Daikin Daikin EKWHCTRL1 Modbus RTU template

Daikin EKWHCTRL1

Room controller for Daikin fan coils and Altherma HPC convectors: temperature, season and fan program.

The Daikin EKWHCTRL1 is a wall-mounted room control that sets the temperature, season and fan program of Daikin fan coils and Altherma HPC heat pump convectors. This Modbus RTU template reads air temperature, humidity, setpoint, status and alarms, and lets you write the setpoint, season, fan program and standby from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
36, read and write
Brand
Daikin
Key readings
Air temperature · Relative humidity · Actual setpoint · Operating status · Alarms · Hot water temperature
Available commands
Temperature setpoint · Season mode · Fan program · Standby · Setpoint limits · Fan speeds
Compatible models
EKWHCTRL1 · EKWHCTRL1A · EKWHCTRL0 · EKRTCTRL1 · Daikin Altherma HPC heat pump convector with electronic control · Daikin fan coil units with INN-FR-B32 board
Last updated

Registers (36)

36 read, 25 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Air Temperature°CRead0FC03int16
Control Air Temperature°CRead18FC03int16
Relative Humidity%Read20FC03uint16
Hot Water Temperature H2°CRead1FC03int16
Actual Setpoint°CRead8FC03int16
Fan Motor Speed SetpointRead
Output Relay StatusRead
Status FlagsRead
Alarm FlagsRead
ProgramRead and write
Temperature Setpoint°CRead and write
Season ModeRead and write
Web FlagsRead and write
Minimum Setpoint°CRead and write
Maximum Setpoint°CRead and write
Web Minimum Setpoint°CRead and write
Web Maximum Setpoint°CRead and write
Presence Setpoint OffsetKRead and write
Min Heating Water Temperature°CRead and write
Max Cooling Water Temperature°CRead and write
Fan Speed MVV5Read and write
Fan Speed MVV4Read and write
Fan Speed MVV3Read and write
Fan Speed MVV2Read and write
Fan Speed MVV1Read and write
Fan Speed MVVP1Read and write
Fan Speed MVVP2Read and write
Fan Speed MVVP3Read and write
Air Probe OffsetKRead and write
H2 Probe OffsetKRead and write
H4 Probe OffsetKRead and write
Maintenance IntervalhRead and write
Fan Operating HourshRead and write
Modbus AddressRead and write
Firmware ReleaseRead
Firmware IdentifierRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show the room temperature and setpoint of every fan coil in one ModbusCloud dashboard.
  • Send an email alert when the alarm flags are not 0, for example a fan motor fault or a dirty filter.
  • Switch fan coils to standby or change the setpoint remotely for an empty office or holiday home.
  • Change the season from heating to cooling for all units without visiting the building.
  • Keep a year of room temperature history to answer comfort complaints with real data.

Installation

  1. Connect A and B of the controller to the RS485 port of the ModbusCloud Gateway with shielded twisted pair, no star wiring, and a 120 ohm resistor at both ends of the bus.

  2. Give each controller its own address: in standby, hold AUTO for 5 seconds and set 2 to 255 with the arrow keys. Note which address belongs to which room.

  3. In ModbusCloud, add a Modbus device with the address of the controller, 9600 baud, 8 data bits, no parity and 1 stop bit, and import this template.

  4. Check that Air Temperature or Control Air Temperature shows the room temperature and that Alarm Flags reads 0.

Things to watch for

The controller does not answer at all. What should I check?

Check 9600 baud, no parity, 1 stop bit and the address set on the keypad. Swap A and B if needed and make sure the bus has no star branches and a 120 ohm resistor at both ends. The controller answers at most three registers per request; a master that asks for longer blocks gets no reply.

Air Temperature stays 0 but Control Air Temperature shows a value. Why?

Older and newer firmware put the room temperature at different addresses. The template has both. Keep the register that shows the real room temperature and hide the other one in your dashboard.

Several registers always read 0 on the wall control. Is that a fault?

No. Hot water temperature, motor speed, relay outputs and the fan speed steps only exist on fan coils with the INN-FR-B32 board. On a wall control without that board they stay 0 or give no answer.

How do I switch a fan coil on, off or to night mode?

All of this lives in the Program register. Bits 0 to 2 choose the fan program (0 auto, 1 silent, 2 night, 3 maximum), bit 4 locks the keypad and bit 7 puts the unit in standby. Read the register first and change only the bits you need, so the system flags in bits 8 to 15 stay as they are.

The setpoint I write is not accepted. What is wrong?

The setpoint must lie between Minimum Setpoint and Maximum Setpoint, or between the web limits when web flag 5 is set, and is written in tenths of a degree. Also check that web flags 1 or 6 do not block the unit.