Janitza UMG 605-PRO
Power quality analyser for voltage, current, power, harmonics, flicker and energy per phase and tariff.
The Janitza UMG 605-PRO is a power quality analyser that measures voltage, current, power, harmonics and flicker in low and medium voltage distribution boards. This Modbus RTU template reads all measured, mean, minimum and maximum values and the energy counters per tariff into ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 1299, read and write
- Brand
- Janitza
- Key readings
- Voltage L-N and L-L · Current per phase · Real power · Reactive power · Power factor · Frequency · THD voltage and current · Real energy
- Available commands
- Voltage phase angles
- Compatible models
- UMG 605-PRO
- Last updated
Registers (1299)
1299 read, 6 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Voltage L1-N | V | Read | |||
| Voltage L2-N | V | Read | |||
| Voltage L3-N | V | Read | |||
| Voltage L1-L2 | V | Read | |||
| Voltage L2-L3 | V | Read | |||
| Voltage L3-L1 | V | Read | |||
| Apparent Current, L1-N | A | Read | |||
| Apparent Current, L2-N | A | Read | |||
| Apparent Current, L3-N | A | Read | |||
| Vector Sum; IN=I1+I2+I3 | A | Read | |||
| Real Power L1-N | W | Read | |||
| Real Power L2-N | W | Read | |||
| Real Power L3-N | W | Read | |||
| Psum3=P1+P2+P3 | W | Read | |||
| Apparent Power L1-N | VA | Read | |||
| Apparent Power L2-N | VA | Read | |||
| Apparent Power L3-N | VA | Read | |||
| Sum; Ssum3=S1+S2+S3 | VA | Read | |||
| Reactive Power L1 (Fundamental Comp.) | var | Read | |||
| Reactive Power L2 (Fundamental Comp.) | var | Read | |||
| Reactive Power L3 (Fundamental Comp.) | var | Read | |||
| Qsum3=Q1+Q2+Q3 (Fundamental Comp.) | var | Read | |||
| CosPhi; UL1 IL1 (Fundamental Comp.) | Read | ||||
| CosPhi; UL2 IL2 (Fundamental Comp.) | Read | ||||
| CosPhi; UL3 IL3 (Fundamental Comp.) | Read | ||||
| Measured Frequency | Hz | Read | |||
| Rotation Field; 1=right, 0=none, -1=left | Read | ||||
| Real Energy L1 | Wh | Read | |||
| Real Energy L2 | Wh | Read | |||
| Real Energy L3 | Wh | Read | |||
| Real Energy L1..L3 | Wh | Read | |||
| Real Energy L1, Consumed | Wh | Read | |||
| Real Energy L2, Consumed | Wh | Read | |||
| Real Energy L3, Consumed | Wh | Read | |||
| Real Energy L1..L3, Consumed, Rate 1 | Wh | Read | |||
| Real Energy L1, Delivered | Wh | Read | |||
| Real Energy L2, Delivered | Wh | Read | |||
| Real Energy L3, Delivered | Wh | Read | |||
| Real Energy L1..L3, Delivered | Wh | Read | |||
| Apparent Energy L1 | VAh | Read | |||
| Apparent Energy L2 | VAh | Read | |||
| Apparent Energy L3 | VAh | Read | |||
| Apparent Energy L1..L3 | VAh | Read | |||
| Reactive Energy L1 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy L2 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy L3 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy L1..L3 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy, Inductive, L1 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy, Inductive, L2 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy, Inductive, L3 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy L1..L3, Ind. (Fundamental Comp.) | varh | Read | |||
| Reactive Energy, Capacitive, L1 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy, Capacitive, L2 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy, Capacitive, L3 (Fundamental Comp.) | varh | Read | |||
| Reactive Energy L1..L3, Cap. (Fundamental Comp.) | varh | Read | |||
| Harmonic, THD,U L1-N | % | Read | |||
| Harmonic, THD,U L2-N | % | Read | |||
| Harmonic, THD,U L3-N | % | Read | |||
| Harmonic, THD,I L1 | % | Read | |||
| Harmonic, THD,I L2 | % | Read | |||
| Harmonic, THD,I L3 | % | Read | |||
| Voltage Phase L-L [0] | ° | Read and write | |||
| Voltage Phase L-L [1] | ° | Read and write | |||
| Voltage Phase L-L [2] | ° | Read and write | |||
| Voltage Phase L-N [0] | ° | Read and write | |||
| Voltage Phase L-N [1] | ° | Read and write | |||
| Voltage Phase L-N [2] | ° | Read and write | |||
| Lock Transformer Ratios, 0=not Locked, 1=locked | Read | ||||
| Time (UTC) | Read | ||||
| Time (UTC) (Clock) | s | Read | |||
| Day (1..31) | Read | ||||
| Month (0=Jan, .. 11=Dec) | Read | ||||
| Year | Read | ||||
| Hour (1..24) | h | Read | |||
| Minute (1..59) | min | Read | |||
| Second (1..59) | s | Read | |||
| Weekday (0=Sun, .. 6=Sat) | Read | ||||
| Harmonic, THD, U L1-L2 | % | Read | |||
| Harmonic, THD, U L2-L3 | % | Read | |||
| Harmonic, THD, U L3-L1 | % | Read | |||
| Interharmonics, U L1-L2 | % | Read | |||
| Interharmonics, U L2-L3 | % | Read | |||
| Interharmonics, U L3-L1 | % | Read | |||
| Harmonic, THD, U L1-N | % | Read | |||
| Harmonic, THD, U L2-N | % | Read | |||
| Harmonic, THD, U L3-N | % | Read | |||
| Harmonic, THD, U L4-N | % | Read | |||
| Harmonic, THD, I L1-N | % | Read | |||
| Harmonic, THD, I L2-N | % | Read | |||
| Harmonic, THD, I L3-N | % | Read | |||
| Harmonic, THD, I L4-N | % | Read | |||
| Interharmonics, U L1-N | % | Read | |||
| Interharmonics, U L2-N | % | Read | |||
| Interharmonics, U L3-N | % | Read | |||
| Interharmonics, U L4-N | % | Read | |||
| Interharmonics, I L1-N | % | Read | |||
| Interharmonics, I L2-N | % | Read | |||
| Interharmonics, I L3-N | % | Read | |||
| Interharmonics, I L4-N | % | Read | |||
| K-Factor, L1 | Read | ||||
| K-Factor, L2 | Read | ||||
| K-Factor, L3 | Read | ||||
| K-Factor, L4 | Read | ||||
| Voltage, L1-N | V | Read | |||
| Voltage, L2-N | V | Read | |||
| Voltage, L3-N | V | Read | |||
| Voltage, L4-N | V | Read | |||
| Apparent Current, L1 | A | Read | |||
| Apparent Current, L2 | A | Read | |||
| Apparent Current, L3 | A | Read | |||
| Apparent Current, L4 | A | Read | |||
| Real Power, L1 | W | Read | |||
| Real Power, L2 | W | Read | |||
| Real Power, L3 | W | Read | |||
| Real Power, L4 | W | Read | |||
| Reactive Power, L1 | var | Read | |||
| Reactive Power, L2 | var | Read | |||
| Reactive Power, L3 | var | Read | |||
| Reactive Power, L4 | var | Read | |||
| Apparent Power, L1 [0] | VA | Read | |||
| Apparent Power, L1 [1] | VA | Read | |||
| Apparent Power, L1 [2] | VA | Read | |||
| Apparent Power, L1 [3] | VA | Read | |||
| Distortion Power Factor, L1 | VA | Read | |||
| Distortion Power Factor, L2 | VA | Read | |||
| Distortion Power Factor, L3 | VA | Read | |||
| Distortion Power Factor, L4 | VA | Read | |||
| Power Factor, L1 | Read | ||||
| Power Factor, L2 | Read | ||||
| Power Factor, L3 | Read | ||||
| Power Factor, L4 | Read | ||||
| Phase Conductor Voltage, U L1-L2 | V | Read | |||
| Phase Conductor Voltage, U L2-L3 | V | Read | |||
| Phase Conductor Voltage, U L3-L1 | V | Read | |||
| Phase Conductor Voltage Real Part, U L1-L2 | V | Read | |||
| Phase Conductor Voltage Real Part, U L2-L3 | V | Read | |||
| Phase Conductor Voltage Real Part, U L3-L1 | V | Read | |||
| Phase Conductor Voltage Imaginary Part, U L1-L2 | V | Read | |||
| Phase Conductor Voltage Imaginary Part, U L2-L3 | V | Read | |||
| Phase Conductor Voltage Imaginary Part, U L3-L1 | V | Read | |||
| Vector Sum, IN = I1 + I2 + I3 | A | Read | |||
| Vector Sum, I1 + I2 + I3 + I4 | A | Read | |||
| Sum, S = S1 + S2 + S3 | VA | Read | |||
| Sum, P = P1 + P2 + P3 | W | Read | |||
| Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 | var | Read | |||
| CosPhi Of Mains Frequency Calculated From Psum3 And Qsum3 | Read | ||||
| Sum, S = S1 + S2 + S3 + S4 | VA | Read | |||
| Sum, P = P1 + P2 + P3 + P4 | W | Read | |||
| Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 + Q4 | var | Read | |||
| CosPhi Of Mains Frequency Calculated From Psum And Qsum | Read | ||||
| Voltage, Real Part, L1-N | V | Read | |||
| Voltage, Real Part, L2-N | V | Read | |||
| Voltage, Real Part, L3-N | V | Read | |||
| Voltage, Real Part, L4-N | V | Read | |||
| Voltage, Imaginary Part, L1-N | V | Read | |||
| Voltage, Imaginary Part, L2-N | V | Read | |||
| Voltage, Imaginary Part, L3-N | V | Read | |||
| Voltage, Imaginary Part, L4-N | V | Read | |||
| Current, Real Part, L1 | A | Read | |||
| Current, Real Part, L2 | A | Read | |||
| Current, Real Part, L3 | A | Read | |||
| Current, Real Part, L4 | A | Read | |||
| Current, Imaginary Part, L1 | A | Read | |||
| Current, Imaginary Part, L2 | A | Read | |||
| Current, Imaginary Part, L3 | A | Read | |||
| Current, Imaginary Part, L4 | A | Read | |||
| Phase, UL1 IL1 | ° | Read | |||
| Phase, UL2 IL2 | ° | Read | |||
| Phase, UL3 IL3 | ° | Read | |||
| Phase, UL4 IL4 | ° | Read | |||
| Fund. Power Factor, CosPhi; UL1 IL1 | Read | ||||
