Thytronic Thytronic SME71 Modbus RTU template

Thytronic SME71

Directional earth fault and short circuit detector for medium voltage secondary substations.

The Thytronic SME71 is a fault detector that signals short circuits and directional earth faults on medium voltage lines in secondary substations, in an indoor and an outdoor version. This Modbus RTU template reads the phase and residual voltages and currents, phase angles, fault records and self-test, and lets you change the earth fault and overcurrent settings and send store, reset and test commands from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
172, read and write
Key readings
Phase voltages · Phase currents · Residual voltage and current · Residual current angle · Current loop output · Fault and event records · Self-test status
Available commands
67N earth fault settings · 51 and 51N current thresholds · Voltage element thresholds · Store and reset commands · Relay and current loop test
Compatible models
SME71-C · SME71-O
Last updated

Registers (172)

161 read, 77 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Phase Voltage V4kVRead
Phase Voltage V8kVRead
Phase Voltage V12kVRead
Phase Voltage V4 (% Un)%Read
Phase Voltage V8 (% Un)%Read
Phase Voltage V12 (% Un)%Read
Residual VoltagekVRead
Residual Voltage (% Un)%Read
Negative Sequence VoltagekVRead
Positive Sequence Voltage (% Un)%Read
Negative Sequence Voltage (% Un)%Read
Phase Current I4ARead
Phase Current I8ARead
Phase Current I12ARead
Residual CurrentARead
Residual Current CompensatedARead
Residual Current Angle°Read
Angle V4-V8°Read
Angle V8-V12°Read
Angle V12-V4°Read
Angle V4-I4°Read
Angle V8-I8°Read
Angle V12-I12°Read
Current Loop OutputmARead
Direction Inversion InputRead
Self-Test LevelRead
Voltage Calibration Status (MA)Read
Voltage Calibration Status (RJ45)Read
Operating ModeRead
Login StatusRead
Failed Login AttemptsRead
Oscillography Recorder StateRead
59 Vss Auto-Calibration StateRead
Function ModeRead and write
Rated Phase VoltagekVRead and write
Rated FrequencyHzRead and write
Input I8/IO SelectionRead and write
Voltage InputRead and write
Current InputRead and write
Current Sensor Secondary VoltageRead and write
Current Sensor TypeRead and write
LED Reset EnableRead and write
67N Reference VoltageRead and write
67N Voltage Threshold%Read and write
67N Residual Current ThresholdARead and write
67N Residual Current CompensationRead and write
67N1 EnableRead and write
67N1 Operate Time ModeRead and write
67N1 Operate TimemsRead and write
67N2 EnableRead and write
67N2 Operate Time ModeRead and write
67N2 Operate TimemsRead and write
51 EnableRead and write
51 Phase Current ThresholdARead and write
51 Operate Time ModeRead and write
51 Operate TimemsRead and write
51N EnableRead and write
51N Residual Current ThresholdARead and write
51N Operate Time ModeRead and write
51N Operate TimemsRead and write
59 Vo EnableRead and write
59 Vo Threshold%Read and write
59 Vo Operate TimemsRead and write
59 Vi EnableRead and write
59 Vi Threshold%Read and write
59 Vi Operate TimemsRead and write
27 Vd EnableRead and write
27 Vd Threshold%Read and write
27 Vd Operate TimemsRead and write
59 Vss EnableRead and write
59 Vss Threshold%Read and write
59 Vss Operate TimesRead and write
59 Vss Auto-CalibrationRead and write
Relay 51 Normal StateRead and write
Relay 59 Normal StateRead and write
Relay 67 Normal StateRead and write
Endesa Timer T1msRead and write
Endesa Timer T2sRead and write
Endesa Timer T3minRead and write
Voltage Monitor Pulse TimemsRead and write
Voltage Monitor Delay TimemsRead and write
Current Loop ModeRead and write
Current Loop Range (Monodirectional)ARead and write
Current Loop Range (Bidirectional)ARead and write
Fault Mask TimemsRead and write
Intermittent Fault Threshold%Read and write
Intermittent Fault Input DelaymsRead and write
Intermittent Fault Output DelaymsRead and write
Virtual DIP SwitchRead and write
Theta Correction MA Rogowski°Read and write
Theta Correction MA Direct°Read and write
Theta Correction RJ45 Rogowski°Read and write
Theta Correction RJ45 Direct°Read and write
Current Calibration InputRead and write
Max Offset StandardRead and write
Max Offset AmplifiedRead and write
Fault Record SelectRead and write
Event Record SelectRead and write
Settings CommandWrite
Reset CommandWrite
Test CommandWrite
Recorded Data Default CommandWrite
Calibration CommandWrite
Operating Mode CommandWrite
Device Restart CommandWrite
Login CommandWrite
Logout CommandWrite
Password Confirm CommandWrite
Password Reset CommandWrite
Set Clock YearRead
Oscillography Pre-TriggerRead
Access User 1Read
Access Password 1Read
Phase Voltage V4 Direct (Test)kVRead
Phase Voltage V8 Direct (Test)kVRead
Phase Voltage V12 Direct (Test)kVRead
Residual Voltage Direct (Test)kVRead
Negative Sequence Voltage Direct (Test)kVRead
Residual Current IO_D (Test)ARead
Residual Current IO_A (Test)ARead
Calibration Angle V4-I4 (Test)°Read
Calibration Angle V4-I8 (Test)°Read
Calibration Angle V4-I12 (Test)°Read
Angle V4-IO_A (Test)°Read
Voltage Calibration Result (MA)Read
Calibration Rated Voltage (MA)kVRead
Calibration Gain V4 (MA)Read
Calibration Gain V8 (MA)Read
Calibration Gain V12 (MA)Read
Calibration Angle V4 (MA)°Read
Calibration Angle V8 (MA)°Read
Calibration Angle V12 (MA)°Read
Voltage Calibration Aux State (MA)Read
Voltage Calibration Result (RJ45)Read
Compensation Gain V4 (RJ45)Read
Compensation Gain V8 (RJ45)Read
Compensation Gain V12 (RJ45)Read
Compensation Angle V4 (RJ45)°Read
Compensation Angle V8 (RJ45)°Read
Compensation Angle V12 (RJ45)°Read
Calibration Gain V4 (RJ45)Read
Calibration Gain V8 (RJ45)Read
Calibration Gain V12 (RJ45)Read
Calibration Angle V4 (RJ45)°Read
Calibration Angle V8 (RJ45)°Read
Calibration Angle V12 (RJ45)°Read
Voltage Compensation Aux State (RJ45)Read
Sensor Voltage Calibration ResultRead
Sensor Voltage Calibration StateRead
Current Calibration ResultRead
Current Calibration StateRead
RJ45 Voltage Swap 4-12 (App)Read
RJ45 Voltage Swap 4-12 (Smp)Read
RJ45 Current Swap 4-12 (App)Read
RJ45 Current Swap 4-12 (Smp)Read
Faults StoredRead
Selected Fault NumberRead
Events StoredRead
Selected Event NumberRead
Oscillography Records StoredRead
Clock YearRead
Device IdentificationRead
Product CodeRead
Serial Number SettingRead and write
Debug Value 1Read
Debug Value 2Read
Debug Value 3Read
Debug Value 4Read
Debug Value 5Read
Debug Value 6Read
Debug Value 7Read
Debug Value 8Read

