Janitza Janitza UMG 605-PRO Modbus RTU template

Janitza UMG 605-PRO

Power quality analyser for voltage, current, power, harmonics, flicker and energy per phase and tariff.

The Janitza UMG 605-PRO is a power quality analyser that measures voltage, current, power, harmonics and flicker in low and medium voltage distribution boards. This Modbus RTU template reads all measured, mean, minimum and maximum values and the energy counters per tariff into ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
1299, read and write
Brand
Janitza
Key readings
Voltage L-N and L-L · Current per phase · Real power · Reactive power · Power factor · Frequency · THD voltage and current · Real energy
Available commands
Voltage phase angles
Compatible models
UMG 605-PRO
Last updated

Registers (1299)

1299 read, 6 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Voltage L1-NVRead
Voltage L2-NVRead
Voltage L3-NVRead
Voltage L1-L2VRead
Voltage L2-L3VRead
Voltage L3-L1VRead
Apparent Current, L1-NARead
Apparent Current, L2-NARead
Apparent Current, L3-NARead
Vector Sum; IN=I1+I2+I3ARead
Real Power L1-NWRead
Real Power L2-NWRead
Real Power L3-NWRead
Psum3=P1+P2+P3WRead
Apparent Power L1-NVARead
Apparent Power L2-NVARead
Apparent Power L3-NVARead
Sum; Ssum3=S1+S2+S3VARead
Reactive Power L1 (Fundamental Comp.)varRead
Reactive Power L2 (Fundamental Comp.)varRead
Reactive Power L3 (Fundamental Comp.)varRead
Qsum3=Q1+Q2+Q3 (Fundamental Comp.)varRead
CosPhi; UL1 IL1 (Fundamental Comp.)Read
CosPhi; UL2 IL2 (Fundamental Comp.)Read
CosPhi; UL3 IL3 (Fundamental Comp.)Read
Measured FrequencyHzRead
Rotation Field; 1=right, 0=none, -1=leftRead
Real Energy L1WhRead
Real Energy L2WhRead
Real Energy L3WhRead
Real Energy L1..L3WhRead
Real Energy L1, ConsumedWhRead
Real Energy L2, ConsumedWhRead
Real Energy L3, ConsumedWhRead
Real Energy L1..L3, Consumed, Rate 1WhRead
Real Energy L1, DeliveredWhRead
Real Energy L2, DeliveredWhRead
Real Energy L3, DeliveredWhRead
Real Energy L1..L3, DeliveredWhRead
Apparent Energy L1VAhRead
Apparent Energy L2VAhRead
Apparent Energy L3VAhRead
Apparent Energy L1..L3VAhRead
Reactive Energy L1 (Fundamental Comp.)varhRead
Reactive Energy L2 (Fundamental Comp.)varhRead
Reactive Energy L3 (Fundamental Comp.)varhRead
Reactive Energy L1..L3 (Fundamental Comp.)varhRead
Reactive Energy, Inductive, L1 (Fundamental Comp.)varhRead
Reactive Energy, Inductive, L2 (Fundamental Comp.)varhRead
Reactive Energy, Inductive, L3 (Fundamental Comp.)varhRead
Reactive Energy L1..L3, Ind. (Fundamental Comp.)varhRead
Reactive Energy, Capacitive, L1 (Fundamental Comp.)varhRead
Reactive Energy, Capacitive, L2 (Fundamental Comp.)varhRead
Reactive Energy, Capacitive, L3 (Fundamental Comp.)varhRead
Reactive Energy L1..L3, Cap. (Fundamental Comp.)varhRead
Harmonic, THD,U L1-N%Read
Harmonic, THD,U L2-N%Read
Harmonic, THD,U L3-N%Read
Harmonic, THD,I L1%Read
Harmonic, THD,I L2%Read
Harmonic, THD,I L3%Read
Voltage Phase L-L [0]°Read and write
Voltage Phase L-L [1]°Read and write
Voltage Phase L-L [2]°Read and write
Voltage Phase L-N [0]°Read and write
Voltage Phase L-N [1]°Read and write
Voltage Phase L-N [2]°Read and write
Lock Transformer Ratios, 0=not Locked, 1=lockedRead
Time (UTC)Read
Time (UTC) (Clock)sRead
Day (1..31)Read
Month (0=Jan, .. 11=Dec)Read
YearRead
Hour (1..24)hRead
Minute (1..59)minRead
Second (1..59)sRead
Weekday (0=Sun, .. 6=Sat)Read
Harmonic, THD, U L1-L2%Read
Harmonic, THD, U L2-L3%Read
Harmonic, THD, U L3-L1%Read
Interharmonics, U L1-L2%Read
Interharmonics, U L2-L3%Read
Interharmonics, U L3-L1%Read
Harmonic, THD, U L1-N%Read
Harmonic, THD, U L2-N%Read
Harmonic, THD, U L3-N%Read
Harmonic, THD, U L4-N%Read
Harmonic, THD, I L1-N%Read
Harmonic, THD, I L2-N%Read
Harmonic, THD, I L3-N%Read
Harmonic, THD, I L4-N%Read
Interharmonics, U L1-N%Read
Interharmonics, U L2-N%Read
Interharmonics, U L3-N%Read
Interharmonics, U L4-N%Read
Interharmonics, I L1-N%Read
Interharmonics, I L2-N%Read
Interharmonics, I L3-N%Read
Interharmonics, I L4-N%Read
K-Factor, L1Read
K-Factor, L2Read
K-Factor, L3Read
K-Factor, L4Read
Voltage, L1-NVRead
Voltage, L2-NVRead
Voltage, L3-NVRead
Voltage, L4-NVRead
Apparent Current, L1ARead
Apparent Current, L2ARead
Apparent Current, L3ARead
Apparent Current, L4ARead
Real Power, L1WRead
Real Power, L2WRead
Real Power, L3WRead
Real Power, L4WRead
Reactive Power, L1varRead
Reactive Power, L2varRead
Reactive Power, L3varRead
Reactive Power, L4varRead
Apparent Power, L1 [0]VARead
Apparent Power, L1 [1]VARead
Apparent Power, L1 [2]VARead
Apparent Power, L1 [3]VARead
Distortion Power Factor, L1VARead
Distortion Power Factor, L2VARead
Distortion Power Factor, L3VARead
Distortion Power Factor, L4VARead
Power Factor, L1Read
Power Factor, L2Read
Power Factor, L3Read
Power Factor, L4Read
Phase Conductor Voltage, U L1-L2VRead
Phase Conductor Voltage, U L2-L3VRead
Phase Conductor Voltage, U L3-L1VRead
Phase Conductor Voltage Real Part, U L1-L2VRead
Phase Conductor Voltage Real Part, U L2-L3VRead
Phase Conductor Voltage Real Part, U L3-L1VRead
Phase Conductor Voltage Imaginary Part, U L1-L2VRead
Phase Conductor Voltage Imaginary Part, U L2-L3VRead
Phase Conductor Voltage Imaginary Part, U L3-L1VRead
Vector Sum, IN = I1 + I2 + I3ARead
Vector Sum, I1 + I2 + I3 + I4ARead
Sum, S = S1 + S2 + S3VARead
Sum, P = P1 + P2 + P3WRead
Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3varRead
CosPhi Of Mains Frequency Calculated From Psum3 And Qsum3Read
Sum, S = S1 + S2 + S3 + S4VARead
Sum, P = P1 + P2 + P3 + P4WRead
Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 + Q4varRead
CosPhi Of Mains Frequency Calculated From Psum And QsumRead
Voltage, Real Part, L1-NVRead
Voltage, Real Part, L2-NVRead
Voltage, Real Part, L3-NVRead
Voltage, Real Part, L4-NVRead
Voltage, Imaginary Part, L1-NVRead
Voltage, Imaginary Part, L2-NVRead
Voltage, Imaginary Part, L3-NVRead
Voltage, Imaginary Part, L4-NVRead
Current, Real Part, L1ARead
Current, Real Part, L2ARead
Current, Real Part, L3ARead
Current, Real Part, L4ARead
Current, Imaginary Part, L1ARead
Current, Imaginary Part, L2ARead
Current, Imaginary Part, L3ARead
Current, Imaginary Part, L4ARead
Phase, UL1 IL1°Read
Phase, UL2 IL2°Read
Phase, UL3 IL3°Read
Phase, UL4 IL4°Read
Fund. Power Factor, CosPhi; UL1 IL1Read
Fund. Power Factor, CosPhi; UL2 IL2Read
Fund. Power Factor, CosPhi; UL3 IL3Read
Fund. Power Factor, CosPhi; UL4 IL4Read
Sign, Q L1, +1=ind., -1=cap.Read
Sign, Q L2, +1=ind., -1=cap.Read
Sign, Q L3, +1=ind., -1=cap.Read
VSign, Q L4, +1=ind., -1=cap.Read
Measured Frequency (200 ms)HzRead
Nominal FrequencyHzRead
Zero Sequence, VoltageVRead
Positive Sequence, VoltageVRead
Negative Sequence, VoltageVRead
Unsymmetrical; Voltage%Read
Unsymmetrical; Current%Read
Rotation Field; 1=right, 0=none, -1=left (200 ms)Read
Zero Sequence, CurrentARead
Positive Sequence, CurrentARead
Negative Sequence, CurrentARead
Input 1, Measured ValueWRead
Input 2, Measured ValueWRead
Crest Factor, I L1ARead
Crest Factor, I L2ARead
Crest Factor, I L3ARead
Crest Factor, I L4ARead
Crest Factor, U L1VRead