| Fund. Power Factor, CosPhi; UL2 IL2 | Read | ||||
| Fund. Power Factor, CosPhi; UL3 IL3 | Read | ||||
| Fund. Power Factor, CosPhi; UL4 IL4 | Read | ||||
| Sign, Q L1, +1=ind., -1=cap. | Read | ||||
| Sign, Q L2, +1=ind., -1=cap. | Read | ||||
| Sign, Q L3, +1=ind., -1=cap. | Read | ||||
| VSign, Q L4, +1=ind., -1=cap. | Read | ||||
| Measured Frequency (200 ms) | Hz | Read | |||
| Nominal Frequency | Hz | Read | |||
| Zero Sequence, Voltage | V | Read | |||
| Positive Sequence, Voltage | V | Read | |||
| Negative Sequence, Voltage | V | Read | |||
| Unsymmetrical; Voltage | % | Read | |||
| Unsymmetrical; Current | % | Read | |||
| Rotation Field; 1=right, 0=none, -1=left (200 ms) | Read | ||||
| Zero Sequence, Current | A | Read | |||
| Positive Sequence, Current | A | Read | |||
| Negative Sequence, Current | A | Read | |||
| Input 1, Measured Value | W | Read | |||
| Input 2, Measured Value | W | Read | |||
| Crest Factor, I L1 | A | Read | |||
| Crest Factor, I L2 | A | Read | |||
| Crest Factor, I L3 | A | Read | |||
| Crest Factor, I L4 | A | Read | |||
| Crest Factor, U L1 | V | Read | |||
| Crest Factor, U L2 | V | Read | |||
| Crest Factor, U L3 | V | Read | |||
| Crest Factor, U L4 | V | Read | |||
| Crest Factor, U L1-L2 | V | Read | |||
| Crest Factor, U L2-L3 | V | Read | |||
| Crest Factor, U L3-L1 | V | Read | |||
| Peak Value Negative, I L1 | A | Read | |||
| Peak Value Negative, I L2 | A | Read | |||
| Peak Value Negative, I L3 | A | Read | |||
| Peak Value Negative, I L4 | A | Read | |||
| Peak Value Negative, U L1-N | V | Read | |||
| Peak Value Negative, U L2-N | V | Read | |||
| Peak Value Negative, U L3-N | V | Read | |||
| Peak Value Negative, U L4-N | V | Read | |||
| Peak Value Positive, I L1 | A | Read | |||
| Peak Value Positive, I L2 | A | Read | |||
| Peak Value Positive, I L3 | A | Read | |||
| Peak Value Positive, I L4 | A | Read | |||
| Peak Value Positive, U L1-N | V | Read | |||
| Peak Value Positive, U L2-N | V | Read | |||
| Peak Value Positive, U L3-N | V | Read | |||
| Peak Value Positive, U L4-N | V | Read | |||
| Peak-peak Value Positive, I L1 | A | Read | |||
| Peak-peak Value Positive, I L2 | A | Read | |||
| Peak-peak Value Positive, I L3 | A | Read | |||
| Peak-peak Value Positive, I L4 | A | Read | |||
| Peak-peak Value Positive, U L1-N | V | Read | |||
| Peak-peak Value Positive, U L2-N | V | Read | |||
| Peak-peak Value Positive, U L3-N | V | Read | |||
| Peak-peak Value Positive, U L4-N | V | Read | |||
| Under Difference, I L1 | % | Read | |||
| Under Difference, I L2 | % | Read | |||
| Under Difference, I L3 | % | Read | |||
| Under Difference, I L4 | % | Read | |||
| Under Difference, U L1 (61000-4-30) | % | Read | |||
| Under Difference, U L2 (61000-4-30) | % | Read | |||
| Under Difference, U L3 (61000-4-30) | % | Read | |||
| Under Difference, U L4 (61000-4-30) | % | Read | |||
| Over Difference, I L1 | % | Read | |||
| Over Difference, I L2 | % | Read | |||
| Over Difference, I L3 | % | Read | |||
| Over Difference, I L4 | % | Read | |||
| Over Difference, U L1 (61000-4-30) | % | Read | |||
| Over Difference, U L2 (61000-4-30) | % | Read | |||
| Over Difference, U L3 (61000-4-30) | % | Read | |||
| Over Difference, U L4 (61000-4-30) | % | Read | |||
| Peak Value Negative, U L1-L2 | V | Read | |||
| Peak Value Negative, U L2-L3 | V | Read | |||
| Peak Value Negative, U L3-L1 | V | Read | |||
| Peak Value Positive, U L1-L2 | V | Read | |||
| Peak Value Positive, U L2-L3 | V | Read | |||
| Peak Value Positive, U L3-L1 | V | Read | |||
| Peak-peak Value, U L1-L2 | V | Read | |||
| Peak-peak Value, U L2-L3 | V | Read | |||
| Peak-peak Value, U L3-L1 | V | Read | |||
| Under Difference, U L1-L2 (61000-4-30) | % | Read | |||
| Under Difference, U L2-L3 (61000-4-30) | % | Read | |||
| Under Difference, U L3-L1 (61000-4-30) | % | Read | |||
| Over Difference, U L1-L2 (61000-4-30) | % | Read | |||
| Over Difference, U L2-L3 (61000-4-30) | % | Read | |||
| Over Difference, U L3-L1 (61000-4-30) | % | Read | |||
| Current Flicker Pf5, L1-N | Read | ||||
| Current Flicker Pf5, L2-N | Read | ||||
| Current Flicker Pf5, L3-N | Read | ||||
| Current Flicker Pf5, L4-N | Read | ||||
| Short-term Flicker Level, Pst (10m), L1-N | Read | ||||
| Short-term Flicker Level, Pst (10m), L2-N | Read | ||||
| Short-term Flicker Level, Pst (10m), L3-N | Read | ||||
| Short-term Flicker Level, Pst (10m), L4-N | Read | ||||
| Long-term Flicker Level, Plt (2h), L1-N | Read | ||||
| Long-term Flicker Level, Plt (2h), L2-N | Read | ||||
| Long-term Flicker Level, Plt (2h), L3-N | Read | ||||
| Long-term Flicker Level, Plt (2h), L4-N | Read | ||||
| Ripple Control Signal, U L1-N (61000-4-30) | V | Read | |||
| Ripple Control Signal, U L2-N (61000-4-30) | V | Read | |||
| Ripple Control Signal, U L3-N (61000-4-30) | V | Read | |||
| Ripple Control Signal, U L4-N (61000-4-30) | V | Read | |||
| Ripple Control Signal, I L1 | A | Read | |||
| Ripple Control Signal, I L2 | A | Read | |||
| Ripple Control Signal, I L3 | A | Read | |||
| Ripple Control Signal, I L4 | A | Read | |||
| Ripple Control Signal, U L1-L2 (61000-4-30) | V | Read | |||
| Ripple Control Signal, U L2-L3 (61000-4-30) | V | Read | |||
| Ripple Control Signal, U L3-L1 (61000-4-30) | V | Read | |||
| Internal Temperature | °C | Read | |||
| PF_Total=P_Sum3/S_Sum3 Internal Temperature | Read | ||||
| IN Total Demand Distortion [0] | % | Read | |||
| IN Total Demand Distortion [1] | % | Read | |||
| IN Total Demand Distortion [2] | % | Read | |||
| IN Total Demand Distortion [3] | % | Read | |||
| IN Total Demand Distortion | % | Read | |||
| ULN Crest Faktor [0] | Read | ||||
| ULN Crest Faktor [1] | Read | ||||
| ULN Crest Faktor [2] | Read | ||||
| ULL Crest Faktor [0] | Read | ||||
| ULL Crest Faktor [1] | Read | ||||
| ULL Crest Faktor [2] | Read | ||||
| IN Crest Faktor [0] | Read | ||||
| IN Crest Faktor [1] | Read | ||||
| IN Crest Faktor [2] | Read | ||||
| IN Crest Faktor [3] | Read | ||||
| Maximum Demand Load Current, L1..L3 | Read | ||||
| Maximum Demand Load Current, L4 | Read | ||||
| Average, U L1-N | V | Read | |||
| Average, U L2-N | V | Read | |||
| Average, U L3-N | V | Read | |||
| Average, U L4-N | V | Read | |||
| Average, U L1-L2 | V | Read | |||
| Average, U L2-L3 | V | Read | |||
| Average, U L3-L4 | V | Read | |||
| Mean Value Of The Crest Factor, U L1-N | % | Read | |||
| Mean Value Of The Crest Factor, U L2-N | % | Read | |||
| Mean Value Of The Crest Factor, U L3-N | % | Read | |||
| Mean Value Of The Crest Factor, U L4-N | % | Read | |||
| Mean Value Of The Crest Factor, U L1-L2 | % | Read | |||
| Mean Value Of The Crest Factor, U L2-L3 | % | Read | |||
| Mean Value Of The Crest Factor, U L3-L4 | % | Read | |||
| Mean Value Zero Sequence | V | Read | |||
| Mean Value Positive Sequence | V | Read | |||
| Mean Value Negative Sequence | V | Read | |||
| Mean Value THD U L1-N | % | Read | |||
| Mean Value THD U L2-N | % | Read | |||
| Mean Value THD U L3-N | % | Read | |||
| Mean Value THD U L4-N | % | Read | |||
| Mean Value ZHD U L1-N | % | Read | |||
| Mean Value ZHD U L2-N | % | Read | |||
| Mean Value ZHD U L3-N | % | Read | |||
| Mean Value ZHD U L4-N | % | Read | |||
| Over Difference, U L1 (61000-4-30) (Mean) | % | Read | |||
| Over Difference, U L2 (61000-4-30) (Mean) | % | Read | |||
| Over Difference, U L3 (61000-4-30) (Mean) | % | Read | |||
| Over Difference, U L4 (61000-4-30) (Mean) | % | Read | |||
| Under Difference, U L1 (61000-4-30) (Mean) | % | Read | |||
| Under Difference, U L2 (61000-4-30) (Mean) | % | Read | |||
| Under Difference, U L3 (61000-4-30) (Mean) | % | Read | |||
| Under Difference, U L4 (61000-4-30) (Mean) | % | Read | |||
| Peak Value Negative, U L1-N (Mean) | V | Read | |||
| Peak Value Negative, U L2-N (Mean) | V | Read | |||
| Peak Value Negative, U L3-N (Mean) | V | Read | |||
| Peak Value Negative, U L4-N (Mean) | V | Read | |||
| Peak Value Positive, U L1-N (Mean) | V | Read | |||
| Peak Value Positive, U L2-N (Mean) | V | Read | |||
| Peak Value Positive, U L3-N (Mean) | V | Read | |||
| Peak Value Positive, U L4-N (Mean) | V | Read | |||
| Peak-peak Value Positive, U L1-N (Mean) | V | Read | |||
| Peak-peak Value Positive, U L2-N (Mean) | V | Read | |||
| Peak-peak Value Positive, U L3-N (Mean) | V | Read | |||
| Peak-peak Value Positive, U L4-N (Mean) | V | Read | |||
| Harmonic, THD, U L1-L2 (Mean) | % | Read | |||
| Harmonic, THD, U L2-L3 (Mean) | % | Read | |||
| Harmonic, THD, U L3-L1 (Mean) | % | Read | |||
