentARead
Fault Record SelectRead and write
Event Record SelectRead and write
I> Time CurveRead and write
I> Inverse Pickup (x In)Read and write
tI> Inverse Time SettingsRead and write
I> Definite Pickup (x In)Read and write
tI> Definite Operate TimesRead and write
tI> Reset TimesRead and write
I> Cold Load ModeRead and write
I> Cold Load TimesRead and write
I> Definite Cold Load Pickup (x In)Read and write
I> Inverse Cold Load Pickup (x In)Read and write
I>> Time CurveRead and write
I>> Inverse Pickup (x In)Read and write
tI>> Inverse Time SettingsRead and write
I>> Definite Pickup (x In)Read and write
tI>> Definite Operate TimesRead and write
tI>> Reset TimesRead and write
I>> Cold Load ModeRead and write
I>> Cold Load TimesRead and write
I>> Definite Cold Load Pickup (x In)Read and write
I>> Inverse Cold Load Pickup (x In)Read and write
I>>> Definite Pickup (x In)Read and write
tI>>> Definite Operate TimesRead and write
tI>>> Reset TimesRead and write
I>>> Cold Load ModeRead and write
I>>> Cold Load TimesRead and write
I>>> Definite Cold Load Pickup (x In)Read and write
IE> Pickup (x In)Read and write
tIE> Operate TimesRead and write
tIE> Reset TimesRead and write
IE> Cold Load ModeRead and write
IE> Cold Load TimesRead and write
IE> Cold Load Pickup (x In)Read and write
IE>> Pickup (x In)Read and write
tIE>> Operate TimesRead and write
tIE>> Reset TimesRead and write
IE>> Cold Load ModeRead and write
IE>> Cold Load TimesRead and write
IE>> Cold Load Pickup (x In)Read and write
IN>AL Pickup (x INn)Read and write
tIN>AL Operate TimesRead and write
IN>AL Cold Load ModeRead and write
IN>AL Cold Load TimesRead and write
IN>AL Cold Load Pickup (x INn)Read and write
IN> Pickup (x INn)Read and write
tIN> Operate TimesRead and write
IN> Cold Load ModeRead and write
IN> Cold Load TimesRead and write
IN> Cold Load Pickup (x INn)Read and write
IN>> Pickup (x INn)Read and write
tIN>> Operate TimesRead and write
IN>> Cold Load ModeRead and write
IN>> Cold Load TimesRead and write
IN>> Cold Load Pickup (x INn)Read and write
U> Peak Voltage Pickup (x Un)Read and write
tU> Operate TimesRead and write
tU> Reset TimesRead and write
U> Cold Load ModeRead and write
U> Cold Load TimesRead and write
U> Cold Load Pickup (x Un)Read and write
U>> Peak Voltage Pickup (x Un)Read and write
tU>> Operate TimesRead and write
tU>> Reset TimesRead and write
U>> Cold Load ModeRead and write
U>> Cold Load TimesRead and write
U>> Cold Load Pickup (x Un)Read and write
U>>> Peak Voltage Pickup (x Un)Read and write
tU>>> Operate TimesRead and write
tU>>> Reset TimesRead and write
U>>> Cold Load ModeRead and write
U>>> Cold Load TimesRead and write
U>>> Cold Load Pickup (x Un)Read and write
I<< Phase LogicRead and write
I<< Pickup (x In)Read and write
tI<< Operate TimesRead and write
Discharge TimesRead and write
Discharge Start By UndercurrentRead and write
Breaker Failure TriggersRead and write
Breaker Failure TimesRead and write
Breaker Contact CheckRead and write
Unbalance Compensation Magnitude SettingARead
Relay K1 FunctionsRead
Relay K2 FunctionsRead
Relay K3 FunctionsRead
Relay K4 FunctionsRead
Enable TX DelaymsRead
Oscillography Pre-TriggerRead
Start Count I>Read
Start Count I>>Read
Start Count I>>>Read
Start Count IE>Read
Start Count IE>>Read
Start Count IN>ALRead
Start Count IN>Read
Start Count IN>>Read
Start Count U>Read
Start Count U>>Read
Start Count U>>>Read
Start Count I<<Read
Trip Count I>Read
Trip Count I>>Read
Trip Count I>>>Read
Trip Count IE>Read
Trip Count IE>>Read
Trip Count IN>ALRead
Trip Count IN>Read
Trip Count IN>>Read
Trip Count U>Read
Trip Count U>>Read
Trip Count U>>>Read
Trip Count I<<Read
Faults StoredRead
Selected Fault NumberRead
Events StoredRead
Selected Event NumberRead
Oscillography Records StoredRead
Clock YearRead
Device IdentificationRead
Product CodeRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the phase currents, RMS currents and unbalance current of each bank on a dashboard and keep a year of history per value.
  • Set an alarm on the compensated unbalance current to see failing capacitor elements before the unbalance element trips.
  • Follow the capacitor peak voltages to see how harmonics load the bank over the day.
  • Send an e-mail or webhook alert as soon as the trip flags rise above zero.
  • Check thresholds and operate times remotely and adjust them during commissioning.

Installation

  1. Wire the rear RS485 port of the NC020 to the RS485 port of the ModbusCloud Gateway, A to A and B to B, and terminate the bus at both ends with 120 Ω.

  2. On the relay, open the Communication menu and note the address and baud rate (default 1 and 9600 baud).

  3. In ModbusCloud, add a Modbus device on the RS485 port of the Gateway with the same address, 9600 baud, 8 data bits, no parity and 1 stop bit.

  4. Import the Thytronic NC020 template and check that the phase currents and the unbalance current come in.

  5. Compare the currents with the relay display, and set the phase and unbalance CT primary currents on the relay if you read primary amps.

Things to watch for

The Gateway gets no answer from the NC020. What should I check?

Check that the address and baud rate on the relay match the device in ModbusCloud, that you use the rear RS485 port and not the front port, and that A and B are not swapped. Terminate the bus with 120 Ω at both ends.

The currents do not match the relay display. Why?

With the default Reading Direct the relay reports primary amps, calculated from the phase and unbalance CT primary currents set under Set, Base. With Reading Relative it reports multiples of the rated current. Check both settings on the relay and compare again.

I wrote a new threshold, but it is gone after a restart. Why?

The NC020 keeps changed settings in temporary memory until it receives the store command. After writing new values, write Store to the Settings Command register, or Clear to discard the changes. Read a setting first before you write it, so you know the current value.

Some values stay empty while the currents come in. Is that normal?

The clock, the identification, the stored compensation and the fault and event records are part of larger messages that the relay may only send as a whole. The template fits NC020 relays with identification code 103 or 109; code 108 uses a different layout.

Can a command from ModbusCloud switch the capacitor bank?

Yes. Breaker Command opens or closes the breaker through the output relays assigned to CB Open and CB Close, and a test with trip operates the output relays. Use them only during commissioning or maintenance. Store the unbalance compensation only on a healthy bank, because the present unbalance becomes the new reference.