ModbusCloud
Back to library
Siemens Siemens SENTRON PAC3200 Modbus RTU template
Modbus RTU

Siemens SENTRON PAC3200

Siemens

Three-phase power monitoring device: voltages, currents, power, power factor, THD, demand and status over Modbus RTU or TCP.

Overview

The Siemens SENTRON PAC3200 is a panel-mounted power monitoring device for three-phase and single-phase low-voltage networks. This template follows the register tables in the Siemens PAC3200 manual A5E01168664B-04 (edition 02/2008) and reads voltages, currents, active, reactive and apparent power, power factor, THD, frequency, unbalance, demand values, device status and counters, all as 32-bit values. Default Modbus RTU link through the PAC RS485 expansion module: address 126, 19200 baud, 8 data bits, no parity, 2 stop bits. The built-in Ethernet port offers the same registers over Modbus TCP on port 502.

Key readings

  • Phase-to-neutral and phase-to-phase voltages
  • Current per phase and average current
  • Active, reactive and apparent power per phase and in total
  • Power factor per phase and total
  • THD of voltage and current, voltage and current unbalance
  • Frequency
  • Demand values for import and export
  • Device status, limit violations and operating hours

Use cases

  • Alert when Total Active Power exceeds the contracted connection capacity of a building.
  • Monitor Current L1, L2 and L3 and Current Unbalance to spot an overloaded phase in a distribution board.
  • Track THD Voltage and THD Current per phase to find harmonic problems from drives or LED lighting.
  • Compare Demand Active Power Import across weeks to plan peak shaving or a tariff change.
  • Raise a warning when Device Status reports a voltage or current overload, or when Limit Violations is not 0.
  • Log Total Power Factor to decide whether reactive power compensation is needed.

Installation

  1. 1Fit the PAC RS485 expansion module to the PAC3200 and connect its A and B terminals to the RS485 port of your ModbusCloud Gateway. Terminate both ends of the bus.
  2. 2On the meter, open SETTINGS > RS485 MODULE and check ADDRESS (default 126), BAUD RATE (19200), SETTINGS (8N2) and PROTOCOL (MODBUS RTU).
  3. 3For Modbus TCP instead, set IP ADDRESS, SUBNET and GATEWAY under SETTINGS > COMMUNICATION and switch PROTOCOL from SEAbus TCP to MODBUS TCP; the meter restarts.
  4. 4In ModbusCloud, add a Modbus device with the same address and serial settings (or the IP address and port 502), then import this template.
  5. 5Check the link: Frequency should read about 50 Hz and Voltage L1-N about 230 V on a standard low-voltage network.

Things to watch for

The meter does not answer over RS485. What should I check?
Modbus RTU only works with the PAC RS485 expansion module fitted. Check the module settings under SETTINGS > RS485 MODULE: default address 126, 19200 baud and 8N2, so two stop bits and no parity, which many tools do not use by default. Then swap A and B and check the termination at both ends of the bus.
Modbus TCP connects but nothing comes back on port 502.
The Ethernet port speaks SEAbus TCP by default. Switch PROTOCOL to MODBUS TCP under SETTINGS > COMMUNICATION and confirm the restart. Set IP address, subnet and gateway before the switch.
Why do I get an exception or strange values when I read a register?
Every measured value is a float in two registers. The PAC3200 returns an error when a read starts in the second register of a value, and a shifted address gives nonsense. Use the addresses exactly as in this template (Voltage L1-N at 1, Total Active Power at 65) with high word first.
Where are the kWh counters?
Siemens stores the energy counters (offset 801 onward) as 64-bit double values. ModbusCloud templates hold 16-bit and 32-bit values only, so they are not in this template. Demand Active Power Import and the power readings are included.
Currents and power are far too low or too high.
The PAC3200 applies the CT and VT ratios itself. Check Primary Current and Secondary Current, and with voltage transformers Primary Voltage and Secondary Voltage, against the installed transformers. Connection Type must match the wiring, for example 3P4W for a four-wire network.
Several meters on one bus answer at random.
Every device on the RS485 line needs its own address. All PAC RS485 modules leave the factory with address 126, so give each meter a unique address from 1 to 126 before you connect them together.