| Interharmonics, U L1-L2 (Mean) | % | Read | |||
| Interharmonics, U L2-L3 (Mean) | % | Read | |||
| Interharmonics, U L3-L1 (Mean) | % | Read | |||
| Over Difference, U L1-L2 (61000-4-30) (Mean) | % | Read | |||
| Over Difference, U L2-L3 (61000-4-30) (Mean) | % | Read | |||
| Over Difference, U L3-L1 (61000-4-30) (Mean) | % | Read | |||
| Under Difference, U L1-L2 (61000-4-30) (Mean) | % | Read | |||
| Under Difference, U L2-L3 (61000-4-30) (Mean) | % | Read | |||
| Under Difference, U L3-L1 (61000-4-30) (Mean) | % | Read | |||
| Peak Value Negative, U L1-L2 (Mean) | V | Read | |||
| Peak Value Negative, U L2-L3 (Mean) | V | Read | |||
| Peak Value Negative, U L3-L1 (Mean) | V | Read | |||
| Peak Value Positive, U L1-L2 (Mean) | V | Read | |||
| Peak Value Positive, U L2-L3 (Mean) | V | Read | |||
| Peak Value Positive, U L3-L1 (Mean) | V | Read | |||
| Peak-peak Value, U L1-L2 (Mean) | V | Read | |||
| Peak-peak Value, U L2-L3 (Mean) | V | Read | |||
| Peak-peak Value, U L3-L1 (Mean) | V | Read | |||
| Star Connection Voltage (Mean) | V | Read | |||
| Unsymmetrical; Voltage (Mean) | % | Read | |||
| Measured Frequency (Mean) | Hz | Read | |||
| Nominal Frequency (Mean) | Hz | Read | |||
| Average, P L1 | W | Read | |||
| Average, P L2 | W | Read | |||
| Average, P L3 | W | Read | |||
| Average, P L4 | W | Read | |||
| Average, Psum=P1+P2+P3+P4 | W | Read | |||
| Average, Qsum=Q1+Q2+Q3+Q4 | var | Read | |||
| Average, Q L1 | var | Read | |||
| Average, Q L2 | var | Read | |||
| Average, Q L3 | var | Read | |||
| Average, Q L4 | var | Read | |||
| Average, Psum3=P1+P2+P3 | W | Read | |||
| Average, Qsum3=Q1+Q2+Q3 | var | Read | |||
| Average, I L1 | A | Read | |||
| Average, I L2 | A | Read | |||
| Average, I L3 | A | Read | |||
| Average, I L4 | A | Read | |||
| Average, S L1 | VA | Read | |||
| Average, S L2 | VA | Read | |||
| Average, S L3 | VA | Read | |||
| Average, S L4 | VA | Read | |||
| Average, IN=I1+I2+I3 | A | Read | |||
| Average, Isum=I1+I2+I3+I4 | A | Read | |||
| Average, Ssum3=S1+S2+S3 | VA | Read | |||
| Average, Ssum=S1+S2+S3+S4 | VA | Read | |||
| Harmonic, THD, I L1-N (Mean) | % | Read | |||
| Harmonic, THD, I L2-N (Mean) | % | Read | |||
| Harmonic, THD, I L3-N (Mean) | % | Read | |||
| Harmonic, THD, I L4-N (Mean) | % | Read | |||
| Interharmonics, I L1-N (Mean) | % | Read | |||
| Interharmonics, I L2-N (Mean) | % | Read | |||
| Interharmonics, I L3-N (Mean) | % | Read | |||
| Interharmonics, I L4-N (Mean) | % | Read | |||
| IN Crest Faktor [0] (Mean) | % | Read | |||
| IN Crest Faktor [1] (Mean) | % | Read | |||
| IN Crest Faktor [2] (Mean) | % | Read | |||
| IN Crest Faktor [3] (Mean) | % | Read | |||
| Average, Current, Zero Sequence | A | Read | |||
| Average, Current, Positive Sequence | A | Read | |||
| Average, Current, Negative Sequence | A | Read | |||
| Unsymmetrical; Current (Mean) | % | Read | |||
| Over Difference, I L1 (Mean) | % | Read | |||
| Over Difference, I L2 (Mean) | % | Read | |||
| Over Difference, I L3 (Mean) | % | Read | |||
| Over Difference, I L4 (Mean) | % | Read | |||
| Under Difference, I L1 (Mean) | % | Read | |||
| Under Difference, I L2 (Mean) | % | Read | |||
| Under Difference, I L3 (Mean) | % | Read | |||
| Under Difference, I L4 (Mean) | % | Read | |||
| Peak Value Negative, I L1 (Mean) | A | Read | |||
| Peak Value Negative, I L2 (Mean) | A | Read | |||
| Peak Value Negative, I L3 (Mean) | A | Read | |||
| Peak Value Negative, I L4 (Mean) | A | Read | |||
| Peak Value Positive, I L1 (Mean) | A | Read | |||
| Peak Value Positive, I L2 (Mean) | A | Read | |||
| Peak Value Positive, I L3 (Mean) | A | Read | |||
| Peak Value Positive, I L4 (Mean) | A | Read | |||
| Peak-peak Value Positive, I L1 (Mean) | A | Read | |||
| Peak-peak Value Positive, I L2 (Mean) | A | Read | |||
| Peak-peak Value Positive, I L3 (Mean) | A | Read | |||
| Peak-peak Value Positive, I L4 (Mean) | A | Read | |||
| Current Flicker Pf5, L1-N (Mean) | Read | ||||
| Current Flicker Pf5, L2-N (Mean) | Read | ||||
| Current Flicker Pf5, L3-N (Mean) | Read | ||||
| Current Flicker Pf5, L4-N (Mean) | Read | ||||
| Short-term Flicker Level, Pst (10m), L1-N (Mean) | Read | ||||
| Short-term Flicker Level, Pst (10m), L2-N (Mean) | Read | ||||
| Short-term Flicker Level, Pst (10m), L3-N (Mean) | Read | ||||
| Short-term Flicker Level, Pst (10m), L4-N (Mean) | Read | ||||
| Long-term Flicker Level, Plt (2h), L1-N (Mean) | Read | ||||
| Long-term Flicker Level, Plt (2h), L2-N (Mean) | Read | ||||
| Long-term Flicker Level, Plt (2h), L3-N (Mean) | Read | ||||
| Long-term Flicker Level, Plt (2h), L4-N (Mean) | Read | ||||
| Ripple Control Signal, I L1 (Mean) | A | Read | |||
| Ripple Control Signal, I L2 (Mean) | A | Read | |||
| Ripple Control Signal, I L3 (Mean) | A | Read | |||
| Ripple Control Signal, I L4 (Mean) | A | Read | |||
| Ripple Control Signal, U L1-L2 (61000-4-30) (Mean) | V | Read | |||
| Ripple Control Signal, U L2-L3 (61000-4-30) (Mean) | V | Read | |||
| Ripple Control Signal, U L3-L1 (61000-4-30) (Mean) | V | Read | |||
| Power Factor, L1 (Mean) | % | Read | |||
| Power Factor, L2 (Mean) | % | Read | |||
| Power Factor, L3 (Mean) | % | Read | |||
| Power Factor, L4 (Mean) | % | Read | |||
| Distortion Power Factor, L1 (Mean) | var | Read | |||
| Distortion Power Factor, L2 (Mean) | var | Read | |||
| Distortion Power Factor, L3 (Mean) | var | Read | |||
| Distortion Power Factor, L4 (Mean) | var | Read | |||
| K-Factor, L1 (Mean) | % | Read | |||
| K-Factor, L2 (Mean) | % | Read | |||
| K-Factor, L3 (Mean) | % | Read | |||
| K-Factor, L4 (Mean) | % | Read | |||
| Input 1, Measured Value (Mean) | W | Read | |||
| Input 2, Measured Value (Mean) | W | Read | |||
| Internal Temperature (Mean) | °C | Read | |||
| ULN_AVG_SUM | V | Read | |||
| ULL_AVG_SUM | V | Read | |||
| ILN_AVG_SUM | A | Read | |||
| TDD_AVG | % | Read | |||
| Minimum, U L1-N | V | Read | |||
| Minimum, U L2-N | V | Read | |||
| Minimum, U L3-N | V | Read | |||
| Minimum, U L4-N | V | Read | |||
| Minimum, U L1-L2 | V | Read | |||
| Minimum, U L2-L3 | V | Read | |||
| Minimum, U L3-L4 | V | Read | |||
| Crest Factor, U L1 (Min) | % | Read | |||
| Crest Factor, U L2 (Min) | % | Read | |||
| Crest Factor, U L3 (Min) | % | Read | |||
| Crest Factor, U L4 (Min) | % | Read | |||
| Crest Factor, U L1-L2 (Min) | % | Read | |||
| Crest Factor, U L2-L3 (Min) | % | Read | |||
| Crest Factor, U L3-L1 (Min) | % | Read | |||
| Zero Sequence, Voltage (Min) | V | Read | |||
| Positive Sequence, Voltage (Min) | V | Read | |||
| Negative Sequence, Voltage (Min) | V | Read | |||
| Ripple Control Signal, U L1-N (61000-4-30) (Min) | V | Read | |||
| Ripple Control Signal, U L2-N (61000-4-30) (Min) | V | Read | |||
| Ripple Control Signal, U L3-N (61000-4-30) (Min) | V | Read | |||
| Ripple Control Signal, U L4-N (61000-4-30) (Min) | V | Read | |||
| Harmonic, THD, U L1-N (Min) | % | Read | |||
| Harmonic, THD, U L2-N (Min) | % | Read | |||
| Harmonic, THD, U L3-N (Min) | % | Read | |||
| Harmonic, THD, U L4-N (Min) | % | Read | |||
| Interharmonics, U L1-N (Min) | % | Read | |||
| Interharmonics, U L2-N (Min) | % | Read | |||
| Interharmonics, U L3-N (Min) | % | Read | |||
| Interharmonics, U L4-N (Min) | % | Read | |||
| Over Difference, U L1 (61000-4-30) (Min) | % | Read | |||
| Over Difference, U L2 (61000-4-30) (Min) | % | Read | |||
| Over Difference, U L3 (61000-4-30) (Min) | % | Read | |||
| Over Difference, U L4 (61000-4-30) (Min) | % | Read | |||
| Under Difference, U L1 (61000-4-30) (Min) | % | Read | |||
| Under Difference, U L2 (61000-4-30) (Min) | % | Read | |||
| Under Difference, U L3 (61000-4-30) (Min) | % | Read | |||
| Under Difference, U L4 (61000-4-30) (Min) | % | Read | |||
| Peak Value Negative, U L1-N (Min) | V | Read | |||
| Peak Value Negative, U L2-N (Min) | V | Read | |||
| Peak Value Negative, U L3-N (Min) | V | Read | |||
| Peak Value Negative, U L4-N (Min) | V | Read | |||
| Peak Value Positive, U L1-N (Min) | V | Read | |||
| Peak Value Positive, U L2-N (Min) | V | Read | |||
| Peak Value Positive, U L3-N (Min) | V | Read | |||
| Peak Value Positive, U L4-N (Min) | V | Read | |||
| Peak-peak Value Positive, U L1-N (Min) | V | Read | |||
| Peak-peak Value Positive, U L2-N (Min) | V | Read | |||
| Peak-peak Value Positive, U L3-N (Min) | V | Read | |||
| Peak-peak Value Positive, U L4-N (Min) | V | Read | |||
| Harmonic, THD, U L1-L2 (Min) | % | Read | |||
| Harmonic, THD, U L2-L3 (Min) | % | Read | |||
| Harmonic, THD, U L3-L1 (Min) | % | Read | |||