Crest Factor, U L2VRead
Crest Factor, U L3VRead
Crest Factor, U L4VRead
Crest Factor, U L1-L2VRead
Crest Factor, U L2-L3VRead
Crest Factor, U L3-L1VRead
Peak Value Negative, I L1ARead
Peak Value Negative, I L2ARead
Peak Value Negative, I L3ARead
Peak Value Negative, I L4ARead
Peak Value Negative, U L1-NVRead
Peak Value Negative, U L2-NVRead
Peak Value Negative, U L3-NVRead
Peak Value Negative, U L4-NVRead
Peak Value Positive, I L1ARead
Peak Value Positive, I L2ARead
Peak Value Positive, I L3ARead
Peak Value Positive, I L4ARead
Peak Value Positive, U L1-NVRead
Peak Value Positive, U L2-NVRead
Peak Value Positive, U L3-NVRead
Peak Value Positive, U L4-NVRead
Peak-peak Value Positive, I L1ARead
Peak-peak Value Positive, I L2ARead
Peak-peak Value Positive, I L3ARead
Peak-peak Value Positive, I L4ARead
Peak-peak Value Positive, U L1-NVRead
Peak-peak Value Positive, U L2-NVRead
Peak-peak Value Positive, U L3-NVRead
Peak-peak Value Positive, U L4-NVRead
Under Difference, I L1%Read
Under Difference, I L2%Read
Under Difference, I L3%Read
Under Difference, I L4%Read
Under Difference, U L1 (61000-4-30)%Read
Under Difference, U L2 (61000-4-30)%Read
Under Difference, U L3 (61000-4-30)%Read
Under Difference, U L4 (61000-4-30)%Read
Over Difference, I L1%Read
Over Difference, I L2%Read
Over Difference, I L3%Read
Over Difference, I L4%Read
Over Difference, U L1 (61000-4-30)%Read
Over Difference, U L2 (61000-4-30)%Read
Over Difference, U L3 (61000-4-30)%Read
Over Difference, U L4 (61000-4-30)%Read
Peak Value Negative, U L1-L2VRead
Peak Value Negative, U L2-L3VRead
Peak Value Negative, U L3-L1VRead
Peak Value Positive, U L1-L2VRead
Peak Value Positive, U L2-L3VRead
Peak Value Positive, U L3-L1VRead
Peak-peak Value, U L1-L2VRead
Peak-peak Value, U L2-L3VRead
Peak-peak Value, U L3-L1VRead
Under Difference, U L1-L2 (61000-4-30)%Read
Under Difference, U L2-L3 (61000-4-30)%Read
Under Difference, U L3-L1 (61000-4-30)%Read
Over Difference, U L1-L2 (61000-4-30)%Read
Over Difference, U L2-L3 (61000-4-30)%Read
Over Difference, U L3-L1 (61000-4-30)%Read
Current Flicker Pf5, L1-NRead
Current Flicker Pf5, L2-NRead
Current Flicker Pf5, L3-NRead
Current Flicker Pf5, L4-NRead
Short-term Flicker Level, Pst (10m), L1-NRead
Short-term Flicker Level, Pst (10m), L2-NRead
Short-term Flicker Level, Pst (10m), L3-NRead
Short-term Flicker Level, Pst (10m), L4-NRead
Long-term Flicker Level, Plt (2h), L1-NRead
Long-term Flicker Level, Plt (2h), L2-NRead
Long-term Flicker Level, Plt (2h), L3-NRead
Long-term Flicker Level, Plt (2h), L4-NRead
Ripple Control Signal, U L1-N (61000-4-30)VRead
Ripple Control Signal, U L2-N (61000-4-30)VRead
Ripple Control Signal, U L3-N (61000-4-30)VRead
Ripple Control Signal, U L4-N (61000-4-30)VRead
Ripple Control Signal, I L1ARead
Ripple Control Signal, I L2ARead
Ripple Control Signal, I L3ARead
Ripple Control Signal, I L4ARead
Ripple Control Signal, U L1-L2 (61000-4-30)VRead
Ripple Control Signal, U L2-L3 (61000-4-30)VRead
Ripple Control Signal, U L3-L1 (61000-4-30)VRead
Internal Temperature°CRead
PF_Total=P_Sum3/S_Sum3 Internal TemperatureRead
IN Total Demand Distortion [0]%Read
IN Total Demand Distortion [1]%Read
IN Total Demand Distortion [2]%Read
IN Total Demand Distortion [3]%Read
IN Total Demand Distortion%Read
ULN Crest Faktor [0]Read
ULN Crest Faktor [1]Read
ULN Crest Faktor [2]Read
ULL Crest Faktor [0]Read
ULL Crest Faktor [1]Read
ULL Crest Faktor [2]Read
IN Crest Faktor [0]Read
IN Crest Faktor [1]Read
IN Crest Faktor [2]Read
IN Crest Faktor [3]Read
Maximum Demand Load Current, L1..L3Read
Maximum Demand Load Current, L4Read
Average, U L1-NVRead
Average, U L2-NVRead
Average, U L3-NVRead
Average, U L4-NVRead
Average, U L1-L2VRead
Average, U L2-L3VRead
Average, U L3-L4VRead
Mean Value Of The Crest Factor, U L1-N%Read
Mean Value Of The Crest Factor, U L2-N%Read
Mean Value Of The Crest Factor, U L3-N%Read
Mean Value Of The Crest Factor, U L4-N%Read
Mean Value Of The Crest Factor, U L1-L2%Read
Mean Value Of The Crest Factor, U L2-L3%Read
Mean Value Of The Crest Factor, U L3-L4%Read
Mean Value Zero SequenceVRead
Mean Value Positive SequenceVRead
Mean Value Negative SequenceVRead
Mean Value THD U L1-N%Read
Mean Value THD U L2-N%Read
Mean Value THD U L3-N%Read
Mean Value THD U L4-N%Read
Mean Value ZHD U L1-N%Read
Mean Value ZHD U L2-N%Read
Mean Value ZHD U L3-N%Read
Mean Value ZHD U L4-N%Read
Over Difference, U L1 (61000-4-30) (Mean)%Read
Over Difference, U L2 (61000-4-30) (Mean)%Read
Over Difference, U L3 (61000-4-30) (Mean)%Read
Over Difference, U L4 (61000-4-30) (Mean)%Read
Under Difference, U L1 (61000-4-30) (Mean)%Read
Under Difference, U L2 (61000-4-30) (Mean)%Read
Under Difference, U L3 (61000-4-30) (Mean)%Read
Under Difference, U L4 (61000-4-30) (Mean)%Read
Peak Value Negative, U L1-N (Mean)VRead
Peak Value Negative, U L2-N (Mean)VRead
Peak Value Negative, U L3-N (Mean)VRead
Peak Value Negative, U L4-N (Mean)VRead
Peak Value Positive, U L1-N (Mean)VRead
Peak Value Positive, U L2-N (Mean)VRead
Peak Value Positive, U L3-N (Mean)VRead
Peak Value Positive, U L4-N (Mean)VRead
Peak-peak Value Positive, U L1-N (Mean)VRead
Peak-peak Value Positive, U L2-N (Mean)VRead
Peak-peak Value Positive, U L3-N (Mean)VRead
Peak-peak Value Positive, U L4-N (Mean)VRead
Harmonic, THD, U L1-L2 (Mean)%Read
Harmonic, THD, U L2-L3 (Mean)%Read
Harmonic, THD, U L3-L1 (Mean)%Read
Interharmonics, U L1-L2 (Mean)%Read
Interharmonics, U L2-L3 (Mean)%Read
Interharmonics, U L3-L1 (Mean)%Read
Over Difference, U L1-L2 (61000-4-30) (Mean)%Read
Over Difference, U L2-L3 (61000-4-30) (Mean)%Read
Over Difference, U L3-L1 (61000-4-30) (Mean)%Read
Under Difference, U L1-L2 (61000-4-30) (Mean)%Read
Under Difference, U L2-L3 (61000-4-30) (Mean)%Read
Under Difference, U L3-L1 (61000-4-30) (Mean)%Read
Peak Value Negative, U L1-L2 (Mean)VRead
Peak Value Negative, U L2-L3 (Mean)VRead
Peak Value Negative, U L3-L1 (Mean)VRead
Peak Value Positive, U L1-L2 (Mean)VRead
Peak Value Positive, U L2-L3 (Mean)VRead
Peak Value Positive, U L3-L1 (Mean)VRead
Peak-peak Value, U L1-L2 (Mean)VRead
Peak-peak Value, U L2-L3 (Mean)VRead
Peak-peak Value, U L3-L1 (Mean)VRead
Star Connection Voltage (Mean)VRead
Unsymmetrical; Voltage (Mean)%Read
Measured Frequency (Mean)HzRead
Nominal Frequency (Mean)HzRead
Average, P L1WRead
Average, P L2WRead
Average, P L3WRead
Average, P L4WRead
Average, Psum=P1+P2+P3+P4WRead
Average, Qsum=Q1+Q2+Q3+Q4varRead
Average, Q L1varRead
Average, Q L2varRead
Average, Q L3varRead
Average, Q L4varRead
Average, Psum3=P1+P2+P3WRead
Average, Qsum3=Q1+Q2+Q3varRead
Average, I L1ARead
Average, I L2ARead
Average, I L3ARead
Average, I L4ARead
Average, S L1VARead
Average, S L2VARead
Average, S L3VARead
Average, S L4VARead
Average, IN=I1+I2+I3ARead
Average, Isum=I1+I2+I3+I4ARead
Average, Ssum3=S1+S2+S3VARead
Average, Ssum=S1+S2+S3+S4VARead
Harmonic, THD, I L1-N (Mean)%Read
Harmonic, THD, I L2-N (Mean)%Read
Harmonic, THD, I L3-N (Mean)%Read
Harmonic, THD, I L4-N (Mean)%Read
Interharmonics, I L1-N (Mean)%Read
Interharmonics, I L2-N (Mean)%Read
