Wilo IL-E / DL-E

Glanded pump with speed control: differential pressure, flow, power, status and error codes.

The Wilo IL-E and DL-E are electronically controlled glanded pumps, as are the IP-E, DP-E and BL-E, that circulate water in heating, cooling and industrial systems of larger buildings. This Modbus RTU template reads differential pressure, flow, speed, power, energy and error codes, and lets you switch the pump and set its control mode, setpoint and PID parameters from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
65, read and write
Brand
Wilo
Key readings
Differential pressure · Flow · Speed · Power input · Electrical current · Energy consumption · Error code
Available commands
Pump on and off · Control mode · Setpoint · Preset values · PID parameters
Compatible models
IL-E · DL-E · IP-E · DP-E · BL-E
Last updated

Registers (65)

65 read, 17 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
PressureRead1FC04uint16
Flowm³/hRead2FC04uint16
SpeedrpmRead7FC04uint16
Power InputWRead4FC04uint16
Electrical CurrentARead6FC04uint16
Energy ConsumptionkWhRead
Operation TimehRead
Operating Hours DPhRead
Duty Point Actual%Read
Control Function ActualRead
Setpoint Signal SourceRead and write
Operation StatusRead
Pump StatusRead
State DiagnosticsRead
Error TypeRead
Error MessageRead
Service MessageRead
Warning/Error CodeRead
Effective Pump CommandRead
Supported ErrorsRead
Supported Service MessagesRead
Pump CommandRead and write
Duty Point Setpoint%Read and write
Control FunctionRead and write
Bus Command TimerRead and write
Bus Command Timer TimeoutsRead and write
Duty Point Preset%Read and write
Control Function PresetRead and write
Pump Command PresetRead and write
Setpoint Source PresetRead and write
PID KpRead and write
PID TisRead and write
PID TdsRead and write
Temperature Mode TminKRead and write
Temperature Mode TmaxKRead and write
Temperature Mode Pressure at TminRead and write
Temperature Mode Pressure at TmaxRead and write
Speed MaxrpmRead
Speed MinrpmRead
Pressure MaxRead
Pressure MinRead
Pressure Max VariableRead
Pressure Min VariableRead
Flow Maxm³/hRead
Flow Minm³/hRead
Power Input MaxWRead
Slave PressureRead
Slave Flowm³/hRead
Slave Energy ConsumptionkWhRead
Slave Power InputWRead
Slave Operation TimehRead
Slave Electrical CurrentARead
Slave SpeedrpmRead
Slave Error TypeRead
Slave Pump StatusRead
Slave Warning/Error CodeRead
Pump ModuleRead
Pump TypeRead
Pump Type CANRead
Slave Pump ModuleRead
Slave Pump TypeRead
Slave Pump Type CANRead
Heartbeat CountRead
Application VersionRead
Vendor IDRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show differential pressure, flow and power of the main heating and chilled water pumps on one dashboard.
  • Get an email when the error code is no longer 0 or the pump reports an overvoltage or blocked rotor.
  • Track energy use and running hours of duty and standby pump in the history to plan maintenance.
  • Change the differential pressure setpoint or switch to PID control remotely during commissioning.
  • Alert when the pump runs at its upper regulation limit and no longer reaches the setpoint.

Installation

  1. Fit the Wilo IF-Module Modbus in the pump and connect RS485 A and B to the ModbusCloud Gateway. Terminate the bus at both ends.

  2. In the pump menu set the Modbus address (5.2.3.0), the baud rate code 5 for 9600 (5.2.4.0) and the frame code 2 for 8N1 (5.2.5.0).

  3. In ModbusCloud, add a Modbus device (RTU) with address 1, 9600 baud, 8 data bits, no parity and 1 stop bit, then import this template.

  4. Check that Application Version shows a value such as 512 (firmware 2.00) and that pressure and power come in.

Things to watch for

The pump does not answer. What should I check?

Check that the IF-Module Modbus sits in the pump and that address, baud rate and frame code in the pump menu match the device in ModbusCloud. Swap A and B if nothing answers, and terminate the bus only at both ends. IL-E and DL-E pumps with a segment display do not support the IF module.

Why are some values 65535 or 32767?

Those are the error values of the pump: the value is not available at the moment, for example the slave registers on a single pump. A pressure of 65535 often means the differential pressure sensor is missing or faulty.

In which unit is the pressure?

The pump reports pressure in steps of 10 cm water column. After scaling the value is in cm H2O; divide by 100 for metres of head, or by about 1020 for bar.

What should I watch out for when I write to the pump?

With the factory setting the pump follows the bus only. Write the bus command timer first, then control mode, setpoint and pump command, and read the effective values back. Do not overwrite a building management system that also drives the pump, and keep in mind that writing must be enabled for the gateway.

Want to see how it works?

Electrician working in an open distribution board