| Interharmonics, U L1-L2 (Min) | % | Read | |||
| Interharmonics, U L2-L3 (Min) | % | Read | |||
| Interharmonics, U L3-L1 (Min) | % | Read | |||
| Over Difference, U L1-L2 (61000-4-30) (Min) | % | Read | |||
| Over Difference, U L2-L3 (61000-4-30) (Min) | % | Read | |||
| Over Difference, U L3-L1 (61000-4-30) (Min) | % | Read | |||
| Under Difference, U L1-L2 (61000-4-30) (Min) | % | Read | |||
| Under Difference, U L2-L3 (61000-4-30) (Min) | % | Read | |||
| Under Difference, U L3-L1 (61000-4-30) (Min) | % | Read | |||
| Peak Value Negative, U L1-L2 (Min) | V | Read | |||
| Peak Value Negative, U L2-L3 (Min) | V | Read | |||
| Peak Value Negative, U L3-L1 (Min) | V | Read | |||
| Peak Value Positive, U L1-L2 (Min) | V | Read | |||
| Peak Value Positive, U L2-L3 (Min) | V | Read | |||
| Peak Value Positive, U L3-L1 (Min) | V | Read | |||
| Peak-peak Value, U L1-L2 (Min) | V | Read | |||
| Peak-peak Value, U L2-L3 (Min) | V | Read | |||
| Peak-peak Value, U L3-L1 (Min) | V | Read | |||
| Star Connection Voltage (Min) | V | Read | |||
| Unsymmetrical; Voltage (Min) | % | Read | |||
| Measured Frequency (Min) | Hz | Read | |||
| Nominal Frequency (Min) | Hz | Read | |||
| Real Power, L1 (Min) | W | Read | |||
| Real Power, L2 (Min) | W | Read | |||
| Real Power, L3 (Min) | W | Read | |||
| Real Power, L4 (Min) | W | Read | |||
| Sum, P = P1 + P2 + P3 + P4 (Min) | W | Read | |||
| Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 + Q4 (Min) | var | Read | |||
| Reactive Power, L1 (Min) | var | Read | |||
| Reactive Power, L2 (Min) | var | Read | |||
| Reactive Power, L3 (Min) | var | Read | |||
| Reactive Power, L4 (Min) | var | Read | |||
| Sum, P = P1 + P2 + P3 (Min) | W | Read | |||
| Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 (Min) | var | Read | |||
| Internal Temperature (Min) | °C | Read | |||
| Maximum, U L1-N | V | Read | |||
| Maximum, U L2-N | V | Read | |||
| Maximum, U L3-N | V | Read | |||
| Maximum, U L4-N | V | Read | |||
| Maximum, U L1-L2 | V | Read | |||
| Maximum, U L2-L3 | V | Read | |||
| Maximum, U L3-L4 | V | Read | |||
| Crest Factor, U L1 (Max) | % | Read | |||
| Crest Factor, U L2 (Max) | % | Read | |||
| Crest Factor, U L3 (Max) | % | Read | |||
| Crest Factor, U L4 (Max) | % | Read | |||
| Crest Factor, U L1-L2 (Max) | % | Read | |||
| Crest Factor, U L2-L3 (Max) | % | Read | |||
| Crest Factor, U L3-L1 (Max) | % | Read | |||
| Zero Sequence, Voltage (Max) | V | Read | |||
| Positive Sequence, Voltage (Max) | V | Read | |||
| Negative Sequence, Voltage (Max) | V | Read | |||
| Ripple Control Signal, U L1-N (61000-4-30) (Max) | V | Read | |||
| Ripple Control Signal, U L2-N (61000-4-30) (Max) | V | Read | |||
| Ripple Control Signal, U L3-N (61000-4-30) (Max) | V | Read | |||
| Ripple Control Signal, U L4-N (61000-4-30) (Max) | V | Read | |||
| Harmonic, THD, U L1-N (Max) | % | Read | |||
| Harmonic, THD, U L2-N (Max) | % | Read | |||
| Harmonic, THD, U L3-N (Max) | % | Read | |||
| Harmonic, THD, U L4-N (Max) | % | Read | |||
| Interharmonics, U L1-N (Max) | % | Read | |||
| Interharmonics, U L2-N (Max) | % | Read | |||
| Interharmonics, U L3-N (Max) | % | Read | |||
| Interharmonics, U L4-N (Max) | % | Read | |||
| Over Difference, U L1 (61000-4-30) (Max) | % | Read | |||
| Over Difference, U L2 (61000-4-30) (Max) | % | Read | |||
| Over Difference, U L3 (61000-4-30) (Max) | % | Read | |||
| Over Difference, U L4 (61000-4-30) (Max) | % | Read | |||
| Under Difference, U L1 (61000-4-30) (Max) | % | Read | |||
| Under Difference, U L2 (61000-4-30) (Max) | % | Read | |||
| Under Difference, U L3 (61000-4-30) (Max) | % | Read | |||
| Under Difference, U L4 (61000-4-30) (Max) | % | Read | |||
| Peak Value Negative, U L1-N (Max) | V | Read | |||
| Peak Value Negative, U L2-N (Max) | V | Read | |||
| Peak Value Negative, U L3-N (Max) | V | Read | |||
| Peak Value Negative, U L4-N (Max) | V | Read | |||
| Peak Value Positive, U L1-N (Max) | V | Read | |||
| Peak Value Positive, U L2-N (Max) | V | Read | |||
| Peak Value Positive, U L3-N (Max) | V | Read | |||
| Peak Value Positive, U L4-N (Max) | V | Read | |||
| Peak-peak Value Positive, U L1-N (Max) | V | Read | |||
| Peak-peak Value Positive, U L2-N (Max) | V | Read | |||
| Peak-peak Value Positive, U L3-N (Max) | V | Read | |||
| Peak-peak Value Positive, U L4-N (Max) | V | Read | |||
| Harmonic, THD, U L1-L2 (Max) | % | Read | |||
| Harmonic, THD, U L2-L3 (Max) | % | Read | |||
| Harmonic, THD, U L3-L1 (Max) | % | Read | |||
| Interharmonics, U L1-L2 (Max) | % | Read | |||
| Interharmonics, U L2-L3 (Max) | % | Read | |||
| Interharmonics, U L3-L1 (Max) | % | Read | |||
| Over Difference, U L1-L2 (61000-4-30) (Max) | % | Read | |||
| Over Difference, U L2-L3 (61000-4-30) (Max) | % | Read | |||
| Over Difference, U L3-L1 (61000-4-30) (Max) | % | Read | |||
| Under Difference, U L1-L2 (61000-4-30) (Max) | % | Read | |||
| Under Difference, U L2-L3 (61000-4-30) (Max) | % | Read | |||
| Under Difference, U L3-L1 (61000-4-30) (Max) | % | Read | |||
| Peak Value Negative, U L1-L2 (Max) | V | Read | |||
| Peak Value Negative, U L2-L3 (Max) | V | Read | |||
| Peak Value Negative, U L3-L1 (Max) | V | Read | |||
| Peak Value Positive, U L1-L2 (Max) | V | Read | |||
| Peak Value Positive, U L2-L3 (Max) | V | Read | |||
| Peak Value Positive, U L3-L1 (Max) | V | Read | |||
| Peak-peak Value, U L1-L2 (Max) | V | Read | |||
| Peak-peak Value, U L2-L3 (Max) | V | Read | |||
| Peak-peak Value, U L3-L1 (Max) | V | Read | |||
| Star Connection Voltage (Max) | V | Read | |||
| Unsymmetrical; Voltage (Max) | % | Read | |||
| Measured Frequency (Max) | Hz | Read | |||
| Nominal Frequency (Max) | Hz | Read | |||
| Real Power, L1 (Max) | W | Read | |||
| Real Power, L2 (Max) | W | Read | |||
| Real Power, L3 (Max) | W | Read | |||
| Real Power, L4 (Max) | W | Read | |||
| Sum, P = P1 + P2 + P3 + P4 (Max) | W | Read | |||
| Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 + Q4 (Max) | var | Read | |||
| Reactive Power, L1 (Max) | var | Read | |||
| Reactive Power, L2 (Max) | var | Read | |||
| Reactive Power, L3 (Max) | var | Read | |||
| Reactive Power, L4 (Max) | var | Read | |||
| Sum, P = P1 + P2 + P3 (Max) | W | Read | |||
| Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 (Max) | var | Read | |||
| Apparent Current, L1 (Max) | A | Read | |||
| Apparent Current, L2 (Max) | A | Read | |||
| Apparent Current, L3 (Max) | A | Read | |||
| Apparent Current, L4 (Max) | A | Read | |||
| Apparent Power, L1 [0] (Max) | VA | Read | |||
| Apparent Power, L1 [1] (Max) | VA | Read | |||
| Apparent Power, L1 [2] (Max) | VA | Read | |||
| Apparent Power, L1 [3] (Max) | VA | Read | |||
| Vector Sum, IN = I1 + I2 + I3 (Max) | A | Read | |||
| Vector Sum, I1 + I2 + I3 + I4 (Max) | A | Read | |||
| Sum, S = S1 + S2 + S3 (Max) | VA | Read | |||
| Sum, S = S1 + S2 + S3 + S4 (Max) | VA | Read | |||
| Harmonic, THD, I L1-N (Max) | % | Read | |||
| Harmonic, THD, I L2-N (Max) | % | Read | |||
| Harmonic, THD, I L3-N (Max) | % | Read | |||
| Harmonic, THD, I L4-N (Max) | % | Read | |||
| Interharmonics, I L1-N (Max) | % | Read | |||
| Interharmonics, I L2-N (Max) | % | Read | |||
| Interharmonics, I L3-N (Max) | % | Read | |||
| Interharmonics, I L4-N (Max) | % | Read | |||
| IN Crest Faktor [0] (Max) | % | Read | |||
| IN Crest Faktor [1] (Max) | % | Read | |||
| IN Crest Faktor [2] (Max) | % | Read | |||
| IN Crest Faktor [3] (Max) | % | Read | |||
| Zero Sequence, Current (Max) | A | Read | |||
| Positive Sequence, Current (Max) | A | Read | |||
| Negative Sequence, Current (Max) | A | Read | |||
| Unsymmetrical; Current (Max) | % | Read | |||
| Over Difference, I L1 (Max) | % | Read | |||
| Over Difference, I L2 (Max) | % | Read | |||
| Over Difference, I L3 (Max) | % | Read | |||
| Over Difference, I L4 (Max) | % | Read | |||
| Under Difference, I L1 (Max) | % | Read | |||
| Under Difference, I L2 (Max) | % | Read | |||
| Under Difference, I L3 (Max) | % | Read | |||
| Under Difference, I L4 (Max) | % | Read | |||
| Peak Value Negative, I L1 (Max) | A | Read | |||
| Peak Value Negative, I L2 (Max) | A | Read | |||
| Peak Value Negative, I L3 (Max) | A | Read | |||
| Peak Value Negative, I L4 (Max) | A | Read | |||
| Peak Value Positive, I L1 (Max) | A | Read | |||
| Peak Value Positive, I L2 (Max) | A | Read | |||
| Peak Value Positive, I L3 (Max) | A | Read | |||
| Peak Value Positive, I L4 (Max) | A | Read | |||
| Peak-peak Value Positive, I L1 (Max) | A | Read | |||
| Peak-peak Value Positive, I L2 (Max) | A | Read | |||