Interharmonics, I L3-N (Mean)%Read
Interharmonics, I L4-N (Mean)%Read
IN Crest Faktor [0] (Mean)%Read
IN Crest Faktor [1] (Mean)%Read
IN Crest Faktor [2] (Mean)%Read
IN Crest Faktor [3] (Mean)%Read
Average, Current, Zero SequenceARead
Average, Current, Positive SequenceARead
Average, Current, Negative SequenceARead
Unsymmetrical; Current (Mean)%Read
Over Difference, I L1 (Mean)%Read
Over Difference, I L2 (Mean)%Read
Over Difference, I L3 (Mean)%Read
Over Difference, I L4 (Mean)%Read
Under Difference, I L1 (Mean)%Read
Under Difference, I L2 (Mean)%Read
Under Difference, I L3 (Mean)%Read
Under Difference, I L4 (Mean)%Read
Peak Value Negative, I L1 (Mean)ARead
Peak Value Negative, I L2 (Mean)ARead
Peak Value Negative, I L3 (Mean)ARead
Peak Value Negative, I L4 (Mean)ARead
Peak Value Positive, I L1 (Mean)ARead
Peak Value Positive, I L2 (Mean)ARead
Peak Value Positive, I L3 (Mean)ARead
Peak Value Positive, I L4 (Mean)ARead
Peak-peak Value Positive, I L1 (Mean)ARead
Peak-peak Value Positive, I L2 (Mean)ARead
Peak-peak Value Positive, I L3 (Mean)ARead
Peak-peak Value Positive, I L4 (Mean)ARead
Current Flicker Pf5, L1-N (Mean)Read
Current Flicker Pf5, L2-N (Mean)Read
Current Flicker Pf5, L3-N (Mean)Read
Current Flicker Pf5, L4-N (Mean)Read
Short-term Flicker Level, Pst (10m), L1-N (Mean)Read
Short-term Flicker Level, Pst (10m), L2-N (Mean)Read
Short-term Flicker Level, Pst (10m), L3-N (Mean)Read
Short-term Flicker Level, Pst (10m), L4-N (Mean)Read
Long-term Flicker Level, Plt (2h), L1-N (Mean)Read
Long-term Flicker Level, Plt (2h), L2-N (Mean)Read
Long-term Flicker Level, Plt (2h), L3-N (Mean)Read
Long-term Flicker Level, Plt (2h), L4-N (Mean)Read
Ripple Control Signal, I L1 (Mean)ARead
Ripple Control Signal, I L2 (Mean)ARead
Ripple Control Signal, I L3 (Mean)ARead
Ripple Control Signal, I L4 (Mean)ARead
Ripple Control Signal, U L1-L2 (61000-4-30) (Mean)VRead
Ripple Control Signal, U L2-L3 (61000-4-30) (Mean)VRead
Ripple Control Signal, U L3-L1 (61000-4-30) (Mean)VRead
Power Factor, L1 (Mean)%Read
Power Factor, L2 (Mean)%Read
Power Factor, L3 (Mean)%Read
Power Factor, L4 (Mean)%Read
Distortion Power Factor, L1 (Mean)varRead
Distortion Power Factor, L2 (Mean)varRead
Distortion Power Factor, L3 (Mean)varRead
Distortion Power Factor, L4 (Mean)varRead
K-Factor, L1 (Mean)%Read
K-Factor, L2 (Mean)%Read
K-Factor, L3 (Mean)%Read
K-Factor, L4 (Mean)%Read
Input 1, Measured Value (Mean)WRead
Input 2, Measured Value (Mean)WRead
Internal Temperature (Mean)°CRead
ULN_AVG_SUMVRead
ULL_AVG_SUMVRead
ILN_AVG_SUMARead
TDD_AVG%Read
Minimum, U L1-NVRead
Minimum, U L2-NVRead
Minimum, U L3-NVRead
Minimum, U L4-NVRead
Minimum, U L1-L2VRead
Minimum, U L2-L3VRead
Minimum, U L3-L4VRead
Crest Factor, U L1 (Min)%Read
Crest Factor, U L2 (Min)%Read
Crest Factor, U L3 (Min)%Read
Crest Factor, U L4 (Min)%Read
Crest Factor, U L1-L2 (Min)%Read
Crest Factor, U L2-L3 (Min)%Read
Crest Factor, U L3-L1 (Min)%Read
Zero Sequence, Voltage (Min)VRead
Positive Sequence, Voltage (Min)VRead
Negative Sequence, Voltage (Min)VRead
Ripple Control Signal, U L1-N (61000-4-30) (Min)VRead
Ripple Control Signal, U L2-N (61000-4-30) (Min)VRead
Ripple Control Signal, U L3-N (61000-4-30) (Min)VRead
Ripple Control Signal, U L4-N (61000-4-30) (Min)VRead
Harmonic, THD, U L1-N (Min)%Read
Harmonic, THD, U L2-N (Min)%Read
Harmonic, THD, U L3-N (Min)%Read
Harmonic, THD, U L4-N (Min)%Read
Interharmonics, U L1-N (Min)%Read
Interharmonics, U L2-N (Min)%Read
Interharmonics, U L3-N (Min)%Read
Interharmonics, U L4-N (Min)%Read
Over Difference, U L1 (61000-4-30) (Min)%Read
Over Difference, U L2 (61000-4-30) (Min)%Read
Over Difference, U L3 (61000-4-30) (Min)%Read
Over Difference, U L4 (61000-4-30) (Min)%Read
Under Difference, U L1 (61000-4-30) (Min)%Read
Under Difference, U L2 (61000-4-30) (Min)%Read
Under Difference, U L3 (61000-4-30) (Min)%Read
Under Difference, U L4 (61000-4-30) (Min)%Read
Peak Value Negative, U L1-N (Min)VRead
Peak Value Negative, U L2-N (Min)VRead
Peak Value Negative, U L3-N (Min)VRead
Peak Value Negative, U L4-N (Min)VRead
Peak Value Positive, U L1-N (Min)VRead
Peak Value Positive, U L2-N (Min)VRead
Peak Value Positive, U L3-N (Min)VRead
Peak Value Positive, U L4-N (Min)VRead
Peak-peak Value Positive, U L1-N (Min)VRead
Peak-peak Value Positive, U L2-N (Min)VRead
Peak-peak Value Positive, U L3-N (Min)VRead
Peak-peak Value Positive, U L4-N (Min)VRead
Harmonic, THD, U L1-L2 (Min)%Read
Harmonic, THD, U L2-L3 (Min)%Read
Harmonic, THD, U L3-L1 (Min)%Read
Interharmonics, U L1-L2 (Min)%Read
Interharmonics, U L2-L3 (Min)%Read
Interharmonics, U L3-L1 (Min)%Read
Over Difference, U L1-L2 (61000-4-30) (Min)%Read
Over Difference, U L2-L3 (61000-4-30) (Min)%Read
Over Difference, U L3-L1 (61000-4-30) (Min)%Read
Under Difference, U L1-L2 (61000-4-30) (Min)%Read
Under Difference, U L2-L3 (61000-4-30) (Min)%Read
Under Difference, U L3-L1 (61000-4-30) (Min)%Read
Peak Value Negative, U L1-L2 (Min)VRead
Peak Value Negative, U L2-L3 (Min)VRead
Peak Value Negative, U L3-L1 (Min)VRead
Peak Value Positive, U L1-L2 (Min)VRead
Peak Value Positive, U L2-L3 (Min)VRead
Peak Value Positive, U L3-L1 (Min)VRead
Peak-peak Value, U L1-L2 (Min)VRead
Peak-peak Value, U L2-L3 (Min)VRead
Peak-peak Value, U L3-L1 (Min)VRead
Star Connection Voltage (Min)VRead
Unsymmetrical; Voltage (Min)%Read
Measured Frequency (Min)HzRead
Nominal Frequency (Min)HzRead
Real Power, L1 (Min)WRead
Real Power, L2 (Min)WRead
Real Power, L3 (Min)WRead
Real Power, L4 (Min)WRead
Sum, P = P1 + P2 + P3 + P4 (Min)WRead
Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 + Q4 (Min)varRead
Reactive Power, L1 (Min)varRead
Reactive Power, L2 (Min)varRead
Reactive Power, L3 (Min)varRead
Reactive Power, L4 (Min)varRead
Sum, P = P1 + P2 + P3 (Min)WRead
Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 (Min)varRead
Internal Temperature (Min)°CRead
Maximum, U L1-NVRead
Maximum, U L2-NVRead
Maximum, U L3-NVRead
Maximum, U L4-NVRead
Maximum, U L1-L2VRead
Maximum, U L2-L3VRead
Maximum, U L3-L4VRead
Crest Factor, U L1 (Max)%Read
Crest Factor, U L2 (Max)%Read
Crest Factor, U L3 (Max)%Read
Crest Factor, U L4 (Max)%Read
Crest Factor, U L1-L2 (Max)%Read
Crest Factor, U L2-L3 (Max)%Read
Crest Factor, U L3-L1 (Max)%Read
Zero Sequence, Voltage (Max)VRead
Positive Sequence, Voltage (Max)VRead
Negative Sequence, Voltage (Max)VRead
Ripple Control Signal, U L1-N (61000-4-30) (Max)VRead
Ripple Control Signal, U L2-N (61000-4-30) (Max)VRead
Ripple Control Signal, U L3-N (61000-4-30) (Max)VRead
Ripple Control Signal, U L4-N (61000-4-30) (Max)VRead
Harmonic, THD, U L1-N (Max)%Read
Harmonic, THD, U L2-N (Max)%Read
Harmonic, THD, U L3-N (Max)%Read
Harmonic, THD, U L4-N (Max)%Read
Interharmonics, U L1-N (Max)%Read
Interharmonics, U L2-N (Max)%Read
Interharmonics, U L3-N (Max)%Read
Interharmonics, U L4-N (Max)%Read
Over Difference, U L1 (61000-4-30) (Max)%Read
Over Difference, U L2 (61000-4-30) (Max)%Read
Over Difference, U L3 (61000-4-30) (Max)%Read
Over Difference, U L4 (61000-4-30) (Max)%Read
Under Difference, U L1 (61000-4-30) (Max)%Read
