Danfoss Danfoss EKE 1C Modbus RTU template

Danfoss EKE 1C

Superheat controller for stepper motor expansion valves in refrigeration, air conditioning and heat pumps.

The Danfoss EKE 1C is a superheat controller that drives a stepper motor expansion valve on the evaporator of chillers, cold rooms, air conditioning and heat pumps. This Modbus RTU template reads superheat, valve opening degree, temperatures, pressures and alarms, and lets you write the main switch, setpoints and controller settings from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
249, read and write
Brand
Danfoss
Key readings
Actual superheat · Valve opening degree · Suction pipe temperature · Evaporating pressure · Condensing pressure · Operation status · Alarm status
Available commands
Main switch · Superheat setpoint · Temperature setpoint · Alarm limits · Manual opening degree
Compatible models
EKE 1C · EKE 1B
Last updated

Registers (249)

249 read, 210 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Actual SuperheatKRead
Actual SH ReferenceKRead
Actual Opening Degree%Read
S2 Suction Pipe Temperature°CRead
S3 Media Inlet Temperature°CRead
S4 Media Outlet Temperature°CRead
Pe Evaporator PressurebarRead
Te Saturated Evaporation Temperature°CRead
Pc Condenser PressurebarRead
Tc Saturated Condenser Temperature°CRead
Operation StatusRead
Number Of Active AlarmsRead
Alarm NotificationRead
Alarm StatusRead
Warning StatusRead
Error StatusRead
Alarm RelayRead
Liquid Line Solenoid ValveRead
Actual StepRead
Actual Temperature ReferenceKRead
Actual Battery VoltageVRead
Thermostat Cut-in TimeminRead
Thermostat Average Cut-in TimeminRead
Thermostat Average Cut-out TimeminRead
External Reference Signal VoltageVRead
External Reference Signal CurrentmARead
Actual External Reference Temperature OffsetKRead
Actual External Reference SH OffsetKRead
DI Main SwitchRead
DI Defrost StartRead
DI Preset Opening DegreeRead
DI HeatingRead
Average SuperheatKRead
Average Temperature°CRead
Actual External Reference Maximum Opening Degree%Read
DI Power Backup SignalRead
Power Backup StatusRead
Modbus HeatingRead and write
Modbus Preset Opening DegreeRead and write
Modbus Defrost StartRead and write
Modbus Main SwitchRead and write
Bus Shared PcbarRead and write
Bus Shared PebarRead and write
Bus Shared S2°CRead and write
Bus Shared S3°CRead and write
Bus Shared S4°CRead and write
Bus External ReferenceKRead and write
Valve Current PositionRead
Valve Target PositionRead
Service Number Of StepsRead and write
User Controls LEDsRead and write
Green LED PatternRead and write
Red LED PatternRead and write
Main SwitchRead and write
Operation ModeRead and write
Sensor SelectRead and write
Thermostatic ModeRead and write
Temperature Setpoint°CRead and write
Temperature DifferentialKRead and write
External Reference Offset MaxKRead and write
External Reference Offset MinKRead and write
S2 CorrectionKRead and write
S3 CorrectionKRead and write
S4 CorrectionKRead and write
Pe CorrectionbarRead and write
Pc CorrectionbarRead and write
Display UnitRead and write
Compressor Capacity%Read and write
RefrigerantRead and write
Refrigerant Factor A1Read and write
Refrigerant Factor A2Read and write
Refrigerant Factor A3Read and write
Refrigerant Min Temperature°CRead and write
Refrigerant Max Temperature°CRead and write
DI1 ConfigurationRead and write
DI2 ConfigurationRead and write
DI3 ConfigurationRead and write
DO1 ConfigurationRead and write
Pe Transmitter MinbarRead and write
Pe Transmitter MaxbarRead and write
Pc Transmitter MinbarRead and write
Pc Transmitter MaxbarRead and write
External Reference Configuration EKE 1CRead and write
LanguageRead and write
Password DailyRead and write
Manual Mode TimeoutsRead and write
Enter Service StateRead and write
Manual ModeRead and write
Manual Opening Degree%Read and write
Manual StepRead and write
Manual HomingRead and write
Manual Relay DO1Read and write
Apply DefaultsRead and write
MTR TnRead and write
MTR KpRead and write
Startup ModeRead and write
Startup TimesRead and write
Min Startup TimesRead and write
Startup Opening Degree%Read and write
SH Reference ModeRead and write
SH Fixed SetpointKRead and write
SH MaxKRead and write
SH MinKRead and write
SH TnsRead and write
SH Kp MinRead and write
SH KpRead and write
SH KpTeRead and write
SH Reference Delta Temperature Factor%Read and write
SH Close FunctionRead and write
SH Close SetpointKRead and write
SH Close Tn DivideRead and write
SH Close Kp FactorRead and write
Limit KpRead and write
Limit TnsRead and write
Min S4 ModeRead and write
Min S4 Setpoint°CRead and write
StabilityRead and write
T0 Variance FactorRead and write
MOP FunctionRead and write
MOP Setpoint°CRead and write
LOP FunctionRead and write
LOP Setpoint°CRead and write
LOP Priority ModeRead and write
LOP Max TimesRead and write
LOP Oscillation DetectionRead and write
High Condensing Temperature ProtectionRead and write
High Condensing Temperature Protection Setpoint°CRead and write
Compressor Speed Feed ForwardRead and write
Compressor Feed Forward Low Capacity Point%Read and write