| Peak-peak Value Positive, I L3 (Max) | A | Read | |||
| Peak-peak Value Positive, I L4 (Max) | A | Read | |||
| Current Flicker Pf5, L1-N (Max) | Read | ||||
| Current Flicker Pf5, L2-N (Max) | Read | ||||
| Current Flicker Pf5, L3-N (Max) | Read | ||||
| Current Flicker Pf5, L4-N (Max) | Read | ||||
| Short-term Flicker Level, Pst (10m), L1-N (Max) | Read | ||||
| Short-term Flicker Level, Pst (10m), L2-N (Max) | Read | ||||
| Short-term Flicker Level, Pst (10m), L3-N (Max) | Read | ||||
| Short-term Flicker Level, Pst (10m), L4-N (Max) | Read | ||||
| Long-term Flicker Level, Plt (2h), L1-N (Max) | Read | ||||
| Long-term Flicker Level, Plt (2h), L2-N (Max) | Read | ||||
| Long-term Flicker Level, Plt (2h), L3-N (Max) | Read | ||||
| Long-term Flicker Level, Plt (2h), L4-N (Max) | Read | ||||
| Ripple Control Signal, I L1 (Max) | A | Read | |||
| Ripple Control Signal, I L2 (Max) | A | Read | |||
| Ripple Control Signal, I L3 (Max) | A | Read | |||
| Ripple Control Signal, I L4 (Max) | A | Read | |||
| Ripple Control Signal, U L1-L2 (61000-4-30) (Max) | V | Read | |||
| Ripple Control Signal, U L2-L3 (61000-4-30) (Max) | V | Read | |||
| Ripple Control Signal, U L3-L1 (61000-4-30) (Max) | V | Read | |||
| Power Factor, L1 (Max) | % | Read | |||
| Power Factor, L2 (Max) | % | Read | |||
| Power Factor, L3 (Max) | % | Read | |||
| Power Factor, L4 (Max) | % | Read | |||
| Distortion Power Factor, L1 (Max) | var | Read | |||
| Distortion Power Factor, L2 (Max) | var | Read | |||
| Distortion Power Factor, L3 (Max) | var | Read | |||
| Distortion Power Factor, L4 (Max) | var | Read | |||
| K-Factor, L1 (Max) | % | Read | |||
| K-Factor, L2 (Max) | % | Read | |||
| K-Factor, L3 (Max) | % | Read | |||
| K-Factor, L4 (Max) | % | Read | |||
| Input 1, Measured Value (Max) | W | Read | |||
| Input 2, Measured Value (Max) | W | Read | |||
| Internal Temperature (Max) | °C | Read | |||
| Star Connection Voltage | V | Read | |||
| Status Digital Output 1, 0=not Active, 1=active | Read | ||||
| Status Digital Output 2, 0=not Active, 1=active | Read | ||||
| Status Digital Input 1, 0=not Active, 1=active [0] | Read | ||||
| Status Digital Input 1, 0=not Active, 1=active [1] | Read | ||||
| Event Counter | Read | ||||
| Flag Counter | Read | ||||
| Error Counter, Transients | Read | ||||
| Error Counter, Half-cycle Effective Values | Read | ||||
| Error Counter, Receive RS232 | Read | ||||
| Error Counter, Send RS232 | Read | ||||
| Error Counter, RS232 | Read | ||||
| Error Counter, Receive RS485 | Read | ||||
| Error Counter, Send RS485 | Read | ||||
| Error Counter, RS485 | Read | ||||
| 1= Delete All Real Energy Counters | Read | ||||
| 1= Delete All Reactive Energy Counters | Read | ||||
| RUN (Internal) | Read | ||||
| L1, L2, L3; Current Transformer, Primary | A | Read | |||
| L4; Current Transformer, Primary | A | Read | |||
| L1, L2, L3; Current Transf., Secondary | A | Read | |||
| L4; Current Transformer, Secondary | A | Read | |||
| L1, L2, L3; Voltage Transformer, Primary | V | Read | |||
| L4; Voltage Transformer, Primary | V | Read | |||
| L1, L2, L3; Spannungswandler, Sekundär | V | Read | |||
| L4; Spannungswandler, Sekundär | V | Read | |||
| Nominal Current Transf.; I L1, I L2, I L3 | A | Read | |||
| Nominal Current Transformer; I L4 | A | Read | |||
| Nominal Voltage; L1, L2, L3 | V | Read | |||
| Nominal Voltage; L4 | V | Read | |||
| Nominal Current; L1, L2, L3 | A | Read | |||
| Nominal Current; L4 | A | Read | |||
| TRNS_DELTA [0] (Internal) | % | Read | |||
| TRNS_DELTA [1] (Internal) | % | Read | |||
| TRNS_I_ABS [0] (Internal) | % | Read | |||
| TRNS_I_ABS [1] (Internal) | % | Read | |||
| TRNS_U_ABS [0] (Internal) | % | Read | |||
| TRNS_U_ABS [1] (Internal) | % | Read | |||
| I_EVT_MAX [0] (Internal) | % | Read | |||
| I_EVT_MAX [1] (Internal) | % | Read | |||
| U_EVT_MAX [0] (Internal) | % | Read | |||
| U_EVT_MAX [1] (Internal) | % | Read | |||
| U_EVT_MIN [0] (Internal) | % | Read | |||
| U_EVT_MIN [1] (Internal) | % | Read | |||
| U_EVT_OFF [0] (Internal) | % | Read | |||
| U_EVT_OFF [1] (Internal) | % | Read | |||
| Nominal Frequency 50Hz Or 60Hz | Hz | Read | |||
| FLICKER_SYSTEM (Internal) | Read | ||||
| TRNS_PRE (Internal) | Read | ||||
| TRNS_POST (Internal) | Read | ||||
| DEV_NAME (Internal) | Read | ||||
| DEV_DESC (Internal) | Read | ||||
| LANGUAGE (Internal) | Read | ||||
| SERNR (Internal) | Read | ||||
| PRODNR (Internal) | Read | ||||
| MBUSADDR (Internal) | Read | ||||
| MODE485 (Internal) | Read | ||||
| BAUD485 (Internal) | Read | ||||
| BAUD232 (Internal) | Read | ||||
| MODE232 (Internal) | Read | ||||
| Network Address | Read | ||||
| Network Mask | Read | ||||
| Gateway | Read | ||||
| 1=DHCP On, 0=DHCP Off | Read | ||||
| Contrast | Read | ||||
| Type Temperature Sensor | Read | ||||
| Status, Button 1 | Read | ||||
| Status, Button 2 | Read | ||||
| Status, Button 3 | Read | ||||
| DEBUG_IP (Internal) | Read | ||||
| Time Zone | s | Read | |||
| STIME (Internal) | s | Read | |||
| Start Day Of Summer/winter Switchover (Spring) | Read | ||||
| Start Hour Of Summer/winter Switchover | h | Read | |||
| Start Month Of Summer/winter Switchover | Read | ||||
| Start Minute Of Summer/winter Switchover | min | Read | |||
| Summer/winter Switchover (Spring) | Read | ||||
| Start Day Of Summer/winter Switchover (Autumn) | Read | ||||
| Start Hour Of Summer/winter Switchover (Other) | h | Read | |||
| Start Month Of Summer/winter Switchover (Other) | Read | ||||
| Start Minute Of Summer/winter Switchover (Other) | min | Read | |||
| Summer/Winter Switchover (Autumn) | Read | ||||
| EVT_VAL_PRE (Internal) | Read | ||||
| EVT_VAL_POST (Internal) | Read | ||||
| TRNS_MODE (Internal) | Read | ||||
| EVT_MODE (Internal) | Read | ||||
| CON_AUX_MODE (Internal) | Read | ||||
| CON_MODE (Internal) | Read | ||||
| PHASE_MODE (Internal) | Read | ||||
| COLOR [0] (Internal) | Read | ||||
| COLOR [1] (Internal) | Read | ||||
| COLOR [2] (Internal) | Read | ||||
| COLOR [3] (Internal) | Read | ||||
| COLOR [4] (Internal) | Read | ||||
| COLOR [5] (Internal) | Read | ||||
| COLOR [6] (Internal) | Read | ||||
| COLOR [7] (Internal) | Read | ||||
| GUEST_PASSWD (Internal) | Read | ||||
| USER_PASSWD (Internal) | Read | ||||
| ADMIN_PASSWD (Internal) | Read | ||||
| PULSWERT [0] (Internal) | Read | ||||
| PULSWERT [1] (Internal) | Read | ||||
| MAXSIZE_REC (Internal) | % | Read | |||
| MAXSIZE_TRNS (Internal) | % | Read | |||
| MAXSIZE_VWW (Internal) | % | Read | |||
| MAXSIZE_EVT (Internal) | % | Read | |||
| MAXSIZE_FLAGS (Internal) | % | Read | |||
| TFTP_FILE_NR (Internal) | Read | ||||
| TFTP_NEWFILE (Internal) | Read | ||||
| DIGOUTEVT [0] (Internal) | Read | ||||
| DIGOUTEVT [1] (Internal) | Read | ||||
| DIGOUTEVT_TIME [0] (Internal) | s | Read | |||
| DIGOUTEVT_TIME [1] (Internal) | s | Read | |||
| INVERT_DIGOUT [0] (Internal) | Read | ||||
| INVERT_DIGOUT [1] (Internal) | Read | ||||
| KORR_INT (Internal) | Read | ||||
| QUARZ_KORR_NTP (Internal) | ppm | Read | |||
| BACNET_SENDIAM_TIME (Internal) | s | Read | |||
| HTML_PORT (Internal) | Read | ||||
| IP_ADDR_STR (Internal) | Read | ||||
| IP_GATEWAY_STR (Internal) | Read | ||||
| IP_MASK_STR (Internal) | Read | ||||
| NAMESRV_IP (Internal) | Read | ||||
| NTPSRV_IP (Internal) | Read | ||||
| HOSTNAME (Internal) | Read | ||||
| EVT_NAME (Internal) | Read | ||||
| FL_NAME (Internal) | Read | ||||
| TR_NAME (Internal) | Read | ||||
| HWW_NAME (Internal) | Read | ||||
| FILEMAGIC (Internal) | Read | ||||
| MODE_NTP (Internal) | Read | ||||
| QUARZ_KORR (Internal) | ppm | Read | |||
| RC_FREQ (Internal) | Hz | Read | |||
| TFTP_PRG1 Part 1 (Internal) | Read | ||||
| TFTP_PRG1 Part 2 (Internal) | Read | ||||
| TFTP_PRG2 Part 1 (Internal) | Read | ||||
| TFTP_PRG2 Part 2 (Internal) | Read | ||||
| TFTP_PRG3 Part 1 (Internal) | Read | ||||
| TFTP_PRG3 Part 2 (Internal) | Read | ||||
| TFTP_PRG4 Part 1 (Internal) | Read | ||||
| TFTP_PRG4 Part 2 (Internal) | Read | ||||
| TFTP_PRG5 Part 1 (Internal) | Read | ||||
| TFTP_PRG5 Part 2 (Internal) | Read | ||||
| TFTP_PRG6 Part 1 (Internal) | Read | ||||
| TFTP_PRG6 Part 2 (Internal) | Read | ||||
| TFTP_REC Part 1 (Internal) | Read | ||||
| TFTP_REC Part 2 (Internal) | Read | ||||
| TFTP_DISPLAY Part 1 (Internal) | Read | ||||
| TFTP_DISPLAY Part 2 (Internal) | Read | ||||
| RELEASE (Internal) | Read | ||||
| DOWNLOAD (Internal) | Read | ||||
| DUMMY (Internal) | Read | ||||
| MASTER_TIMEOUT (Internal) | ms | Read | |||
| ED_PASSWD (Internal) | Read | ||||