Under Difference, U L2 (61000-4-30) (Max)%Read
Under Difference, U L3 (61000-4-30) (Max)%Read
Under Difference, U L4 (61000-4-30) (Max)%Read
Peak Value Negative, U L1-N (Max)VRead
Peak Value Negative, U L2-N (Max)VRead
Peak Value Negative, U L3-N (Max)VRead
Peak Value Negative, U L4-N (Max)VRead
Peak Value Positive, U L1-N (Max)VRead
Peak Value Positive, U L2-N (Max)VRead
Peak Value Positive, U L3-N (Max)VRead
Peak Value Positive, U L4-N (Max)VRead
Peak-peak Value Positive, U L1-N (Max)VRead
Peak-peak Value Positive, U L2-N (Max)VRead
Peak-peak Value Positive, U L3-N (Max)VRead
Peak-peak Value Positive, U L4-N (Max)VRead
Harmonic, THD, U L1-L2 (Max)%Read
Harmonic, THD, U L2-L3 (Max)%Read
Harmonic, THD, U L3-L1 (Max)%Read
Interharmonics, U L1-L2 (Max)%Read
Interharmonics, U L2-L3 (Max)%Read
Interharmonics, U L3-L1 (Max)%Read
Over Difference, U L1-L2 (61000-4-30) (Max)%Read
Over Difference, U L2-L3 (61000-4-30) (Max)%Read
Over Difference, U L3-L1 (61000-4-30) (Max)%Read
Under Difference, U L1-L2 (61000-4-30) (Max)%Read
Under Difference, U L2-L3 (61000-4-30) (Max)%Read
Under Difference, U L3-L1 (61000-4-30) (Max)%Read
Peak Value Negative, U L1-L2 (Max)VRead
Peak Value Negative, U L2-L3 (Max)VRead
Peak Value Negative, U L3-L1 (Max)VRead
Peak Value Positive, U L1-L2 (Max)VRead
Peak Value Positive, U L2-L3 (Max)VRead
Peak Value Positive, U L3-L1 (Max)VRead
Peak-peak Value, U L1-L2 (Max)VRead
Peak-peak Value, U L2-L3 (Max)VRead
Peak-peak Value, U L3-L1 (Max)VRead
Star Connection Voltage (Max)VRead
Unsymmetrical; Voltage (Max)%Read
Measured Frequency (Max)HzRead
Nominal Frequency (Max)HzRead
Real Power, L1 (Max)WRead
Real Power, L2 (Max)WRead
Real Power, L3 (Max)WRead
Real Power, L4 (Max)WRead
Sum, P = P1 + P2 + P3 + P4 (Max)WRead
Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 + Q4 (Max)varRead
Reactive Power, L1 (Max)varRead
Reactive Power, L2 (Max)varRead
Reactive Power, L3 (Max)varRead
Reactive Power, L4 (Max)varRead
Sum, P = P1 + P2 + P3 (Max)WRead
Mains Frequency Reactive Power Sum, Q = Q1 + Q2 + Q3 (Max)varRead
Apparent Current, L1 (Max)ARead
Apparent Current, L2 (Max)ARead
Apparent Current, L3 (Max)ARead
Apparent Current, L4 (Max)ARead
Apparent Power, L1 [0] (Max)VARead
Apparent Power, L1 [1] (Max)VARead
Apparent Power, L1 [2] (Max)VARead
Apparent Power, L1 [3] (Max)VARead
Vector Sum, IN = I1 + I2 + I3 (Max)ARead
Vector Sum, I1 + I2 + I3 + I4 (Max)ARead
Sum, S = S1 + S2 + S3 (Max)VARead
Sum, S = S1 + S2 + S3 + S4 (Max)VARead
Harmonic, THD, I L1-N (Max)%Read
Harmonic, THD, I L2-N (Max)%Read
Harmonic, THD, I L3-N (Max)%Read
Harmonic, THD, I L4-N (Max)%Read
Interharmonics, I L1-N (Max)%Read
Interharmonics, I L2-N (Max)%Read
Interharmonics, I L3-N (Max)%Read
Interharmonics, I L4-N (Max)%Read
IN Crest Faktor [0] (Max)%Read
IN Crest Faktor [1] (Max)%Read
IN Crest Faktor [2] (Max)%Read
IN Crest Faktor [3] (Max)%Read
Zero Sequence, Current (Max)ARead
Positive Sequence, Current (Max)ARead
Negative Sequence, Current (Max)ARead
Unsymmetrical; Current (Max)%Read
Over Difference, I L1 (Max)%Read
Over Difference, I L2 (Max)%Read
Over Difference, I L3 (Max)%Read
Over Difference, I L4 (Max)%Read
Under Difference, I L1 (Max)%Read
Under Difference, I L2 (Max)%Read
Under Difference, I L3 (Max)%Read
Under Difference, I L4 (Max)%Read
Peak Value Negative, I L1 (Max)ARead
Peak Value Negative, I L2 (Max)ARead
Peak Value Negative, I L3 (Max)ARead
Peak Value Negative, I L4 (Max)ARead
Peak Value Positive, I L1 (Max)ARead
Peak Value Positive, I L2 (Max)ARead
Peak Value Positive, I L3 (Max)ARead
Peak Value Positive, I L4 (Max)ARead
Peak-peak Value Positive, I L1 (Max)ARead
Peak-peak Value Positive, I L2 (Max)ARead
Peak-peak Value Positive, I L3 (Max)ARead
Peak-peak Value Positive, I L4 (Max)ARead
Current Flicker Pf5, L1-N (Max)Read
Current Flicker Pf5, L2-N (Max)Read
Current Flicker Pf5, L3-N (Max)Read
Current Flicker Pf5, L4-N (Max)Read
Short-term Flicker Level, Pst (10m), L1-N (Max)Read
Short-term Flicker Level, Pst (10m), L2-N (Max)Read
Short-term Flicker Level, Pst (10m), L3-N (Max)Read
Short-term Flicker Level, Pst (10m), L4-N (Max)Read
Long-term Flicker Level, Plt (2h), L1-N (Max)Read
Long-term Flicker Level, Plt (2h), L2-N (Max)Read
Long-term Flicker Level, Plt (2h), L3-N (Max)Read
Long-term Flicker Level, Plt (2h), L4-N (Max)Read
Ripple Control Signal, I L1 (Max)ARead
Ripple Control Signal, I L2 (Max)ARead
Ripple Control Signal, I L3 (Max)ARead
Ripple Control Signal, I L4 (Max)ARead
Ripple Control Signal, U L1-L2 (61000-4-30) (Max)VRead
Ripple Control Signal, U L2-L3 (61000-4-30) (Max)VRead
Ripple Control Signal, U L3-L1 (61000-4-30) (Max)VRead
Power Factor, L1 (Max)%Read
Power Factor, L2 (Max)%Read
Power Factor, L3 (Max)%Read
Power Factor, L4 (Max)%Read
Distortion Power Factor, L1 (Max)varRead
Distortion Power Factor, L2 (Max)varRead
Distortion Power Factor, L3 (Max)varRead
Distortion Power Factor, L4 (Max)varRead
K-Factor, L1 (Max)%Read
K-Factor, L2 (Max)%Read
K-Factor, L3 (Max)%Read
K-Factor, L4 (Max)%Read
Input 1, Measured Value (Max)WRead
Input 2, Measured Value (Max)WRead
Internal Temperature (Max)°CRead
Star Connection VoltageVRead
Status Digital Output 1, 0=not Active, 1=activeRead
Status Digital Output 2, 0=not Active, 1=activeRead
Status Digital Input 1, 0=not Active, 1=active [0]Read
Status Digital Input 1, 0=not Active, 1=active [1]Read
Event CounterRead
Flag CounterRead
Error Counter, TransientsRead
Error Counter, Half-cycle Effective ValuesRead
Error Counter, Receive RS232Read
Error Counter, Send RS232Read
Error Counter, RS232Read
Error Counter, Receive RS485Read
Error Counter, Send RS485Read
Error Counter, RS485Read
1= Delete All Real Energy CountersRead
1= Delete All Reactive Energy CountersRead
RUN (Internal)Read
L1, L2, L3; Current Transformer, PrimaryARead
L4; Current Transformer, PrimaryARead
L1, L2, L3; Current Transf., SecondaryARead
L4; Current Transformer, SecondaryARead
L1, L2, L3; Voltage Transformer, PrimaryVRead
L4; Voltage Transformer, PrimaryVRead
L1, L2, L3; Spannungswandler, SekundärVRead
L4; Spannungswandler, SekundärVRead
Nominal Current Transf.; I L1, I L2, I L3ARead
Nominal Current Transformer; I L4ARead
Nominal Voltage; L1, L2, L3VRead
Nominal Voltage; L4VRead
Nominal Current; L1, L2, L3ARead
Nominal Current; L4ARead
TRNS_DELTA [0] (Internal)%Read
TRNS_DELTA [1] (Internal)%Read
TRNS_I_ABS [0] (Internal)%Read
TRNS_I_ABS [1] (Internal)%Read
TRNS_U_ABS [0] (Internal)%Read
TRNS_U_ABS [1] (Internal)%Read
I_EVT_MAX [0] (Internal)%Read
I_EVT_MAX [1] (Internal)%Read
U_EVT_MAX [0] (Internal)%Read
U_EVT_MAX [1] (Internal)%Read
U_EVT_MIN [0] (Internal)%Read
U_EVT_MIN [1] (Internal)%Read
U_EVT_OFF [0] (Internal)%Read
U_EVT_OFF [1] (Internal)%Read
Nominal Frequency 50Hz Or 60HzHzRead
FLICKER_SYSTEM (Internal)Read
TRNS_PRE (Internal)Read
TRNS_POST (Internal)Read
DEV_NAME (Internal)Read
DEV_DESC (Internal)Read
LANGUAGE (Internal)Read
SERNR (Internal)Read
PRODNR (Internal)Read
MBUSADDR (Internal)Read
MODE485 (Internal)Read
BAUD485 (Internal)Read