Registers (61)

61 read / 0 write

NameAddressFunctionTypeUnitAccess
Voltage L1-N
Phase-to-neutral voltage L1-N in volts, IEEE 754 float. Manual name: Voltage Va-n.
•••••••••VR
Voltage L2-N
Phase-to-neutral voltage L2-N in volts, IEEE 754 float. Manual name: Voltage Vb-n.
•••••••••VR
Voltage L3-N
Phase-to-neutral voltage L3-N in volts, IEEE 754 float. Manual name: Voltage Vc-n.
•••••••••VR
Voltage L1-L2
Phase-to-phase voltage L1-L2 in volts. Manual name: Voltage Va-b.
•••••••••VR
Voltage L2-L3
Phase-to-phase voltage L2-L3 in volts. Manual name: Voltage Vb-c.
•••••••••VR
Voltage L3-L1
Phase-to-phase voltage L3-L1 in volts. Manual name: Voltage Vc-a.
•••••••••VR
Current L1
Current in phase L1 in amperes. Manual name: Current a.
•••••••••AR
Current L2
Current in phase L2 in amperes. Manual name: Current b.
•••••••••AR
Current L3
Current in phase L3 in amperes. Manual name: Current c.
•••••••••AR
Active Power L1
Active power in phase L1 in watts. Manual name: Active Power a.
•••••••••WR
Active Power L2
Active power in phase L2 in watts. Manual name: Active Power b.
•••••••••WR
Active Power L3
Active power in phase L3 in watts. Manual name: Active Power c.
•••••••••WR
Total Active Power
Sum of the active power of all phases in watts. Manual name: Total Active Power.
•••••••••WR
Total Reactive Power
Sum of the reactive power of all phases in var. Manual name: Total Reactive Power.
•••••••••varR
Total Apparent Power
Sum of the apparent power of all phases in VA. Manual name: Total Apparent Power.
•••••••••VAR
Total Power Factor
Power factor over all phases. Manual name: Total Power Factor.
•••••••••R
Frequency
Mains frequency in hertz, range 45 to 65 Hz. Manual name: Frequency.
•••••••••HzR
Average Voltage L-N
Average of the three phase-to-neutral voltages in volts. Manual name: Average Voltage Vph-n.
•••••••••VR
Average Voltage L-L
Average of the three phase-to-phase voltages in volts. Manual name: Average Voltage Vph-ph.
•••••••••VR
Average Current
Average of the three phase currents in amperes. Manual name: Average Current.
•••••••••AR
Reactive Power L1
Reactive power in phase L1 in var. Manual name: Reactive Power a.
•••••••••varR
Reactive Power L2
Reactive power in phase L2 in var. Manual name: Reactive Power b.
•••••••••varR
Reactive Power L3
Reactive power in phase L3 in var. Manual name: Reactive Power c.
•••••••••varR
Apparent Power L1
Apparent power in phase L1 in VA. Manual name: Apparent Power a.
•••••••••VAR
Apparent Power L2
Apparent power in phase L2 in VA. Manual name: Apparent Power b.
•••••••••VAR
Apparent Power L3
Apparent power in phase L3 in VA. Manual name: Apparent Power c.
•••••••••VAR
Power Factor L1
Power factor of phase L1, range 0 to 1 per the manual. Manual name: Power Factor a.
•••••••••R
Power Factor L2
Power factor of phase L2, range 0 to 1 per the manual. Manual name: Power Factor b.
•••••••••R
Power Factor L3
Power factor of phase L3, range 0 to 1 per the manual. Manual name: Power Factor c.
•••••••••R
THD Voltage L1
Total harmonic distortion (THD-R) of the voltage in phase L1, 0 to 100 %. Manual name: THD-R Voltage a.
•••••••••%R
THD Voltage L2
Total harmonic distortion (THD-R) of the voltage in phase L2, 0 to 100 %. Manual name: THD-R Voltage b.
•••••••••%R
THD Voltage L3
Total harmonic distortion (THD-R) of the voltage in phase L3, 0 to 100 %. Manual name: THD-R Voltage c.
•••••••••%R
THD Current L1
Total harmonic distortion (THD-R) of the current in phase L1, 0 to 100 %. Manual name: THD-R Current a.
•••••••••%R
THD Current L2
Total harmonic distortion (THD-R) of the current in phase L2, 0 to 100 %. Manual name: THD-R Current b.
•••••••••%R
THD Current L3
Total harmonic distortion (THD-R) of the current in phase L3, 0 to 100 %. Manual name: THD-R Current c.
•••••••••%R
Voltage Unbalance
Amplitude unbalance of the voltage, 0 to 100 %. Manual name: Amplitude Unbalance - Voltage.
•••••••••%R
Current Unbalance
Amplitude unbalance of the current, 0 to 200 %. Manual name: Amplitude Unbalance - Current.
•••••••••%R
Max Total Active Power
Highest total active power since the maximum values were last reset, in watts. Manual name: Max. Total Active Power.