| HTML_PASSWD (Internal) | Read | ||||
| PASSWD_MODE (Internal) | Read | ||||
| CHALLENGE (Internal) | Read | ||||
| BACNET_PASSWORD (Internal) | Read | ||||
| FORBID_CFG_HTML (Internal) | Read | ||||
| FORBID_FTP (Internal) | Read | ||||
| FORBID_CFG_FTP (Internal) | Read | ||||
| FORBID_MODETH (Internal) | Read | ||||
| FORBID_CFG_MODETH (Internal) | Read | ||||
| FORBID_BACNET (Internal) | Read | ||||
| IP_UP (Internal) | Read | ||||
| SYSVAR_CNT (Internal) | Read | ||||
| SEQ_IP0 (Internal) | Read | ||||
| SEQ_IP1 (Internal) | Read | ||||
| SEQ_IP2 (Internal) | Read | ||||
| SEQ_IP3 (Internal) | Read | ||||
| SEQ_IP4 (Internal) | Read | ||||
| SEQ_IP5 (Internal) | Read | ||||
| SEQ_IP6 (Internal) | Read | ||||
| SEQ_IP7 (Internal) | Read | ||||
| CH_MAP [0] (Internal) | Read | ||||
| CH_MAP [1] (Internal) | Read | ||||
| CH_MAP [2] (Internal) | Read | ||||
| CH_MAP [3] (Internal) | Read | ||||
| CH_MAP [4] (Internal) | Read | ||||
| CH_MAP [5] (Internal) | Read | ||||
| CH_MAP [6] (Internal) | Read | ||||
| CH_MAP [7] (Internal) | Read | ||||
| NTP_DIV (Internal) | s | Read | |||
| NTP_TURNAROUND (Internal) | s | Read | |||
| NTP_KORR (Internal) | ppm | Read | |||
| RX_ETH_COUNT (Internal) | Read | ||||
| TX_ETH_COUNT (Internal) | Read | ||||
| ERR_ETH_COUNT (Internal) | Read | ||||
| RX_NTP_COUNT (Internal) | Read | ||||
| TX_NTP_COUNT (Internal) | Read | ||||
| ERR_NTP_COUNT (Internal) | Read | ||||
| RX_DNS_COUNT (Internal) | Read | ||||
| TX_DNS_COUNT (Internal) | Read | ||||
| ERR_DNS_COUNT (Internal) | Read | ||||
| RX_DHCP_COUNT (Internal) | Read | ||||
| TX_DHCP_COUNT (Internal) | Read | ||||
| ERR_DHCP_COUNT (Internal) | Read | ||||
| TX_EMAIL_COUNT (Internal) | Read | ||||
| ERR_EMAIL_COUNT (Internal) | Read | ||||
| MTU_SIZE (Internal) | Read | ||||
| 10ms Only For Internal Use | Read | ||||
| Real Energy, Consumption, Tariff 3, L1 | Wh | Read | |||
| Real Energy, Consumption, Tariff 3, L2 | Wh | Read | |||
| Real Energy, Consumption, Tariff 3, L3 | Wh | Read | |||
| Real Energy, Consumption, Tariff 3, L4 | Wh | Read | |||
| Real Energy, Consump., Tariff 3, L1..L3 | Wh | Read | |||
| Real Energy, Consump., Tariff 3, L1..L4 | Wh | Read | |||
| Real Energy, Consumption, Tariff 4, L1 | Wh | Read | |||
| Real Energy, Consumption, Tariff 4, L2 | Wh | Read | |||
| Real Energy, Consumption, Tariff 4, L3 | Wh | Read | |||
| Real Energy, Consumption, Tariff 4, L4 | Wh | Read | |||
| Real Energy, Consump., Tariff 4, L1..L3 | Wh | Read | |||
| Real Energy, Consump., Tariff 4, L1..L4 | Wh | Read | |||
| Real Energy, Supply, Tariff 3, L1 | Wh | Read | |||
| Real Energy, Supply, Tariff 3, L2 | Wh | Read | |||
| Real Energy, Supply, Tariff 3, L3 | Wh | Read | |||
| Real Energy, Supply, Tariff 3, L4 | Wh | Read | |||
| Real Energy, Supply, Tariff 3, L1..L3 | Wh | Read | |||
| Real Energy, Supply, Tariff 3, L1..L4 | Wh | Read | |||
| Real Energy, Supply, Tariff 4, L1 | Wh | Read | |||
| Real Energy, Supply, Tariff 4, L2 | Wh | Read | |||
| Real Energy, Supply, Tariff 4, L3 | Wh | Read | |||
| Real Energy, Supply, Tariff 4, L4 | Wh | Read | |||
| Real Energy, Supply, Tariff 4, L1..L3 | Wh | Read | |||
| Real Energy, Supply, Tariff 4, L1..L4 | Wh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L1 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L2 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L3 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L4 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L1..L3 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L1..L4 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 4, L1 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 4, L2 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 4, L3 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 4, L4 | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L1..L3 (Other) | varh | Read | |||
| Reactive Energy, Induktiv, Tariff 3, L1..L4 (Other) | varh | Read | |||
| SNMP_USERVAR [0] (Internal) | Read | ||||
| SNMP_USERVAR [1] (Internal) | Read | ||||
| SNMP_USERVAR [2] (Internal) | Read | ||||
| SNMP_USERVAR [3] (Internal) | Read | ||||
| SNMP_USERVAR [4] (Internal) | Read | ||||
| SNMP_USERVAR [5] (Internal) | Read | ||||
| SNMP_USERVAR [6] (Internal) | Read | ||||
| SNMP_USERVAR [7] (Internal) | Read | ||||
| SNMP_USERVAR [8] (Internal) | Read | ||||
| SNMP_USERVAR [9] (Internal) | Read | ||||
| SNMP_USERVAR [10] (Internal) | Read | ||||
| SNMP_USERVAR [11] (Internal) | Read | ||||
| SNMP_USERVAR [12] (Internal) | Read | ||||
| SNMP_USERVAR [13] (Internal) | Read | ||||
| SNMP_USERVAR [14] (Internal) | Read | ||||
| SNMP_USERVAR [15] (Internal) | Read | ||||
| AKT_EVT_START [0] (Internal) | s | Read | |||
| AKT_EVT_START [1] (Internal) | s | Read | |||
| AKT_EVT_START [2] (Internal) | s | Read | |||
| AKT_EVT_START [3] (Internal) | s | Read | |||
| AKT_EVT_START [4] (Internal) | s | Read | |||
| AKT_EVT_START [5] (Internal) | s | Read | |||
| AKT_EVT_START [6] (Internal) | s | Read | |||
| AKT_EVT_START [7] (Internal) | s | Read | |||
| AKT_EVT_STOP [0] (Internal) | s | Read | |||
| AKT_EVT_STOP [1] (Internal) | s | Read | |||
| AKT_EVT_STOP [2] (Internal) | s | Read | |||
| AKT_EVT_STOP [3] (Internal) | s | Read | |||
| AKT_EVT_STOP [4] (Internal) | s | Read | |||
| AKT_EVT_STOP [5] (Internal) | s | Read | |||
| AKT_EVT_STOP [6] (Internal) | s | Read | |||
| AKT_EVT_STOP [7] (Internal) | s | Read | |||
| AKT_EVT_BOUND [0] (Internal) | Read | ||||
| AKT_EVT_BOUND [1] (Internal) | Read | ||||
| AKT_EVT_BOUND [2] (Internal) | Read | ||||
| AKT_EVT_BOUND [3] (Internal) | Read | ||||
| AKT_EVT_BOUND [4] (Internal) | Read | ||||
| AKT_EVT_BOUND [5] (Internal) | Read | ||||
| AKT_EVT_BOUND [6] (Internal) | Read | ||||
| AKT_EVT_BOUND [7] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [0] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [1] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [2] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [3] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [4] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [5] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [6] (Internal) | Read | ||||
| AKT_EVT_MAXVAL [7] (Internal) | Read | ||||
| AKT_EVT_MINVAL [0] (Internal) | Read | ||||
| AKT_EVT_MINVAL [1] (Internal) | Read | ||||
| AKT_EVT_MINVAL [2] (Internal) | Read | ||||
| AKT_EVT_MINVAL [3] (Internal) | Read | ||||
| AKT_EVT_MINVAL [4] (Internal) | Read | ||||
| AKT_EVT_MINVAL [5] (Internal) | Read | ||||
| AKT_EVT_MINVAL [6] (Internal) | Read | ||||
| AKT_EVT_MINVAL [7] (Internal) | Read | ||||
| AKT_EVT_AVG [0] (Internal) | Read | ||||
| AKT_EVT_AVG [1] (Internal) | Read | ||||
| AKT_EVT_AVG [2] (Internal) | Read | ||||
| AKT_EVT_AVG [3] (Internal) | Read | ||||
| AKT_EVT_AVG [4] (Internal) | Read | ||||
| AKT_EVT_AVG [5] (Internal) | Read | ||||
| AKT_EVT_AVG [6] (Internal) | Read | ||||
| AKT_EVT_AVG [7] (Internal) | Read | ||||
| AKT_EVT_REASON [0] (Internal) | Read | ||||
| AKT_EVT_REASON [1] (Internal) | Read | ||||
| AKT_EVT_REASON [2] (Internal) | Read | ||||
| AKT_EVT_REASON [3] (Internal) | Read | ||||
| AKT_EVT_REASON [4] (Internal) | Read | ||||
| AKT_EVT_REASON [5] (Internal) | Read | ||||
| AKT_EVT_REASON [6] (Internal) | Read | ||||
| AKT_EVT_REASON [7] (Internal) | Read | ||||
| AKT_EVT_CNT [0] (Internal) | Read | ||||
| AKT_EVT_CNT [1] (Internal) | Read | ||||
| AKT_EVT_CNT [2] (Internal) | Read | ||||
| AKT_EVT_CNT [3] (Internal) | Read | ||||
| AKT_EVT_CNT [4] (Internal) | Read | ||||
| AKT_EVT_CNT [5] (Internal) | Read | ||||
| AKT_EVT_CNT [6] (Internal) | Read | ||||
| AKT_EVT_CNT [7] (Internal) | Read | ||||
| HW_INDEX (Internal) | Read | ||||
| PTP_VERSION (Internal) | Read | ||||
| PTP_DOMAIN (Internal) | Read | ||||
| PTP_CLOCK_CLASS (Internal) | Read | ||||
| PTP_CLOCK_ACCURACY (Internal) | Read | ||||
| PTP_TIME_SOURCE (Internal) | Read | ||||
| PTP_TWO_STEP (Internal) | Read | ||||
| PTP_DELAY_MECHANISM (Internal) | Read | ||||
| PTP_PROFILE_ID [0] (Internal) | Read | ||||
| PTP_PROFILE_ID [1] (Internal) | Read | ||||
| PTP_PROFILE_ID [2] (Internal) | Read | ||||
| PTP_PROFILE_ID [3] (Internal) | Read | ||||
| PTP_PROFILE_ID [4] (Internal) | Read | ||||
| PTP_PROFILE_ID [5] (Internal) | Read | ||||
| PTP_ANNOUNCE_RECEIPT_TIMEOUT (Internal) | Read | ||||
| PTP_STATE (Internal) | Read | ||||
| PTP_MANAGEMENT_INTERFACE (Internal) | Read | ||||
| PTP_PRIORITY1 (Internal) | Read | ||||
| PTP_PRIORITY2 (Internal) | Read | ||||
| INIT_CUSTOMKEY (Internal) | Read | ||||
