Danfoss Danfoss AK-CC 350 Modbus RTU template

Danfoss AK-CC 350

Controls temperature, defrost and fans in refrigerated display cabinets and cold rooms.

The Danfoss AK-CC 350 is a case and cold room controller that regulates temperature, defrost and fans in refrigerated display cabinets and cold rooms. This Modbus RTU template reads all temperatures, the controller state and every alarm, and lets you change the setpoint, alarm limits and defrost settings from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 38400 baud
Registers
118, read and write
Brand
Danfoss
Key readings
Thermostat air temperature · S3 and S4 air temperature · S5 evaporator temperature · HACCP temperature · Controller state · Alarm flags
Available commands
Temperature setpoint · Main switch · Defrost start · Alarm limits · Defrost schedule
Compatible models
AK-CC 350 (084B4165)
Last updated

Registers (118)

118 read, 85 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Thermostat Air Temperature°CRead
S4 Air Temperature°CRead
S3 Air Temperature°CRead
S5 Temperature°CRead
Display Air Temperature°CRead
Alarm Air Temperature°CRead
Regulation Reference°CRead
HACCP Temperature°CRead
HACCP Peak Temperature°CRead
Controller StateRead
Defrost StateRead
DI1 StatusRead
DI2 StatusRead
Night ConditionRead
Controller ErrorRead
Controller Error AlarmRead
Clock Error AlarmRead
S3 Sensor ErrorRead
S4 Sensor ErrorRead
S5 Sensor ErrorRead
High Temperature AlarmRead
Low Temperature AlarmRead
HACCP AlarmRead
Door AlarmRead
DI1 AlarmRead
DI2 AlarmRead
Max Defrost Time AlarmRead
Max Hold Time AlarmRead
Case Cleaning AlarmRead
Standby Mode AlarmRead
Main SwitchRead and write
Temperature Setpoint°CRead and write
Defrost StartRead and write
Reset AlarmRead and write
Forced CoolingRead and write
Night SetbackRead and write
Thermostat DifferentialKRead and write
Max Setpoint Limit°CRead and write
Min Setpoint Limit°CRead and write
Display S4 Weighting%Read and write
Display Temperature AdjustmentKRead and write
Temperature UnitRead and write
S4 Sensor CorrectionKRead and write
S3 Sensor CorrectionKRead and write
Night Setback OffsetKRead and write
Thermostat S4 Weighting%Read and write
Reference Offset ActiveRead and write
Reference OffsetKRead and write
Compressor Min On TimeminRead and write
Compressor Min Off TimeminRead and write
Compressor Relay NC FunctionRead and write
External RelaysRead and write
Defrost MethodRead and write
Defrost Stop Temperature°CRead and write
Defrost IntervalhRead and write
Max Defrost DurationminRead and write
Defrost Start Delay At Power UpminRead and write
Drip Off TimeminRead and write
Fan Start Delay After DefrostminRead and write
Fan Start Temperature°CRead and write
Fan During DefrostRead and write
Defrost Stop SensorRead and write
Pump Down DelayminRead and write
Max Refrigeration Time Between DefrostshRead and write
Defrost On Demand S5 VariationKRead and write
Hold After DefrostRead and write
Max Hold Time After Coordinated DefrostminRead and write
Defrost 1 Start HourhRead and write
Defrost 1 Start MinuteminRead and write
Defrost 2 Start HourhRead and write
Defrost 2 Start MinuteminRead and write
Defrost 3 Start HourhRead and write
Defrost 3 Start MinuteminRead and write
Defrost 4 Start HourhRead and write
Defrost 4 Start MinuteminRead and write
Defrost 5 Start HourhRead and write
Defrost 5 Start MinuteminRead and write
Defrost 6 Start HourhRead and write
Defrost 6 Start MinuteminRead and write
Fan Stop At Compressor CutoutRead and write
Fan Stop DelayminRead and write
Fan Stop Temperature°CRead and write
Temperature Alarm DelayminRead and write
Door Alarm DelayminRead and write
Alarm Delay After DefrostminRead and write
High Alarm Limit°CRead and write
Low Alarm Limit°CRead and write
DI1 Alarm DelayminRead and write
DI2 Alarm DelayminRead and write
Alarm S4 Weighting%Read and write
HACCP Sensor SelectionRead and write
HACCP Alarm Limit°CRead and write
HACCP Alarm DelayminRead and write
HACCP S4 Weighting%Read and write
Output Delay At Start UpsRead and write
DI1 ConfigurationRead and write
Sensor TypeRead and write
DI2 ConfigurationRead and write
Case CleaningRead and write
Compressor RelayRead and write
Defrost RelayRead and write
Fan RelayRead and write
Alarm RelayRead and write
Light ConfigurationRead and write
Light Remote SwitchRead and write
Light RelayRead and write
Rail Heat On Time Day%Read and write
Rail Heat On Time Night%Read and write
Rail Heat PeriodminRead and write
Rail Heat RelayRead and write
Drain DelayminRead and write
Suction Line Valve RelayRead and write
Compressor 2 Cut In DelaysRead and write
Compressor 2 RelayRead and write
Heat Function Start OffsetKRead and write
Application ModeRead
Module Software VersionRead
Transceiver TypeRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show the thermostat air temperature of every cabinet in one dashboard and keep a year of history as evidence for food safety checks.
  • Send an email when the high or low temperature alarm flag goes to 1, or when a sensor error appears.
  • Alert when the HACCP temperature passes its limit, separately from the normal temperature alarm.
  • Check from the history whether defrosts start on schedule and how long the cabinet stays in each controller state.
  • Adjust the setpoint or alarm limits of a cold room remotely after a change in the stored product.

Installation

  1. Connect the Disp./MODBUS terminals A+ and B- of the controller to the RS485 port of the ModbusCloud Gateway, with a 120 ohm termination at the end of the bus.

  2. Set a unique network address in parameter o03 (1 to 240) on each controller.

  3. In ModbusCloud, add a Modbus device with that address, 38400 baud, 8 data bits, even parity and 1 stop bit, and import this template.

  4. Check that the thermostat air temperature and the controller state show plausible values.

  5. If nothing answers, try 19200 or 9600 baud and swap A+ and B- once.

Things to watch for

The controller does not answer at all. What should I check?

Check that o03 holds an address other than 0, that the wires go to the Disp./MODBUS terminals and not the LON RS485 terminals, and that A+ and B- are not swapped. Danfoss does not publish the serial settings for this controller; start at 38400 baud 8E1 and try 19200 and 9600 if it stays silent.

Why do I read 1200 on the S3 or S5 temperature?

Temperatures come in tenths, so the template shows 120.0. A fixed high value like this usually means the sensor is not connected or not used in the selected application. The matching sensor error flag tells you whether the controller sees a fault.

Writing a setting has no effect. Why?

Some settings, such as the defrost method and the input configuration, can only change while the main switch stops regulation (0). Relay registers only switch in manual service (main switch -1). Set the main switch back to 1 afterwards, otherwise the cabinet stops cooling.

Some registers return errors or zero. Is the template wrong?

The controller has ten applications and not every function exists in each one: light, rail heat, a second compressor and the suction line valve only appear in some. Application Mode shows which one is active, and registers for other applications can stay empty.