Compressor Feed Forward SH Tn FactorRead and write
SH Control Sensor Error ActionRead and write
Thermostatic Sensor Error ActionRead and write
Fixed Opening Degree During Emergency Cooling%Read and write
Heat Startup TimesRead and write
Heat Min Startup TimesRead and write
Heat Startup Opening Degree%Read and write
Heat SH Fixed SetpointKRead and write
Heat SH MaxKRead and write
Heat SH MinKRead and write
Heat SH Reference Delta Temperature Factor%Read and write
Heat SH TnsRead and write
Heat SH Kp MinRead and write
Heat SH KpRead and write
Heat SH KpTeRead and write
Heat SH Close SetpointKRead and write
Heat Limit TnsRead and write
Heat Limit KpRead and write
Defrost Start TimesRead and write
Defrost Opening Degree%Read and write
Defrost End Closed TimesRead and write
Defrost End Opening Degree TimesRead and write
Maximum Opening Degree%Read and write
Average Opening Degree%Read and write
Estimated KpTeRead and write
Average Delta TemperatureRead and write
Low Min S4 DelaysRead and write
Low Min S4 BandKRead and write
Upper Temperature AlarmKRead and write
Lower Temperature AlarmKRead and write
Temperature Alarm DelayminRead and write
Battery AlarmRead and write
MOP Alarm DelaysRead and write
MOP Alarm DifferentialKRead and write
LOP Alarm DelaysRead and write
LOP Alarm DifferentialKRead and write
Condensing Temperature Alarm DelaysRead and write
Condensing Temperature Alarm DifferentialKRead and write
High SH Alarm DelaysRead and write
High SH Alarm DifferentialKRead and write
Low SH Alarm DelaysRead and write
Low SH Alarm DifferentialKRead and write
Lack Of Capacity Alarm DelayminRead and write
AI1 ConfigurationRead and write
AI4 Configuration EKE 1CRead and write
AI5 ConfigurationRead and write
S2 Sensor Configuration EKE 1CRead and write
S3 Sensor Configuration EKE 1CRead and write
S4 Sensor Configuration EKE 1CRead and write
Pe Transmitter Configuration EKE 1CRead and write
Pe Ratio Low%Read and write
Pe Ratio High%Read and write
Pe Voltage Low EKE 1CVRead and write
Pe Voltage High EKE 1CVRead and write
Pe Current LowmARead and write
Pe Current HighmARead and write
Pc Transmitter ConfigurationRead and write
Pc Ratio Low%Read and write
Pc Ratio High%Read and write
Pc Voltage LowVRead and write
Pc Voltage HighVRead and write
Pc Current LowmARead and write
Pc Current HighmARead and write
External Reference Current HighmARead and write
External Reference Current LowmARead and write
External Reference Voltage HighVRead and write
External Reference Voltage LowVRead and write
Driver Reference Configuration EKE 1CRead and write
Valve ConfigurationRead and write
Valve Motor TypeRead and write
Valve Drive CurrentmARead and write
Valve Step PositioningRead and write
Valve Total StepsRead and write
Valve SpeedRead and write
Valve Start Speed%Read and write
Valve Emergency Speed%Read and write
Valve Acceleration Current%Read and write
Valve Acceleration TimemsRead and write
Valve Holding Current%Read and write
Valve Step ModeRead and write
Valve Duty Cycle%Read and write
Minimum Opening Degree%Read and write
Valve Opening Degree During Stop%Read and write
Start Backlash%Read and write
Compensation Backlash%Read and write
Overdrive%Read and write
Overdrive Enable Opening Degree%Read and write
Overdrive Block TimeminRead and write
Valve Excitation Time After StopmsRead and write
Preset Opening Degree%Read and write
Valve Neutral Zone%Read and write
AI4 Lowpass BandwidthRead and write
AI4 Configuration EKE 1A 1BRead and write
S4 Sensor Configuration EKE 1BRead and write
S3 Sensor Configuration EKE 1BRead and write
S2 Sensor Configuration EKE 1BRead and write
S2 Sensor Configuration EKE 1ARead and write
Pe Transmitter Configuration EKE 1BRead and write
Pe Voltage High EKE 1A 1BVRead and write
Pe Voltage Low EKE 1A 1BVRead and write
External Reference Configuration EKE 1BRead and write
External Reference Configuration EKE 1ARead and write
Driver Reference Configuration EKE 1BRead and write
Controller AddressRead and write
CAN Bus Min Update IntervalsRead and write
Modbus Min Update IntervalsRead and write
Modbus BaudrateRead and write
Modbus ModeRead and write
Modbus MappingRead and write
CAN BaudrateRead and write
Signal Sharing PeRead and write
Signal Sharing PcRead and write
Signal Sharing S3Read and write
Login TimeoutminRead and write
Backlight TimeoutminRead and write
Password ServiceRead and write
Password CommissionRead and write
Display Contrast%Read and write
Display Brightness%Read and write
Opening Degree UnitRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show actual superheat, opening degree and suction temperature on one dashboard per evaporator.
  • Alert when the alarm status or error status turns on, or when superheat stays above a limit.
  • Keep a year of superheat and media temperature history to see how a cold room behaves through the seasons.
  • Switch the controller on or off remotely with the main switch register.
  • Adjust the temperature setpoint or the superheat limits from ModbusCloud without going to site.