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the phase voltages, phase currents and residual values of each substation on a dashboard with a year of history.
  • Get an e-mail or webhook alert when the number of stored faults changes or the self-test level rises above zero.
  • Follow the residual voltage and current over time to see how the earth fault level of a line develops.
  • Check the 67N and overcurrent settings remotely and adjust them during commissioning.
  • Watch the voltage on the three phases to see when a line section goes dead and when it comes back.

Installation

  1. Connect the RS232 port of the SME71 to an RS232 to RS485 converter and wire A and B of the converter to the RS485 port of the ModbusCloud Gateway. Terminate the bus at both ends with 120 Ω.

  2. Look up in ThyVisor which Modbus address the SME71 answers on; the port runs at 9600 baud without parity.

  3. In ModbusCloud, add a Modbus device on the RS485 port of the Gateway with that address, 9600 baud, 8 data bits, no parity and 1 stop bit.

  4. Import the Thytronic SME71 template and check that the phase voltages and the self-test level come in.

  5. Compare the voltages and currents with ThyVisor, and set the rated phase voltage on the SME71 if the kV values look wrong.

Things to watch for

The Gateway gets no answer from the SME71. What should I check?

The SME71 talks Modbus RTU on its RS232 port at 9600 baud without parity, so it needs an RS232 to RS485 converter. Check the wiring and power of the converter, that A and B are not swapped, and that the address in ModbusCloud matches the address ThyVisor uses for the device.

The voltages or currents do not match what I expect. Why?

The voltages come both in percent of the rated voltage and in kV; the kV values depend on the rated phase voltage setting and on the voltage calibration. The currents depend on the sensor type, input and secondary voltage set on the device. Check those settings and the calibration status, and compare again with ThyVisor.

I wrote a new setting, but it is gone after a restart. Why?

The SME71 keeps changed settings in temporary memory until it receives the store command. After writing new values, write Store to the Settings Command register, or Clear to discard the changes. Read a setting first before you write it, so you know the current value.

Some values stay empty while the voltages come in. Is that normal?

The clock, the identification, the access codes and the fault, event and calibration records are part of larger messages that the device may only send as a whole. When one of those stays empty, the voltages, currents, angles and settings are still read as normal.

Can a test command signal a fault to the remote control unit?

Yes. The test command switches output relay 51, 67 or 59 or drives the current loop to 20 mA, and the remote control unit sees that as a real signal. Only use it during commissioning or maintenance, after informing whoever operates the remote control system, and end the test with Test off.

Want to see how it works?