ZCS Azzurro HYD 10000 ZSS/HYD 20000 ZSS - Three-Phase Hybrid Inverter - Modbus

Monitors Azzurro three-phase hybrid inverters via stick logger Modbus TCP.

This template reads PV generation, battery status, grid exchange, and load consumption data from Azzurro HYD 10000 ZSS and HYD 20000 ZSS three-phase hybrid inverters. Communication uses Modbus TCP via the ZSM-ETH-EXT or ZSM-WIFI-EXT stick logger on port 8899. The template is read-only and does not include control registers.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
31, read only
Brand
Azzurro
Key readings
Battery SOC and temperature · PV1 and PV2 power and voltage · Active power output total · Grid energy purchase and selling · Battery charge and discharge totals · Load consumption today and total
Compatible models
HYD 10000 ZSS · HYD 20000 ZSS
Last updated

Registers (31)

31 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Battery_SOC%Read
PV1_PowerkWRead
PV2_PowerkWRead
Power_Bat1WRead
Battery_Temperature°CRead
ReactivePower_Output_TotalWRead
Inverter_StatusRead
PV1_VoltageVRead
PV2_VoltageVRead
PV_Generation_TodaykWRead
PV_Generation_TotalkWRead
ActivePower_Output_TotalWRead
ActivePower_PV_ExtRead
ActivePower_Load_SysRead
Energy_Purchase_TodaykWhRead
Energy_Selling_TodaykWhRead
ActivePower_PCC_TotalWhRead
ApparentPower_Output_TotalRead
ReactivePower_PCC_TotalRead
ApparentPower_PCC_TotalRead
Energy_Purchase_TotalkWhRead
Energy_Selling_TotalkWhRead
Bat_Charge_TotalkWhRead
Bat_Discharge_TotalkWhRead
Bat_Discharge_TodaykWhRead
Load_Consumption_TotalkWhRead
Load_Consumption_TodaykWhRead
Bat_Charge_TodaykWhRead
Active_Power_Load_TotalRead
ReactivePower_Load_TotalRead
ApparentPower_Load_TotalRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time PV production per string and total active power output on a cloud dashboard.
  • Track battery state of charge and temperature to verify correct charge and discharge cycling.
  • Log daily and cumulative grid energy purchase and selling to analyse self-consumption ratios.
  • Create an alert when battery SOC drops below a defined threshold during peak demand hours.
  • Compare load consumption trends over time to advise customers on energy usage optimisation.

Installation

  1. Install the ZSM-ETH-EXT or ZSM-WIFI-EXT stick logger on the Azzurro inverter and connect it to the local network.

  2. Verify that the stick logger has obtained an IP address and is reachable from the ModbusCloud Gateway.

  3. Connect the ModbusCloud Gateway to the same local network as the stick logger via its Ethernet port.

  4. Import the Azzurro HYD 10000 ZSS / HYD 20000 ZSS template in the ModbusCloud platform and set the target IP to the stick logger's address with TCP port 8899.

  5. Confirm that live register values appear on the ModbusCloud dashboard, checking PV power, battery SOC, and grid energy readings for plausibility.

Things to watch for

I cannot reach the stick logger on port 8899. What should I check?

Ensure the stick logger is powered and connected to the local network. Verify its IP address in your router's DHCP table. Check that no firewall rules block TCP port 8899 between the ModbusCloud gateway and the stick logger.

PV power values seem too low compared to actual production. Why?

PV power registers are reported in kilowatts, not watts. Confirm that the template scaling is applied correctly. If you see values like 5.2, that represents 5.2 kW.

Energy total registers show incorrect or very large numbers. What is wrong?

Energy totals use uint32 format spanning two consecutive Modbus addresses. Make sure the template is imported without manual register modifications, as splitting or reordering these addresses will produce wrong values.

Can I use this template to control or configure the inverter remotely?

No. This template is read-only and does not include write registers. All inverter configuration must be done through the manufacturer's own tools or the inverter display.

More TCP templates

Want to see how it works?

Electrician working in an open distribution board