BAUD232 (Internal)Read
MODE232 (Internal)Read
Network AddressRead
Network MaskRead
GatewayRead
1=DHCP On, 0=DHCP OffRead
ContrastRead
Type Temperature SensorRead
Status, Button 1Read
Status, Button 2Read
Status, Button 3Read
DEBUG_IP (Internal)Read
Time ZonesRead
STIME (Internal)sRead
Start Day Of Summer/winter Switchover (Spring)Read
Start Hour Of Summer/winter SwitchoverhRead
Start Month Of Summer/winter SwitchoverRead
Start Minute Of Summer/winter SwitchoverminRead
Summer/winter Switchover (Spring)Read
Start Day Of Summer/winter Switchover (Autumn)Read
Start Hour Of Summer/winter Switchover (Other)hRead
Start Month Of Summer/winter Switchover (Other)Read
Start Minute Of Summer/winter Switchover (Other)minRead
Summer/Winter Switchover (Autumn)Read
EVT_VAL_PRE (Internal)Read
EVT_VAL_POST (Internal)Read
TRNS_MODE (Internal)Read
EVT_MODE (Internal)Read
CON_AUX_MODE (Internal)Read
CON_MODE (Internal)Read
PHASE_MODE (Internal)Read
COLOR [0] (Internal)Read
COLOR [1] (Internal)Read
COLOR [2] (Internal)Read
COLOR [3] (Internal)Read
COLOR [4] (Internal)Read
COLOR [5] (Internal)Read
COLOR [6] (Internal)Read
COLOR [7] (Internal)Read
GUEST_PASSWD (Internal)Read
USER_PASSWD (Internal)Read
ADMIN_PASSWD (Internal)Read
PULSWERT [0] (Internal)Read
PULSWERT [1] (Internal)Read
MAXSIZE_REC (Internal)%Read
MAXSIZE_TRNS (Internal)%Read
MAXSIZE_VWW (Internal)%Read
MAXSIZE_EVT (Internal)%Read
MAXSIZE_FLAGS (Internal)%Read
TFTP_FILE_NR (Internal)Read
TFTP_NEWFILE (Internal)Read
DIGOUTEVT [0] (Internal)Read
DIGOUTEVT [1] (Internal)Read
DIGOUTEVT_TIME [0] (Internal)sRead
DIGOUTEVT_TIME [1] (Internal)sRead
INVERT_DIGOUT [0] (Internal)Read
INVERT_DIGOUT [1] (Internal)Read
KORR_INT (Internal)Read
QUARZ_KORR_NTP (Internal)ppmRead
BACNET_SENDIAM_TIME (Internal)sRead
HTML_PORT (Internal)Read
IP_ADDR_STR (Internal)Read
IP_GATEWAY_STR (Internal)Read
IP_MASK_STR (Internal)Read
NAMESRV_IP (Internal)Read
NTPSRV_IP (Internal)Read
HOSTNAME (Internal)Read
EVT_NAME (Internal)Read
FL_NAME (Internal)Read
TR_NAME (Internal)Read
HWW_NAME (Internal)Read
FILEMAGIC (Internal)Read
MODE_NTP (Internal)Read
QUARZ_KORR (Internal)ppmRead
RC_FREQ (Internal)HzRead
TFTP_PRG1 Part 1 (Internal)Read
TFTP_PRG1 Part 2 (Internal)Read
TFTP_PRG2 Part 1 (Internal)Read
TFTP_PRG2 Part 2 (Internal)Read
TFTP_PRG3 Part 1 (Internal)Read
TFTP_PRG3 Part 2 (Internal)Read
TFTP_PRG4 Part 1 (Internal)Read
TFTP_PRG4 Part 2 (Internal)Read
TFTP_PRG5 Part 1 (Internal)Read
TFTP_PRG5 Part 2 (Internal)Read
TFTP_PRG6 Part 1 (Internal)Read
TFTP_PRG6 Part 2 (Internal)Read
TFTP_REC Part 1 (Internal)Read
TFTP_REC Part 2 (Internal)Read
TFTP_DISPLAY Part 1 (Internal)Read
TFTP_DISPLAY Part 2 (Internal)Read
RELEASE (Internal)Read
DOWNLOAD (Internal)Read
DUMMY (Internal)Read
MASTER_TIMEOUT (Internal)msRead
ED_PASSWD (Internal)Read
HTML_PASSWD (Internal)Read
PASSWD_MODE (Internal)Read
CHALLENGE (Internal)Read
BACNET_PASSWORD (Internal)Read
FORBID_CFG_HTML (Internal)Read
FORBID_FTP (Internal)Read
FORBID_CFG_FTP (Internal)Read
FORBID_MODETH (Internal)Read
FORBID_CFG_MODETH (Internal)Read
FORBID_BACNET (Internal)Read
IP_UP (Internal)Read
SYSVAR_CNT (Internal)Read
SEQ_IP0 (Internal)Read
SEQ_IP1 (Internal)Read
SEQ_IP2 (Internal)Read
SEQ_IP3 (Internal)Read
SEQ_IP4 (Internal)Read
SEQ_IP5 (Internal)Read
SEQ_IP6 (Internal)Read
SEQ_IP7 (Internal)Read
CH_MAP [0] (Internal)Read
CH_MAP [1] (Internal)Read
CH_MAP [2] (Internal)Read
CH_MAP [3] (Internal)Read
CH_MAP [4] (Internal)Read
CH_MAP [5] (Internal)Read
CH_MAP [6] (Internal)Read
CH_MAP [7] (Internal)Read
NTP_DIV (Internal)sRead
NTP_TURNAROUND (Internal)sRead
NTP_KORR (Internal)ppmRead
RX_ETH_COUNT (Internal)Read
TX_ETH_COUNT (Internal)Read
ERR_ETH_COUNT (Internal)Read
RX_NTP_COUNT (Internal)Read
TX_NTP_COUNT (Internal)Read
ERR_NTP_COUNT (Internal)Read
RX_DNS_COUNT (Internal)Read
TX_DNS_COUNT (Internal)Read
ERR_DNS_COUNT (Internal)Read
RX_DHCP_COUNT (Internal)Read
TX_DHCP_COUNT (Internal)Read
ERR_DHCP_COUNT (Internal)Read
TX_EMAIL_COUNT (Internal)Read
ERR_EMAIL_COUNT (Internal)Read
MTU_SIZE (Internal)Read
10ms Only For Internal UseRead
Real Energy, Consumption, Tariff 3, L1WhRead
Real Energy, Consumption, Tariff 3, L2WhRead
Real Energy, Consumption, Tariff 3, L3WhRead
Real Energy, Consumption, Tariff 3, L4WhRead
Real Energy, Consump., Tariff 3, L1..L3WhRead
Real Energy, Consump., Tariff 3, L1..L4WhRead
Real Energy, Consumption, Tariff 4, L1WhRead
Real Energy, Consumption, Tariff 4, L2WhRead
Real Energy, Consumption, Tariff 4, L3WhRead
Real Energy, Consumption, Tariff 4, L4WhRead
Real Energy, Consump., Tariff 4, L1..L3WhRead
Real Energy, Consump., Tariff 4, L1..L4WhRead
Real Energy, Supply, Tariff 3, L1WhRead
Real Energy, Supply, Tariff 3, L2WhRead
Real Energy, Supply, Tariff 3, L3WhRead
Real Energy, Supply, Tariff 3, L4WhRead
Real Energy, Supply, Tariff 3, L1..L3WhRead
Real Energy, Supply, Tariff 3, L1..L4WhRead
Real Energy, Supply, Tariff 4, L1WhRead
Real Energy, Supply, Tariff 4, L2WhRead
Real Energy, Supply, Tariff 4, L3WhRead
Real Energy, Supply, Tariff 4, L4WhRead
Real Energy, Supply, Tariff 4, L1..L3WhRead
Real Energy, Supply, Tariff 4, L1..L4WhRead
Reactive Energy, Induktiv, Tariff 3, L1varhRead
Reactive Energy, Induktiv, Tariff 3, L2varhRead
Reactive Energy, Induktiv, Tariff 3, L3varhRead
Reactive Energy, Induktiv, Tariff 3, L4varhRead
Reactive Energy, Induktiv, Tariff 3, L1..L3varhRead
Reactive Energy, Induktiv, Tariff 3, L1..L4varhRead
Reactive Energy, Induktiv, Tariff 4, L1varhRead
Reactive Energy, Induktiv, Tariff 4, L2varhRead
Reactive Energy, Induktiv, Tariff 4, L3varhRead
Reactive Energy, Induktiv, Tariff 4, L4varhRead
Reactive Energy, Induktiv, Tariff 3, L1..L3 (Other)varhRead
Reactive Energy, Induktiv, Tariff 3, L1..L4 (Other)varhRead
SNMP_USERVAR [0] (Internal)Read
SNMP_USERVAR [1] (Internal)Read
SNMP_USERVAR [2] (Internal)Read
SNMP_USERVAR [3] (Internal)Read
SNMP_USERVAR [4] (Internal)Read
SNMP_USERVAR [5] (Internal)Read
SNMP_USERVAR [6] (Internal)Read
SNMP_USERVAR [7] (Internal)Read
SNMP_USERVAR [8] (Internal)Read
SNMP_USERVAR [9] (Internal)Read
SNMP_USERVAR [10] (Internal)Read
SNMP_USERVAR [11] (Internal)Read
SNMP_USERVAR [12] (Internal)Read
SNMP_USERVAR [13] (Internal)Read
SNMP_USERVAR [14] (Internal)Read
SNMP_USERVAR [15] (Internal)Read
AKT_EVT_START [0] (Internal)sRead
AKT_EVT_START [1] (Internal)sRead
AKT_EVT_START [2] (Internal)sRead
AKT_EVT_START [3] (Internal)sRead
AKT_EVT_START [4] (Internal)sRead
AKT_EVT_START [5] (Internal)sRead
AKT_EVT_START [6] (Internal)sRead
AKT_EVT_START [7] (Internal)sRead
AKT_EVT_STOP [0] (Internal)sRead
AKT_EVT_STOP [1] (Internal)sRead
AKT_EVT_STOP [2] (Internal)sRead
AKT_EVT_STOP [3] (Internal)sRead
AKT_EVT_STOP [4] (Internal)sRead
AKT_EVT_STOP [5] (Internal)sRead
AKT_EVT_STOP [6] (Internal)sRead
AKT_EVT_STOP [7] (Internal)sRead
AKT_EVT_BOUND [0] (Internal)Read
AKT_EVT_BOUND [1] (Internal)Read
AKT_EVT_BOUND [2] (Internal)Read
AKT_EVT_BOUND [3] (Internal)Read
AKT_EVT_BOUND [4] (Internal)Read
AKT_EVT_BOUND [5] (Internal)Read
AKT_EVT_BOUND [6] (Internal)Read
AKT_EVT_BOUND [7] (Internal)Read
