Wilo Wilo Stratos GIGA2.0 Modbus RTU template

Wilo Stratos GIGA2.0

Inline circulation pump for heating, cooling and air conditioning with values, errors and control over Modbus RTU.

The Wilo Stratos GIGA2.0 is a high-efficiency inline pump that circulates water in heating, cooling and air conditioning systems of larger buildings. This Modbus RTU template reads pressure, flow, power, energy, speed, error codes and heat meter values, and lets you set the duty point, control mode and on and off command from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
124, read and write
Brand
Wilo
Key readings
Pressure · Flow · Power input · Energy consumption · Speed · Error code · Heating and cooling energy · Flow and return temperature
Available commands
Pump on and off · Duty point · Control mode · Setpoint source · PID controller settings · Flow limits
Compatible models
Stratos GIGA2.0-I · Stratos GIGA2.0-D
Last updated

Registers (124)

124 read, 26 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Duty Point Setpoint%Read and write1FC03 / FC06int16
Pump CommandRead and write40FC03 / FC06uint16
Control Mode SetpointRead and write42FC03 / FC06uint16
Bus Command TimerRead and write300FC03 / FC06uint16
Reference Temperature T1 SetpointKRead and write302FC03 / FC16float32
Reference Temperature T2 SetpointKRead and write
Sensor Signal InputRead and write
Bus Command Timer TimeoutsRead and write
Setpoint Source SettingRead and write
Duty Point Preset%Read and write
Control Mode PresetRead and write
Pump Command PresetRead and write
Setpoint Source PresetRead and write
PID Gain KpRead and write
PID Integral Time TisRead and write
PID Derivative Time TdsRead and write
Duty Point Aux%Read and write
Control Mode AuxRead and write
Pump Command AuxRead and write
Setpoint Source AuxRead and write
Parameter Set SelectionRead and write
Flow Limit Max Settingm³/hRead and write
Flow Limit Min Settingm³/hRead and write
Flow Limit Off Settingm³/hRead and write
Zero Flow Setpoint Reduction Setting%Read and write
Nominal Flow For Control Settingm³/hRead and write
PressureRead
Flowm³/hRead
Energy ConsumptionkWhRead
Power InputWRead
Operation TimehRead
SpeedrpmRead
Operating Hours Double PumphRead
Active Control ModeRead
Pump Module TypeRead
Pump Type PLRRead
Maximum SpeedrpmRead
Minimum SpeedrpmRead
Max Pressure Setpoint Dp-cRead
Min Pressure Setpoint Dp-cRead
Max Pressure Setpoint Dp-vRead
Min Pressure Setpoint Dp-vRead
Maximum Flowm³/hRead
Minimum Flowm³/hRead
Maximum Power InputWRead
Service MessageRead
Error TypeRead
Error Message BitsRead
Pump StatusRead
State DiagnosticsRead
Slave Pump Module TypeRead
Slave Pump Type PLRRead
Slave Error TypeRead
Slave Pump StatusRead
Duty Point%Read
Duty Point Active Max%Read
Duty Point Active Min%Read
Duty Point 100 Percent ValueRead
Duty Point Unit CodeRead
Active Setpoint SourceRead
Active Parameter SetRead
Maximum PressurebarRead
Duty Point Input Max%Read
Duty Point Input Min%Read
Duty Point Input 100 Percent ValueRead
Duty Point Input Unit CodeRead
Duty Point Aux Max%Read
Duty Point Aux Min%Read
Duty Point Aux 100 Percent ValueRead
Duty Point Aux Unit CodeRead
Duty Point Preset Max%Read
Duty Point Preset Min%Read
Duty Point Preset 100 Percent ValueRead
Duty Point Preset Unit CodeRead
Selected Duty Point%Read
Selected Duty Point Max%Read
Selected Duty Point Min%Read
Selected Duty Point 100 Percent ValueRead
Selected Duty Point Unit CodeRead
Selected Control ModeRead
Selected Pump CommandRead
Selected Setpoint SourceRead
Active Flow Limit Maxm³/hRead
Active Flow Limit Minm³/hRead
Active Flow Limit Offm³/hRead
Active Zero Flow Setpoint Reduction%Read
Active Nominal Flow For Controlm³/hRead
Heating PowerWRead
Cooling PowerWRead
Heating Energy ResettablekWhRead
Heating Energy Reset TimeRead
Cooling Energy ResettablekWhRead
Cooling Energy Reset TimeRead
Heating Energy TotalkWhRead
Cooling Energy TotalkWhRead
Flow TemperatureKRead
Return TemperatureKRead
Input VoltageVRead
Analog Input 1 ValueRead
Analog Input 2 ValueRead
Analog Input 1 Unit CodeRead
Analog Input 2 Unit CodeRead
Reference Temperature T1KRead
Reference Temperature T2KRead
Analog Input 3 ValueRead
Analog Input 4 ValueRead
Analog Input 3 Unit CodeRead
Analog Input 4 Unit CodeRead
Sensor SignalRead
Duty Point Output%Read
Active Pump CommandRead
Pump Command OutputRead
Operation StatusRead
Heartbeat CountRead
System TimesRead
Bus Command Timer RemainingsRead
CIF Firmware VersionRead
Vendor IDRead
Software Build IDRead
Pump Type CANRead
Slave Pump Type CANRead
User Trouble CodeRead
Error CodeRead
Slave Error CodeRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Get an alert when the error code is not 0 and see the Wilo text, such as dry running or a blocked rotor, before you go on site.
  • Log power input and energy consumption per pump to find pumps that run at high load at night.
  • Compare flow and pressure with the design point to check whether a heating or cooling circuit is balanced.
  • Report heating and cooling energy per circuit from the heat meter values on a dashboard.
  • Change the duty point or switch the pump off remotely from ModbusCloud, for example outside office hours.

Installation

  1. Fit the CIF-Module Modbus RTU in the pump and connect RS485 A and B to the ModbusCloud Gateway; switch on the termination at the end of the line.

  2. In the pump menu set the Modbus address, the baud rate and the frame, for example address 1, 9600 baud and 8N1.

  3. In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings, then import this template.

  4. Check that power input and speed show plausible values while the pump runs; if nothing answers, check address, baud rate and A and B.

  5. Before you write a duty point or command, read the current values so you know the starting point.

Things to watch for

The pump does not answer on the bus. What should I check?

The CIF module uses the address, baud rate and frame set in the pump menu; there is no fixed default. Compare them with the device in ModbusCloud, for example 1, 9600 baud and 8N1. Swap A and B if nothing answers, check the termination at both ends of the line and make sure there is only one master on the bus.

Some registers give an error or no value. Why?

Duty point, heat meter values, temperatures, voltage and the auxiliary parameter set need a recent CIF module firmware. Read the CIF firmware version: the main version is in the highest byte. With an older module only the basic values such as pressure, flow, power and the error code are available.

Why does the temperature show 330 instead of 57?

The pump reports flow and return temperature in kelvin. A value of 330.0 K is 56.85 °C; subtract 273.15 to get degrees Celsius.

Pressure looks 10 times too high. Is that right?

The pump reports pressure in cm of water column. The template applies the factor 10, so 500 means 500 cm, about 0.49 bar. A raw value of 65535 means the pressure is not available.

I write a duty point but the pump does not follow it. What is wrong?

The pump only follows the bus when the setpoint source is the CIF module and no local override or external off input is active. The pump command also needs bit 3 set and bits 6 and 7 cleared when you write it. Read the active control mode, setpoint source and pump status first, and change one value at a time.

Want to see how it works?

Electrician working in an open distribution board