•••••••••WR
Min Total Active Power
Lowest total active power since the minimum values were last reset, in watts. Manual name: Min. Total Active Power.
•••••••••WR
Demand Active Power Import
Average active power drawn over the last completed demand period, in watts. Manual name: Demand Active Power - Import.
•••••••••WR
Demand Reactive Power Import
Average reactive power drawn over the last completed demand period, in var. Manual name: Demand Reactive Power - Import.
•••••••••varR
Demand Active Power Export
Average active power delivered over the last completed demand period, in watts. Manual name: Demand Active Power - Export.
•••••••••WR
Demand Reactive Power Export
Average reactive power delivered over the last completed demand period, in var. Manual name: Demand Reactive Power - Export.
•••••••••varR
Max Active Power In Period
Highest active power reading during the demand period, in watts. Manual name: Maximum Active Power Reading during the period.
•••••••••WR
Demand Period Length
Length of the demand period in seconds (set in minutes, 1 to 60, under Demand Period). Manual name: Demand Period.
•••••••••sR
Time Since Demand Period Start
Seconds elapsed since the start of the active demand period. Manual name: Time Since Start of the active demand period.
•••••••••sR
Device Status
Bitfield. 0x08000000 = current overload, 0x04000000 = voltage overload, 0x02000000 = configuration menu active, 0x01000000 = no sync pulse, 0x00000800 = device restarted, 0x00000200 = limit violation stored. 0 = no flag set.
•••••••••R
Limit Violations
Bitfield of the six programmable limits: 0x01 = limit 0 up to 0x20 = limit 5, 0x01000000 = limit logic. A set bit means the limit is violated. 0 = no violation.
•••••••••R
Digital Input Status
State of digital input 0 (bit mask 0x00000001). Manual name: Status of the digital inputs.
•••••••••R
Digital Output Status
State of digital output 0 (bit mask 0x00000001). Manual name: Status of the digital outputs.
•••••••••R
Active Tariff
Tariff that the energy counters are currently counting in: 0 = tariff 1, 1 = tariff 2. Manual name: Active Tariff.
•••••••••R
Working Hours Counter
Operating time counter in seconds, 0 to 999999999. Read only in this template although the manual allows writing it. Manual name: Working hours counter.
•••••••••sR
Universal Counter
Counts pulses or events from the source set under Universal counter source (digital input, digital output or a limit), 0 to 999999999.
•••••••••R
Relevant Parameter Changes
Number of changes to parameters that affect the measurement. Manual name: Relevant Parameter Changes Counter.
•••••••••R
All Parameter Changes
Number of changes to any device parameter. Manual name: Counter All Parameter Changes.
•••••••••R
Connection Type
Configured wiring: 0 = 3P4W, 1 = 3P3W, 2 = 3P4WB, 3 = 3P3WB, 4 = 1P2W. Read only in this template. Manual name: Connection type.
•••••••••R
Primary Current
Configured CT primary current, 1 to 99999 A. Read only in this template. Manual name: Primary current.
•••••••••AR
Secondary Current
Configured CT secondary current, 1 A or 5 A. Read only in this template. Manual name: Secondary current.
•••••••••AR
Primary Voltage
Configured VT primary voltage, 1 to 999999 V, only used when voltage transformers are enabled. Read only in this template.
•••••••••VR
Secondary Voltage
Configured VT secondary voltage, 1 to 690 V, only used when voltage transformers are enabled. Read only in this template.
•••••••••VR
Demand Period Setting
Configured demand period in minutes, 1 to 60. Read only in this template. Manual name: Demand Period.
•••••••••minR

Loading registers…

Read the Siemens SENTRON PAC3200 remotely

We load the templates onto the gateway and set up your portal, you connect it at your customer's site. Tell us briefly what you need and we'll send a proposal.

From €295 + €149/year.

Prefer to configure it yourself? Order the gateway in the shop·Or see the live demo first

EU-hosted
Data in the Netherlands and Germany
Open standard
Based on Modbus RTU/TCP
Free to browse
No account or payment required
European company
Based in the Netherlands

More Siemens templates

More RTU templates