AKT_EVT_MAXVAL [0] (Internal)Read
AKT_EVT_MAXVAL [1] (Internal)Read
AKT_EVT_MAXVAL [2] (Internal)Read
AKT_EVT_MAXVAL [3] (Internal)Read
AKT_EVT_MAXVAL [4] (Internal)Read
AKT_EVT_MAXVAL [5] (Internal)Read
AKT_EVT_MAXVAL [6] (Internal)Read
AKT_EVT_MAXVAL [7] (Internal)Read
AKT_EVT_MINVAL [0] (Internal)Read
AKT_EVT_MINVAL [1] (Internal)Read
AKT_EVT_MINVAL [2] (Internal)Read
AKT_EVT_MINVAL [3] (Internal)Read
AKT_EVT_MINVAL [4] (Internal)Read
AKT_EVT_MINVAL [5] (Internal)Read
AKT_EVT_MINVAL [6] (Internal)Read
AKT_EVT_MINVAL [7] (Internal)Read
AKT_EVT_AVG [0] (Internal)Read
AKT_EVT_AVG [1] (Internal)Read
AKT_EVT_AVG [2] (Internal)Read
AKT_EVT_AVG [3] (Internal)Read
AKT_EVT_AVG [4] (Internal)Read
AKT_EVT_AVG [5] (Internal)Read
AKT_EVT_AVG [6] (Internal)Read
AKT_EVT_AVG [7] (Internal)Read
AKT_EVT_REASON [0] (Internal)Read
AKT_EVT_REASON [1] (Internal)Read
AKT_EVT_REASON [2] (Internal)Read
AKT_EVT_REASON [3] (Internal)Read
AKT_EVT_REASON [4] (Internal)Read
AKT_EVT_REASON [5] (Internal)Read
AKT_EVT_REASON [6] (Internal)Read
AKT_EVT_REASON [7] (Internal)Read
AKT_EVT_CNT [0] (Internal)Read
AKT_EVT_CNT [1] (Internal)Read
AKT_EVT_CNT [2] (Internal)Read
AKT_EVT_CNT [3] (Internal)Read
AKT_EVT_CNT [4] (Internal)Read
AKT_EVT_CNT [5] (Internal)Read
AKT_EVT_CNT [6] (Internal)Read
AKT_EVT_CNT [7] (Internal)Read
HW_INDEX (Internal)Read
PTP_VERSION (Internal)Read
PTP_DOMAIN (Internal)Read
PTP_CLOCK_CLASS (Internal)Read
PTP_CLOCK_ACCURACY (Internal)Read
PTP_TIME_SOURCE (Internal)Read
PTP_TWO_STEP (Internal)Read
PTP_DELAY_MECHANISM (Internal)Read
PTP_PROFILE_ID [0] (Internal)Read
PTP_PROFILE_ID [1] (Internal)Read
PTP_PROFILE_ID [2] (Internal)Read
PTP_PROFILE_ID [3] (Internal)Read
PTP_PROFILE_ID [4] (Internal)Read
PTP_PROFILE_ID [5] (Internal)Read
PTP_ANNOUNCE_RECEIPT_TIMEOUT (Internal)Read
PTP_STATE (Internal)Read
PTP_MANAGEMENT_INTERFACE (Internal)Read
PTP_PRIORITY1 (Internal)Read
PTP_PRIORITY2 (Internal)Read
INIT_CUSTOMKEY (Internal)Read
FORBID_HTML (Internal)Read
IN Distortion Reactive Power [0]varRead
IN Distortion Reactive Power [1]varRead
IN Distortion Reactive Power [2]varRead
IN Distortion Reactive Power [3]varRead
Voltage, Real Part L-L [0]VRead
Voltage, Real Part L-L [1]VRead
Voltage, Real Part L-L [2]VRead
Voltage, Imaginary Part L-L [0]VRead
Voltage, Imaginary Part L-L [1]VRead
Voltage, Imaginary Part L-L [2]VRead
Counter For Started EventsRead
Flags For Running EventsRead
Free Input Field For Storing Numerical InformationRead
Current Rate, Real/apparent EnergyRead
Current Rate, Reactive EnergyRead
Apparent Energy L1 (Energy List)VAhRead
Apparent Energy L2 (Energy List)VAhRead
Apparent Energy L3 (Energy List)VAhRead
Apparent Energy L4VAhRead
Apparent Energy L1+L2+L3VAhRead
Apparent Energy L1+L2+L3+L4VAhRead
Real Energy L1 (Energy List)WhRead
Real Energy L2 (Energy List)WhRead
Real Energy L3 (Energy List)WhRead
Real Energy L4WhRead
Real Energy L1+L2+L3WhRead
Real Energy L1+L2+L3+L4WhRead
Reactive Energy L1varhRead
Reactive Energy L2varhRead
Reactive Energy L3varhRead
Reactive Energy L4varhRead
Reactive Energy L1+L2+L3varhRead
Reactive Energy L1+L2+L3+L4varhRead
Real Energy L1, Consumed (Energy List)WhRead
Real Energy L2, Consumed (Energy List)WhRead
Real Energy L3, Consumed (Energy List)WhRead
Real Energy L4, ConsumedWhRead
Real Energy L1+L2+L3, ConsumedWhRead
Real Energy L1+L2+L3+L4, ConsumedWhRead
Real Energy L1, Delivered (Energy List)WhRead
Real Energy L2, Delivered (Energy List)WhRead
Real Energy L3, Delivered (Energy List)WhRead
Real Energy L4, DeliveredWhRead
Real Energy L1+L2+L3, DeliveredWhRead
Real Energy L1+L2+L3+L4, DeliveredWhRead
Real Energy L1, Consumed, HT (Tariff 1), Rate 1WhRead
Real Energy L2, Consumed, HT (Tariff 1), Rate 1WhRead
Real Energy L3, Consumed, HT (Tariff 1), Rate 1WhRead
Real Energy L4, Consumed, HT (Tariff 1), Rate 1WhRead
Real Energy L1..L3, Consumed, HT (Tariff 1), Rate 1WhRead
Real Energy L1..L4, Consumed, HT (Tariff 1), Rate 1WhRead
Real Energy L1, Consumed, NT (Tariff 1), Rate 2WhRead
Real Energy L2, Consumed, NT (Tariff 1), Rate 2WhRead
Real Energy L3, Consumed, NT (Tariff 1), Rate 2WhRead
Real Energy L4, Consumed, NT (Tariff 1), Rate 2WhRead
Real Energy L1..L3, Consumed, NT (Tariff 1), Rate 2WhRead
Real Energy L1..L4, Consumed, NT (Tariff 1), Rate 2WhRead
Real Energy L1, Delivered, HT (Tariff 2), Rate 1WhRead
Real Energy L2, Delivered, HT (Tariff 2), Rate 1WhRead
Real Energy L3, Delivered, HT (Tariff 2), Rate 1WhRead
Real Energy L4, Delivered, HT (Tariff 2), Rate 1WhRead
Real Energy L1..L3, Delivered, HT (Tariff 2), Rate 1WhRead
Real Energy L1..L4, Delivered, HT (Tariff 2), Rate 1WhRead
Real Energy L1, Delivered, NT (Tariff 2), Rate 2WhRead
Real Energy L2, Delivered, NT (Tariff 2), Rate 2WhRead
Real Energy L3, Delivered, NT (Tariff 2), Rate 2WhRead
Real Energy L4, Delivered, NT (Tariff 2), Rate 2WhRead
Real Energy L1..L3, Delivered, NT (Tariff 2), Rate 2WhRead
Real Energy L1..L4, Delivered, NT (Tariff 2), Rate 2WhRead
Reactive Energy L1, InductivevarhRead
Reactive Energy L2, InductivevarhRead
Reactive Energy L3, InductivevarhRead
Reactive Energy L4, InductivevarhRead
Reactive Energy L1..L3, InductivevarhRead
Reactive Energy L1..L4, InductivevarhRead
Reactive Energy L1, CapacitivevarhRead
Reactive Energy L2, CapacitivevarhRead
Reactive Energy L3, CapacitivevarhRead
Reactive Energy L4, CapacitivevarhRead
Reactive Energy L1..L3, CapacitivevarhRead
Reactive Energy L1..L4, CapacitivevarhRead
Reactive Energy L1, Inductive, Rate 1varhRead
Reactive Energy L2, Inductive, Rate 1varhRead
Reactive Energy L3, Inductive, Rate 1varhRead
Reactive Energy L4, Inductive, Rate 1varhRead
Reactive Energy L1..L3, Inductive, Rate 1varhRead
Reactive Energy L1..L4, Inductive, Rate 1varhRead
Reactive Energy L1, Inductive, Rate 2varhRead
Reactive Energy L2, Inductive, Rate 2varhRead
Reactive Energy L3, Inductive, Rate 2varhRead
Reactive Energy L4, Inductive, Rate 2varhRead
Reactive Energy L1..L3, Inductive, Rate 2varhRead
Reactive Energy L1..L4, Inductive, Rate 2varhRead
Energy Meter (Counter, Not Scaled), Impulse Input 1Read
Energy Meter (Counter, Not Scaled), Impulse Input 2Read
Runtime Of Real And Apparent Energy Meas.sRead
Runtime Of Real And Reactive Energy Meas.sRead
Real Energy, Month High, Jan., Even YearWhRead
Real Energy, Month High, Feb., Even YearWhRead
Real Energy, Month High, March, Even YearWhRead
Real Energy, Month High, April, Even YearWhRead
Real Energy, Month High, May, Even YearWhRead
Real Energy, Month High, June, Even YearWhRead
Real Energy, Month High, July, Even YearWhRead
Real Energy, Month High, Aug., Even YearWhRead
Real Energy, Month High, Sep., Even YearWhRead
Real Energy, Month High, Oct. Even YearWhRead
Real Energy, Month High, Nov., Even YearWhRead
Real Energy, Month High, Dec., Even YearWhRead
Real Energy, Month High, Jan., Uneven YearWhRead
Real Energy, Month High, Feb., Uneven YearWhRead
Real Energy, Month High, March, Uneven YearWhRead
Real Energy, Month High, April, Uneven YearWhRead
Real Energy, Month High, May, Uneven YearWhRead