| FORBID_HTML (Internal) | Read | ||||
| IN Distortion Reactive Power [0] | var | Read | |||
| IN Distortion Reactive Power [1] | var | Read | |||
| IN Distortion Reactive Power [2] | var | Read | |||
| IN Distortion Reactive Power [3] | var | Read | |||
| Voltage, Real Part L-L [0] | V | Read | |||
| Voltage, Real Part L-L [1] | V | Read | |||
| Voltage, Real Part L-L [2] | V | Read | |||
| Voltage, Imaginary Part L-L [0] | V | Read | |||
| Voltage, Imaginary Part L-L [1] | V | Read | |||
| Voltage, Imaginary Part L-L [2] | V | Read | |||
| Counter For Started Events | Read | ||||
| Flags For Running Events | Read | ||||
| Free Input Field For Storing Numerical Information | Read | ||||
| Current Rate, Real/apparent Energy | Read | ||||
| Current Rate, Reactive Energy | Read | ||||
| Apparent Energy L1 (Energy List) | VAh | Read | |||
| Apparent Energy L2 (Energy List) | VAh | Read | |||
| Apparent Energy L3 (Energy List) | VAh | Read | |||
| Apparent Energy L4 | VAh | Read | |||
| Apparent Energy L1+L2+L3 | VAh | Read | |||
| Apparent Energy L1+L2+L3+L4 | VAh | Read | |||
| Real Energy L1 (Energy List) | Wh | Read | |||
| Real Energy L2 (Energy List) | Wh | Read | |||
| Real Energy L3 (Energy List) | Wh | Read | |||
| Real Energy L4 | Wh | Read | |||
| Real Energy L1+L2+L3 | Wh | Read | |||
| Real Energy L1+L2+L3+L4 | Wh | Read | |||
| Reactive Energy L1 | varh | Read | |||
| Reactive Energy L2 | varh | Read | |||
| Reactive Energy L3 | varh | Read | |||
| Reactive Energy L4 | varh | Read | |||
| Reactive Energy L1+L2+L3 | varh | Read | |||
| Reactive Energy L1+L2+L3+L4 | varh | Read | |||
| Real Energy L1, Consumed (Energy List) | Wh | Read | |||
| Real Energy L2, Consumed (Energy List) | Wh | Read | |||
| Real Energy L3, Consumed (Energy List) | Wh | Read | |||
| Real Energy L4, Consumed | Wh | Read | |||
| Real Energy L1+L2+L3, Consumed | Wh | Read | |||
| Real Energy L1+L2+L3+L4, Consumed | Wh | Read | |||
| Real Energy L1, Delivered (Energy List) | Wh | Read | |||
| Real Energy L2, Delivered (Energy List) | Wh | Read | |||
| Real Energy L3, Delivered (Energy List) | Wh | Read | |||
| Real Energy L4, Delivered | Wh | Read | |||
| Real Energy L1+L2+L3, Delivered | Wh | Read | |||
| Real Energy L1+L2+L3+L4, Delivered | Wh | Read | |||
| Real Energy L1, Consumed, HT (Tariff 1), Rate 1 | Wh | Read | |||
| Real Energy L2, Consumed, HT (Tariff 1), Rate 1 | Wh | Read | |||
| Real Energy L3, Consumed, HT (Tariff 1), Rate 1 | Wh | Read | |||
| Real Energy L4, Consumed, HT (Tariff 1), Rate 1 | Wh | Read | |||
| Real Energy L1..L3, Consumed, HT (Tariff 1), Rate 1 | Wh | Read | |||
| Real Energy L1..L4, Consumed, HT (Tariff 1), Rate 1 | Wh | Read | |||
| Real Energy L1, Consumed, NT (Tariff 1), Rate 2 | Wh | Read | |||
| Real Energy L2, Consumed, NT (Tariff 1), Rate 2 | Wh | Read | |||
| Real Energy L3, Consumed, NT (Tariff 1), Rate 2 | Wh | Read | |||
| Real Energy L4, Consumed, NT (Tariff 1), Rate 2 | Wh | Read | |||
| Real Energy L1..L3, Consumed, NT (Tariff 1), Rate 2 | Wh | Read | |||
| Real Energy L1..L4, Consumed, NT (Tariff 1), Rate 2 | Wh | Read | |||
| Real Energy L1, Delivered, HT (Tariff 2), Rate 1 | Wh | Read | |||
| Real Energy L2, Delivered, HT (Tariff 2), Rate 1 | Wh | Read | |||
| Real Energy L3, Delivered, HT (Tariff 2), Rate 1 | Wh | Read | |||
| Real Energy L4, Delivered, HT (Tariff 2), Rate 1 | Wh | Read | |||
| Real Energy L1..L3, Delivered, HT (Tariff 2), Rate 1 | Wh | Read | |||
| Real Energy L1..L4, Delivered, HT (Tariff 2), Rate 1 | Wh | Read | |||
| Real Energy L1, Delivered, NT (Tariff 2), Rate 2 | Wh | Read | |||
| Real Energy L2, Delivered, NT (Tariff 2), Rate 2 | Wh | Read | |||
| Real Energy L3, Delivered, NT (Tariff 2), Rate 2 | Wh | Read | |||
| Real Energy L4, Delivered, NT (Tariff 2), Rate 2 | Wh | Read | |||
| Real Energy L1..L3, Delivered, NT (Tariff 2), Rate 2 | Wh | Read | |||
| Real Energy L1..L4, Delivered, NT (Tariff 2), Rate 2 | Wh | Read | |||
| Reactive Energy L1, Inductive | varh | Read | |||
| Reactive Energy L2, Inductive | varh | Read | |||
| Reactive Energy L3, Inductive | varh | Read | |||
| Reactive Energy L4, Inductive | varh | Read | |||
| Reactive Energy L1..L3, Inductive | varh | Read | |||
| Reactive Energy L1..L4, Inductive | varh | Read | |||
| Reactive Energy L1, Capacitive | varh | Read | |||
| Reactive Energy L2, Capacitive | varh | Read | |||
| Reactive Energy L3, Capacitive | varh | Read | |||
| Reactive Energy L4, Capacitive | varh | Read | |||
| Reactive Energy L1..L3, Capacitive | varh | Read | |||
| Reactive Energy L1..L4, Capacitive | varh | Read | |||
| Reactive Energy L1, Inductive, Rate 1 | varh | Read | |||
| Reactive Energy L2, Inductive, Rate 1 | varh | Read | |||
| Reactive Energy L3, Inductive, Rate 1 | varh | Read | |||
| Reactive Energy L4, Inductive, Rate 1 | varh | Read | |||
| Reactive Energy L1..L3, Inductive, Rate 1 | varh | Read | |||
| Reactive Energy L1..L4, Inductive, Rate 1 | varh | Read | |||
| Reactive Energy L1, Inductive, Rate 2 | varh | Read | |||
| Reactive Energy L2, Inductive, Rate 2 | varh | Read | |||
| Reactive Energy L3, Inductive, Rate 2 | varh | Read | |||
| Reactive Energy L4, Inductive, Rate 2 | varh | Read | |||
| Reactive Energy L1..L3, Inductive, Rate 2 | varh | Read | |||
| Reactive Energy L1..L4, Inductive, Rate 2 | varh | Read | |||
| Energy Meter (Counter, Not Scaled), Impulse Input 1 | Read | ||||
| Energy Meter (Counter, Not Scaled), Impulse Input 2 | Read | ||||
| Runtime Of Real And Apparent Energy Meas. | s | Read | |||
| Runtime Of Real And Reactive Energy Meas. | s | Read | |||
| Real Energy, Month High, Jan., Even Year | Wh | Read | |||
| Real Energy, Month High, Feb., Even Year | Wh | Read | |||
| Real Energy, Month High, March, Even Year | Wh | Read | |||
| Real Energy, Month High, April, Even Year | Wh | Read | |||
| Real Energy, Month High, May, Even Year | Wh | Read | |||
| Real Energy, Month High, June, Even Year | Wh | Read | |||
| Real Energy, Month High, July, Even Year | Wh | Read | |||
| Real Energy, Month High, Aug., Even Year | Wh | Read | |||
| Real Energy, Month High, Sep., Even Year | Wh | Read | |||
| Real Energy, Month High, Oct. Even Year | Wh | Read | |||
| Real Energy, Month High, Nov., Even Year | Wh | Read | |||
| Real Energy, Month High, Dec., Even Year | Wh | Read | |||
| Real Energy, Month High, Jan., Uneven Year | Wh | Read | |||
| Real Energy, Month High, Feb., Uneven Year | Wh | Read | |||
| Real Energy, Month High, March, Uneven Year | Wh | Read | |||
| Real Energy, Month High, April, Uneven Year | Wh | Read | |||
| Real Energy, Month High, May, Uneven Year | Wh | Read | |||
| Real Energy, Month High, June, Uneven Year | Wh | Read | |||
| Real Energy, Month High, July, Uneven Year | Wh | Read | |||
| Real Energy, Month High, Aug., Uneven Year | Wh | Read | |||
| Real Energy, Month High, Sep., Uneven Year | Wh | Read | |||
| Real Energy, Month High, Oct.., Uneven Year | Wh | Read | |||
| Real Energy, Month High, Nov., Uneven Year | Wh | Read | |||
| Real Energy, Month High, Dec., Uneven Year | Wh | Read | |||
| Apparent Energy, Month High, Jan., Even Year | VAh | Read | |||
| Apparent Energy, Month High, Feb., Even Year | VAh | Read | |||
| Apparent Energy, Month High, March, Even Year | VAh | Read | |||
| Apparent Energy, Month High, April, Even Year | VAh | Read | |||
| Apparent Energy, Month High, May, Even Year | VAh | Read | |||
| Apparent Energy, Month High, June, Even Year | VAh | Read | |||
| Apparent Energy, Month High, July, Even Year | VAh | Read | |||
| Apparent Energy, Month High, Aug., Even Year | VAh | Read | |||
| Apparent Energy, Month High, Sep., Even Year | VAh | Read | |||
| Apparent Energy, Month High, Oct., Even Year | VAh | Read | |||
| Apparent Energy, Month High, Nov., Even Year | VAh | Read | |||
| Apparent Energy, Month High, Dec., Even Year | VAh | Read | |||
| Apparent Energy, Month High, Jan., Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, Feb., Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, March, Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, April, Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, May, Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, June, Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, July, Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, Aug., Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, Sep., Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, Oct., Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, Nov., Uneven Year | VAh | Read | |||