Installation

  1. Wire the RS485 terminals D+ and D- of the EKE 1C to the RS485 port of the ModbusCloud Gateway, with a 120 ohm resistor at both ends of the bus.

  2. Check on the controller or with the MMIGRS2 display that the address is unique on the bus and that the bus runs at 19200 baud, 8E1.

  3. In ModbusCloud, add a Modbus device (RTU) with that address and these serial settings, and import this template.

  4. Confirm that actual superheat, S2 temperature and Pe pressure show plausible values.

  5. Decide which setpoints you want to write, and leave configuration registers alone while the system is running.

Things to watch for

The controller does not answer on the bus. What should I check?

The factory setting is address 1, 19200 baud, even parity, 1 stop bit. Many masters default to no parity. Swap D+ and D- if nothing answers, and check that there is a 120 ohm termination at both ends. The EKE has no bias resistors of its own.

Why do temperatures and pressures look ten times too high?

Most values are sent as whole numbers with one decimal implied, so 52 means 5.2. The template applies that scale. For the temperature setpoint the scale is not certain: check the raw value against the display once, and change the scale of that one register if needed.

Can I run several EKE controllers on one RS485 line?

Yes. Give each controller its own address in parameter G001 and keep the same speed and parity on all of them. Wire the bus as one line from device to device, without long branches.

Why is a setting not accepted when I write it?

Many configuration parameters, such as refrigerant, valve and sensor setup, can only be changed while the main switch is off. Switch the controller off, write the setting, and switch it on again. Write only values inside the range of the parameter, and change settings on a running plant with care.