Real Energy, Month High, June, Uneven YearWhRead
Real Energy, Month High, July, Uneven YearWhRead
Real Energy, Month High, Aug., Uneven YearWhRead
Real Energy, Month High, Sep., Uneven YearWhRead
Real Energy, Month High, Oct.., Uneven YearWhRead
Real Energy, Month High, Nov., Uneven YearWhRead
Real Energy, Month High, Dec., Uneven YearWhRead
Apparent Energy, Month High, Jan., Even YearVAhRead
Apparent Energy, Month High, Feb., Even YearVAhRead
Apparent Energy, Month High, March, Even YearVAhRead
Apparent Energy, Month High, April, Even YearVAhRead
Apparent Energy, Month High, May, Even YearVAhRead
Apparent Energy, Month High, June, Even YearVAhRead
Apparent Energy, Month High, July, Even YearVAhRead
Apparent Energy, Month High, Aug., Even YearVAhRead
Apparent Energy, Month High, Sep., Even YearVAhRead
Apparent Energy, Month High, Oct., Even YearVAhRead
Apparent Energy, Month High, Nov., Even YearVAhRead
Apparent Energy, Month High, Dec., Even YearVAhRead
Apparent Energy, Month High, Jan., Uneven YearVAhRead
Apparent Energy, Month High, Feb., Uneven YearVAhRead
Apparent Energy, Month High, March, Uneven YearVAhRead
Apparent Energy, Month High, April, Uneven YearVAhRead
Apparent Energy, Month High, May, Uneven YearVAhRead
Apparent Energy, Month High, June, Uneven YearVAhRead
Apparent Energy, Month High, July, Uneven YearVAhRead
Apparent Energy, Month High, Aug., Uneven YearVAhRead
Apparent Energy, Month High, Sep., Uneven YearVAhRead
Apparent Energy, Month High, Oct., Uneven YearVAhRead
Apparent Energy, Month High, Nov., Uneven YearVAhRead
Apparent Energy, Month High, Dec., Uneven YearVAhRead
Reactive Energy, Month High, Jan., Even YearvarhRead
Reactive Energy, Month High, Feb., Even YearvarhRead
Reactive Energy, Month High, March, Even YearvarhRead
Reactive Energy, Month High, April, Even YearvarhRead
Reactive Energy, Month High, May Even YearvarhRead
Reactive Energy, Month High, June, Even YearvarhRead
Reactive Energy, Month High, July, Even YearvarhRead
Reactive Energy, Month High, Aug., Even YearvarhRead
Reactive Energy, Month High, Sep., Even YearvarhRead
Reactive Energy, Month High, Oct., Even YearvarhRead
Reactive Energy, Month High, Nov., Even YearvarhRead
Reactive Energy, Month High, Dec., Even YearvarhRead
Reactive Energy, Month High, Jan., Uneven YearvarhRead
Reactive Energy, Month High, Feb., Uneven YearvarhRead
Reactive Energy, Month High, March, Uneven YearvarhRead
Reactive Energy, Month High, April, Uneven YearvarhRead
Reactive Energy, Month High, May, Uneven YearvarhRead
Reactive Energy, Month High, June., Uneven YearvarhRead
Reactive Energy, Month High, July., Uneven YearvarhRead
Reactive Energy, Month High, Aug., Uneven YearvarhRead
Reactive Energy, Month High, Sep., Uneven YearvarhRead
Reactive Energy, Month High, Oct., Uneven YearvarhRead
Reactive Energy, Month High, Nov., Uneven YearvarhRead
Reactive Energy, Month High, Dez., Uneven YearvarhRead
EMAX, 15minutes Month High, Jan., Even YearWRead
EMAX, 15minutes Month High, Feb., Even YearWRead
EMAX, 15minutes Month High, March, Even YearWRead
EMAX, 15minutes Month High, April., Even YearWRead
EMAX, 15minutes Month High, May, Even YearWRead
EMAX, 15minutes Month High, June, Even YearWRead
EMAX, 15minutes Month High, July, Even YearWRead
EMAX, 15minutes Month High, Aug., Even YearWRead
EMAX, 15minutes Month High, Sep., Even YearWRead
EMAX, 15minutes Month High, Oct., Even YearWRead
EMAX, 15minutes Month High, Nov., Even YearWRead
EMAX, 15minutes Month High, Dez., Even YearWRead
EMAX, 15minutes Month High, Jan., Uneven YearWRead
EMAX, 15minutes Month High, Feb., Uneven YearWRead
EMAX, 15minutes Month High, March, Uneven YearWRead
EMAX, 15minutes Month High, April, Uneven YearWRead
EMAX, 15minutes Month High, May, Uneven YearWRead
EMAX, 15minutes Month High, June, Uneven YearWRead
EMAX, 15minutes Month High, July, Uneven YearWRead
EMAX, 15minutes Month High, Aug., Uneven YearWRead
EMAX, 15minutes Month High, Sep., Uneven YearWRead
EMAX, 15minutes Month High, Oct., Uneven YearWRead
EMAX, 15minutes Month High, Nov., Uneven YearWRead
EMAX, 15minutes Month High, Dec., Uneven YearWRead
Time Of 15minutes Month High, Jan., Even YearsRead
Time Of 15minutes Month High, Feb., Even YearsRead
Time Of 15minutes Month High, May, Even YearsRead
Time Of 15minutes Month High, June, Even YearsRead
Time Of 15minutes Month High, July., Even YearsRead
Time Of 15minutes Month High, Aug., Even YearsRead
Time Of 15minutes Month High, Sep., Even YearsRead
Time Of 15minutes Month High, Oct., Even YearsRead
Time Of 15minutes Month High, Nov., Even YearsRead
Time Of 15minutes Month High, Dez., Even YearsRead
Time Of 15minutes Month High, Jan., Uneven YearsRead
Time Of 15minutes Month High, Feb., Uneven YearsRead
Time Of 15minutes Month High, March, Uneven YearsRead
Time Of 15minutes Month High, April, Uneven YearsRead
Time Of 15minutes Month High, May, Uneven YearsRead
Time Of 15minutes Month High, June, Uneven YearsRead
Time Of 15minutes Month High, July, Uneven YearsRead
Time Of 15minutes Month High, Aug., Uneven YearsRead
Time Of 15minutes Month High, Sep., Uneven YearsRead
Time Of 15minutes Month High, Oct., Uneven YearsRead
Time Of 15minutes Month High, Nov., Uneven YearsRead
Time Of 15minutes Month High, Dec., Uneven YearsRead
Reactive Energy L1 (Inductive), ConsumedvarhRead
Reactive Energy L2 (Inductive), ConsumedvarhRead
Reactive Energy L3 (Inductive), ConsumedvarhRead
Reactive Energy L4 (Inductive), ConsumedvarhRead
Reactive Energy L1..L3 (Inductive), ConsumedvarhRead
Reactive Energy L1..L4 (Inductive), ConsumedvarhRead
Reactive Energy L1 (Inductive), DeliveredvarhRead
Reactive Energy L2 (Inductive), DeliveredvarhRead
Reactive Energy L3 (Inductive), DeliveredvarhRead
Reactive Energy L4 (Inductive), DeliveredvarhRead
Reactive Energy L1..L3 (Inductive), DeliveredvarhRead
Reactive Energy L1..L4 (Inductive), DeliveredvarhRead
Reactive Energy L1 (Capacitive), ConsumedvarhRead
Reactive Energy L2 (Capacitive), ConsumedvarhRead
Reactive Energy L3 (Capacitive), ConsumedvarhRead
Reactive Energy L4 (Capacitive), ConsumedvarhRead
Reactive Energy L1..L3 (Capacitive), ConsumedvarhRead
Reactive Energy L1..L4 (Capacitive), ConsumedvarhRead
Reactive Energy L1 (Capacitive), DeliveredvarhRead
Reactive Energy L2 (Capacitive), DeliveredvarhRead
Reactive Energy L3 (Capacitive), DeliveredvarhRead
Reactive Energy L4 (Capacitive), DeliveredvarhRead
Reactive Energy L1..L3 (Capacitive), DeliveredvarhRead
Reactive Energy L1..L4 (Capacitive), DeliveredvarhRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show voltage, current and power per phase of the main distribution board on one dashboard.
  • Send an email alert when voltage THD rises above the limit you set for the installation.
  • Keep 365 days of history of frequency, imbalance and flicker to answer power quality complaints.
  • Track consumed and delivered energy per tariff and per month for energy reports.
  • Compare the maximum demand values of several transformer stations to plan capacity.

