Regmet Regmet RK-HTM-D..TFT touch screen controler Modbus RTU template

Regmet RK-HTM-D..TFT touch screen controler

Measures and controls relative humidity and temperature via TFT touch screen controller

The Regmet RK-HTM-D is a TFT touch screen controller for measuring and setting relative humidity and temperature in interior spaces. This Modbus RTU template reads temperature and humidity values, and allows writing setpoints, operating modes, LCD settings, and display symbols via RS485.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
21, read and write
Brand
Regmet
Key readings
Temperature · Relative humidity
Available commands
Setpoint temperature · Setpoint humidity · Required mode 1 to 4 · LCD backlight and colors
Compatible models
RK-HTM-D
Last updated

Registers (21)

2 read, 19 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
1: 0x02 Relative humidity%Read
0: 0x01 Temperature°CRead
9: 0x10 Setpoint humidity%Write
8: 0x09 Setpoint temperature°CWrite
16: 0x17 Required mode 1Write
17: 0x18 Required mode 2Write
76: 0x77 Offset temperature°CWrite
28: 0x29 Status registerWrite
34: 0x35 LCD backlight dayWrite
18: 0x19 Required mode 3Write
24: 0x25 Symbol at position 1Write
25: 0x26 Symbol at position 2Write
26: 0x27 Symbol at position 3Write
37: 0x38 LCD symbol colorWrite
36: 0x37 LCD value colorWrite
39: 0x40 Bit Field (external values)Write
35: 0x36 LCD backlight timeWrite
19: 0x20 Required mode 4Write
27: 0x28 Symbol at position 4Write
38: 0x39 LCD Backlight nightWrite
77: 0x78 Offset relative humidity%Write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor room temperature and relative humidity across multiple zones on a centralized cloud dashboard.
  • Adjust temperature and humidity setpoints remotely without physically visiting each room controller.
  • Create alerts when indoor humidity exceeds a defined threshold for more than a set period.
  • Switch operating modes centrally for seasonal changeovers or occupancy schedule updates.
  • Log historical temperature and humidity data for compliance reporting in climate-sensitive environments.
  • Display status symbols on the RK-HTM-D screen from the cloud to inform occupants about system events.

Installation

  1. Wire the Regmet RK-HTM-D to the ModbusCloud gateway RS485 terminals (A to A, B to B) using twisted-pair shielded cable.

  2. Set a unique Modbus slave address on the RK-HTM-D using its on-device menu or configuration tool.

  3. Configure the ModbusCloud gateway serial port to 19200 baud, 8 data bits, odd parity, and 1 stop bit to match the RK-HTM-D defaults.

  4. Import the Regmet RK-HTM-D template from the ModbusCloud template library and assign it to the correct gateway port and slave address.

  5. Verify communication by checking that live temperature and humidity readings appear on the ModbusCloud dashboard.

  6. If multiple RK-HTM-D units share the same RS485 bus, ensure each has a distinct address and add proper bus termination at the last device.

Things to watch for

The gateway cannot communicate with the RK-HTM-D. What should I check first?

Verify that the baud rate is set to 19200 and parity is set to odd (1 stop bit) on both the gateway and the controller. Also confirm that the A and B RS485 wires are not swapped.

Can I connect multiple RK-HTM-D controllers on one RS485 bus?

Yes. Each controller must have a unique Modbus slave address. Use a daisy-chain topology and place a 120 ohm termination resistor at the last device on the bus.

How do I select operating modes via Modbus?

The template includes write registers for modes 1 through 4. Each register accepts a value from 1 to 68, corresponding to the predefined mode library of the RK-HTM-D. Set the register to the desired mode number.

Can I change the LCD backlight and colors remotely?

Yes. The template exposes writable registers for LCD backlight intensity and color settings. Changes take effect immediately on the TFT display.