Wilo Stratos
Circulator pump: differential pressure, flow, power, fluid temperature and error codes.
The Wilo Stratos is a high-efficiency wet rotor circulator that moves water through heating, cooling and air conditioning systems in buildings. This Modbus RTU template reads differential pressure, flow, speed, power, fluid temperature, energy and error codes, and lets you switch the pump and set its control mode and setpoint from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 64, read and write
- Brand
- Wilo
- Key readings
- Differential pressure · Flow · Speed · Power input · Fluid temperature · Energy consumption · Error code
- Available commands
- Pump on and off · Control mode · Setpoint · Preset values · Temperature mode limits
- Compatible models
- Stratos · Stratos-D · Stratos-Z
- Last updated
Registers (64)
64 read, 16 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Pressure | Read | 1 | FC04 | uint16 | |
| Flow | m³/h | Read | 2 | FC04 | uint16 |
| Speed | rpm | Read | 7 | FC04 | uint16 |
| Power Input | W | Read | 4 | FC04 | uint16 |
| Electrical Current | A | Read | 6 | FC04 | uint16 |
| Fluid Temperature | K | Read | |||
| Energy Consumption | kWh | Read | |||
| Operation Time | h | Read | |||
| Operating Hours DP | h | Read | |||
| Duty Point Actual | % | Read | |||
| Control Function Actual | Read | ||||
| Setpoint Signal Source | Read and write | ||||
| Operation Status | Read | ||||
| Pump Status | Read | ||||
| State Diagnostics | Read | ||||
| Error Type | Read | ||||
| Error Message | Read | ||||
| Service Message | Read | ||||
| Warning/Error Code | Read | ||||
| Effective Pump Command | Read | ||||
| Supported Errors | Read | ||||
| Supported Service Messages | Read | ||||
| Pump Command | Read and write | ||||
| Duty Point Setpoint | % | Read and write | |||
| Control Function | Read and write | ||||
| Bus Command Timer | Read and write | ||||
| Bus Command Timer Timeout | s | Read and write | |||
| Duty Point Preset | % | Read and write | |||
| Control Function Preset | Read and write | ||||
| Pump Command Preset | Read and write | ||||
| Setpoint Source Preset | Read and write | ||||
| PID Ti | s | Read and write | |||
| PID Td | s | Read and write | |||
| Temperature Mode Tmin | K | Read and write | |||
| Temperature Mode Tmax | K | Read and write | |||
| Temperature Mode Pressure at Tmin | Read and write | ||||
| Temperature Mode Pressure at Tmax | Read and write | ||||
| Speed Max | rpm | Read | |||
| Speed Min | rpm | Read | |||
| Pressure Max | Read | ||||
| Pressure Min | Read | ||||
| Pressure Max Variable | Read | ||||
| Pressure Min Variable | Read | ||||
| Flow Max | m³/h | Read | |||
| Power Input Max | W | Read | |||
| Slave Pressure | Read | ||||
| Slave Flow | m³/h | Read | |||
| Slave Energy Consumption | kWh | Read | |||
| Slave Power Input | W | Read | |||
| Slave Operation Time | h | Read | |||
| Slave Electrical Current | A | Read | |||
| Slave Speed | rpm | Read | |||
| Slave Error Type | Read | ||||
| Slave Pump Status | Read | ||||
| Slave Warning/Error Code | Read | ||||
| Pump Module | Read | ||||
| Pump Type | Read | ||||
| Pump Type CAN | Read | ||||
| Slave Pump Module | Read | ||||
| Slave Pump Type | Read | ||||
| Slave Pump Type CAN | Read | ||||
| Heartbeat Count | Read | ||||
| Application Version | Read | ||||
| Vendor ID | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show differential pressure, flow and power of every circulator in a building on one dashboard.
- Get an email when the error code is no longer 0 or the pump reports a blocked rotor or dry running.
- Track energy use and running hours per pump in the history and compare heating seasons.
- Change the differential pressure setpoint or control mode remotely while balancing a heating circuit.
- Watch the fluid temperature of a chilled water circuit and alert above a threshold.
Installation
Fit the Wilo IF-Module Modbus Stratos in the pump and connect RS485 A and B to the ModbusCloud Gateway. Terminate the bus at both ends.
In the pump menu set the Modbus address, the baud rate code 5 for 9600 and the frame code 2 for 8N1.
In ModbusCloud, add a Modbus device (RTU) with address 1, 9600 baud, 8 data bits, no parity and 1 stop bit, then import this template.
Check that Application Version shows a value such as 512 (firmware 2.00) and that pressure and power come in.
Things to watch for
The pump does not answer. What should I check?
Check that the IF-Module Modbus Stratos sits in the pump and that address, baud rate and frame code in the pump menu match the device in ModbusCloud. Swap A and B if nothing answers, and terminate the bus only at both ends. If Application Version is not found, the master may use an address offset of one.
Why is the fluid temperature about 273 degrees too high?
The pump reports temperatures in kelvin. Subtract 273.15 for °C, or set your dashboard and alarm thresholds in kelvin.
In which unit is the pressure?
The pump reports pressure in steps of 10 cm water column. After scaling the value is in cm H2O; divide by 100 for metres of head, or by about 1020 for bar.
What should I watch out for when I write to the pump?
With the factory setting the pump follows the bus only. Write the bus command timer first, then control mode, setpoint and pump command, and read the effective values back. Do not overwrite a building management system that also drives the pump, and keep in mind that writing must be enabled for the gateway.