Installation

  1. Connect RS485 A and B of the UMG 605-PRO to the RS485 port of the ModbusCloud Gateway and terminate both ends of the bus.

  2. Set the device address and baud rate on the meter; the line uses 8 data bits, no parity and 2 stop bits.

  3. In ModbusCloud, add a Modbus device on the Gateway with the same address and serial settings, then import this template.

  4. Check that the voltages L1-N to L3-N and the frequency arrive with plausible values.

Things to watch for

The meter does not answer on the RS485 bus. What should I check?

The UMG 605-PRO uses 8 data bits, no parity and 2 stop bits; many tools default to 1 stop bit or even parity. Match the address and baud rate set on the meter, swap A and B if nothing comes back, and terminate only the two ends of the bus.

Why do the 32-bit values look scrambled?

The registers deliver big-endian data with the high word first. If a value looks wrong, check the word order in the device settings of ModbusCloud. The same data is also available in little-endian at the address plus 32768, but this template uses the big-endian addresses.

Do I have to apply the transformer ratio myself?

Not for this template. Float and integer values already include the current and voltage transformer ratios set in the meter. Check that the primary and secondary values in the meter match the installed transformers.

Which registers can I write from ModbusCloud?

Only the six voltage phase angle registers are marked as read and write in the address list. Read the current value first and change it only when you know why; the other registers, including transformer ratios and settings, are read only in this template.

Can several meters share one RS485 line?

Yes. Give every meter its own address and use the same baud rate and serial settings on all of them. Run the bus as one line from device to device and terminate both ends.

Want to see how it works?