| Apparent Energy, Month High, Dec., Uneven Year | VAh | Read | |||
| Reactive Energy, Month High, Jan., Even Year | varh | Read | |||
| Reactive Energy, Month High, Feb., Even Year | varh | Read | |||
| Reactive Energy, Month High, March, Even Year | varh | Read | |||
| Reactive Energy, Month High, April, Even Year | varh | Read | |||
| Reactive Energy, Month High, May Even Year | varh | Read | |||
| Reactive Energy, Month High, June, Even Year | varh | Read | |||
| Reactive Energy, Month High, July, Even Year | varh | Read | |||
| Reactive Energy, Month High, Aug., Even Year | varh | Read | |||
| Reactive Energy, Month High, Sep., Even Year | varh | Read | |||
| Reactive Energy, Month High, Oct., Even Year | varh | Read | |||
| Reactive Energy, Month High, Nov., Even Year | varh | Read | |||
| Reactive Energy, Month High, Dec., Even Year | varh | Read | |||
| Reactive Energy, Month High, Jan., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, Feb., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, March, Uneven Year | varh | Read | |||
| Reactive Energy, Month High, April, Uneven Year | varh | Read | |||
| Reactive Energy, Month High, May, Uneven Year | varh | Read | |||
| Reactive Energy, Month High, June., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, July., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, Aug., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, Sep., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, Oct., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, Nov., Uneven Year | varh | Read | |||
| Reactive Energy, Month High, Dez., Uneven Year | varh | Read | |||
| EMAX, 15minutes Month High, Jan., Even Year | W | Read | |||
| EMAX, 15minutes Month High, Feb., Even Year | W | Read | |||
| EMAX, 15minutes Month High, March, Even Year | W | Read | |||
| EMAX, 15minutes Month High, April., Even Year | W | Read | |||
| EMAX, 15minutes Month High, May, Even Year | W | Read | |||
| EMAX, 15minutes Month High, June, Even Year | W | Read | |||
| EMAX, 15minutes Month High, July, Even Year | W | Read | |||
| EMAX, 15minutes Month High, Aug., Even Year | W | Read | |||
| EMAX, 15minutes Month High, Sep., Even Year | W | Read | |||
| EMAX, 15minutes Month High, Oct., Even Year | W | Read | |||
| EMAX, 15minutes Month High, Nov., Even Year | W | Read | |||
| EMAX, 15minutes Month High, Dez., Even Year | W | Read | |||
| EMAX, 15minutes Month High, Jan., Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, Feb., Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, March, Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, April, Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, May, Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, June, Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, July, Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, Aug., Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, Sep., Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, Oct., Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, Nov., Uneven Year | W | Read | |||
| EMAX, 15minutes Month High, Dec., Uneven Year | W | Read | |||
| Time Of 15minutes Month High, Jan., Even Year | s | Read | |||
| Time Of 15minutes Month High, Feb., Even Year | s | Read | |||
| Time Of 15minutes Month High, May, Even Year | s | Read | |||
| Time Of 15minutes Month High, June, Even Year | s | Read | |||
| Time Of 15minutes Month High, July., Even Year | s | Read | |||
| Time Of 15minutes Month High, Aug., Even Year | s | Read | |||
| Time Of 15minutes Month High, Sep., Even Year | s | Read | |||
| Time Of 15minutes Month High, Oct., Even Year | s | Read | |||
| Time Of 15minutes Month High, Nov., Even Year | s | Read | |||
| Time Of 15minutes Month High, Dez., Even Year | s | Read | |||
| Time Of 15minutes Month High, Jan., Uneven Year | s | Read | |||
| Time Of 15minutes Month High, Feb., Uneven Year | s | Read | |||
| Time Of 15minutes Month High, March, Uneven Year | s | Read | |||
| Time Of 15minutes Month High, April, Uneven Year | s | Read | |||
| Time Of 15minutes Month High, May, Uneven Year | s | Read | |||
| Time Of 15minutes Month High, June, Uneven Year | s | Read | |||
| Time Of 15minutes Month High, July, Uneven Year | s | Read | |||
| Time Of 15minutes Month High, Aug., Uneven Year | s | Read | |||
| Time Of 15minutes Month High, Sep., Uneven Year | s | Read | |||
| Time Of 15minutes Month High, Oct., Uneven Year | s | Read | |||
| Time Of 15minutes Month High, Nov., Uneven Year | s | Read | |||
| Time Of 15minutes Month High, Dec., Uneven Year | s | Read | |||
| Reactive Energy L1 (Inductive), Consumed | varh | Read | |||
| Reactive Energy L2 (Inductive), Consumed | varh | Read | |||
| Reactive Energy L3 (Inductive), Consumed | varh | Read | |||
| Reactive Energy L4 (Inductive), Consumed | varh | Read | |||
| Reactive Energy L1..L3 (Inductive), Consumed | varh | Read | |||
| Reactive Energy L1..L4 (Inductive), Consumed | varh | Read | |||
| Reactive Energy L1 (Inductive), Delivered | varh | Read | |||
| Reactive Energy L2 (Inductive), Delivered | varh | Read | |||
| Reactive Energy L3 (Inductive), Delivered | varh | Read | |||
| Reactive Energy L4 (Inductive), Delivered | varh | Read | |||
| Reactive Energy L1..L3 (Inductive), Delivered | varh | Read | |||
| Reactive Energy L1..L4 (Inductive), Delivered | varh | Read | |||
| Reactive Energy L1 (Capacitive), Consumed | varh | Read | |||
| Reactive Energy L2 (Capacitive), Consumed | varh | Read | |||
| Reactive Energy L3 (Capacitive), Consumed | varh | Read | |||
| Reactive Energy L4 (Capacitive), Consumed | varh | Read | |||
| Reactive Energy L1..L3 (Capacitive), Consumed | varh | Read | |||
| Reactive Energy L1..L4 (Capacitive), Consumed | varh | Read | |||
| Reactive Energy L1 (Capacitive), Delivered | varh | Read | |||
| Reactive Energy L2 (Capacitive), Delivered | varh | Read | |||
| Reactive Energy L3 (Capacitive), Delivered | varh | Read | |||
| Reactive Energy L4 (Capacitive), Delivered | varh | Read | |||
| Reactive Energy L1..L3 (Capacitive), Delivered | varh | Read | |||
| Reactive Energy L1..L4 (Capacitive), Delivered | varh | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show voltage, current and power per phase of the main distribution board on one dashboard.
- Send an email alert when voltage THD rises above the limit you set for the installation.
- Keep 365 days of history of frequency, imbalance and flicker to answer power quality complaints.
- Track consumed and delivered energy per tariff and per month for energy reports.
- Compare the maximum demand values of several transformer stations to plan capacity.
Installation
Connect RS485 A and B of the UMG 605-PRO to the RS485 port of the ModbusCloud Gateway and terminate both ends of the bus.
Set the device address and baud rate on the meter; the line uses 8 data bits, no parity and 2 stop bits.
In ModbusCloud, add a Modbus device on the Gateway with the same address and serial settings, then import this template.
Check that the voltages L1-N to L3-N and the frequency arrive with plausible values.
Things to watch for
The meter does not answer on the RS485 bus. What should I check?
The UMG 605-PRO uses 8 data bits, no parity and 2 stop bits; many tools default to 1 stop bit or even parity. Match the address and baud rate set on the meter, swap A and B if nothing comes back, and terminate only the two ends of the bus.
Why do the 32-bit values look scrambled?
The registers deliver big-endian data with the high word first. If a value looks wrong, check the word order in the device settings of ModbusCloud. The same data is also available in little-endian at the address plus 32768, but this template uses the big-endian addresses.
Do I have to apply the transformer ratio myself?
Not for this template. Float and integer values already include the current and voltage transformer ratios set in the meter. Check that the primary and secondary values in the meter match the installed transformers.
Which registers can I write from ModbusCloud?
Only the six voltage phase angle registers are marked as read and write in the address list. Read the current value first and change it only when you know why; the other registers, including transformer ratios and settings, are read only in this template.
Can several meters share one RS485 line?
Yes. Give every meter its own address and use the same baud rate and serial settings on all of them. Run the bus as one line from device to device and terminate both ends.
Want to see how it works?