Zehnder Zehnder ComfoConnect Pro Modbus TCP template

Zehnder ComfoConnect Pro

Connects Zehnder ventilation units to smart home systems via Modbus RTU/TCP

The Zehnder ComfoConnect Pro is a gateway that bridges Zehnder ComfoNet ventilation devices (such as the ComfoAir Q) to Modbus TCP. This template reads temperatures, humidity, fan airflow, filter status, and active errors, and allows control of ventilation modes, fan speeds, timers, and temperature setpoints.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
34, read and write
Brand
Zehnder
Key readings
Supply/extract/outdoor/exhaust temperatures · Room/supply/extract/outdoor/exhaust humidity · Supply fan airflow volume · Filter status (days remaining) · Active errors 1 to 4 · Connection status
Available commands
Fan speed level (1/2/3/away) · Mode auto/manual · Party timer · Temperature profile mode and setpoint
Compatible models
Zehnder ComfoAir Q · Zehnder ComfoAir Flex · Zehnder ComfoSwitch C · Zehnder ComfoSense C · Zehnder CO2 Sensor C · Zehnder ComfoConnect Pro
Last updated

Registers (34)

34 read, 14 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
FehlerprotokollRead and write
VerbindungsstatusRead and write
Aktiver Fehler 1Read and write
Temperatur Profil (S)Read
Temperatur Profil Modus (S)Read and write
Raumluft Temperatur°CRead
Abluft Temperatur°CRead
Aussenluft Temperatur°CRead
Zuluft Temperatur°CRead
Fortluft Temperatur°CRead
Abluft Feuchte%Read
Zuluft Feuchte%Read
Fortluft Feuchte%Read
Aussenluft Feuchte%Read
Raumluft Feuchte%Read
Aktiver Fehler 2Read
Aktiver Fehler 3Read and write
Aktiver Fehler 4Read and write
Stufe (S)Read
FilterstatusdaysRead
Filter tauschenRead and write
Zuluft Ventilator Volumenm³Read
ComfoClime (S)Read and write
StandbyRead and write
Abwesenheitsfunktion (S)Read and write
Modus (S) Auto / ManuellRead and write
Fehler zurücksetzen (S)Read
Stufe (S) 1Read and write
Stufe (S) 2Read
Stufe (S) 3Read and write
Stufe (S) AbwesendRead
Temperatur Profil Festwert (S)°CRead
Party timer (S)Read and write
Party timer sec (S)sRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor supply, extract, outdoor, and exhaust temperatures on a live cloud dashboard for each ventilation installation.
  • Create an alert when the filter days remaining drops below a threshold so you can schedule maintenance proactively.
  • Track indoor humidity trends over time and correlate them with ventilation fan speed and mode changes.
  • Remotely switch ventilation mode between auto and manual or adjust fan speed without an on-site visit.
  • Set up notifications for active error codes to detect faults in the Zehnder ComfoAir Q before customers report them.
  • Log airflow volume data to verify that the ventilation system delivers the designed air exchange rate.

Installation

  1. Connect the Zehnder ComfoConnect Pro to the ComfoNet bus of your Zehnder ventilation unit (e.g., ComfoAir Q) and to the local network via LAN or WiFi.

  2. Run the commissioning wizard on the ComfoConnect Pro, then reboot the gateway via its web interface to ensure Modbus registers return valid data.

  3. Note the IP address assigned to the ComfoConnect Pro and confirm it is reachable from the ModbusCloud Gateway on the same network.

  4. Connect and power the ModbusCloud gateway, then register it on the ModbusCloud platform using your installer account.

  5. Import the Zehnder ComfoConnect Pro template from the ModbusCloud template library and assign it to the gateway, entering the correct IP address and Modbus TCP port.

  6. Verify that live readings (temperatures, humidity, fan status) appear on the ModbusCloud dashboard and confirm control registers respond as expected.

Things to watch for

All Modbus registers return zero or no data after initial setup. What is wrong?

After completing the commissioning wizard, you must reboot the ComfoConnect Pro gateway via its web interface. Without this reboot, Modbus data will not be served correctly.

Which firmware version is required on the ComfoConnect Pro?

The template was created and tested with firmware v1.0.4. If you are running an older version, update the gateway firmware through the web interface before importing the template.

Can I use Modbus RTU instead of Modbus TCP?

The ComfoConnect Pro supports both Modbus RTU and Modbus TCP. This template is configured for Modbus TCP. If you need RTU, you will need to adjust the connection settings and wiring accordingly.

Which Zehnder ventilation units are compatible with this template?

The template supports devices connected via the ComfoConnect Pro, including the ComfoAir Q, ComfoAir Flex, ComfoSwitch C, ComfoSense C, and CO2 Sensor C.