
Siemens SINAMICS V20
Compact frequency converter: frequency, current, power, faults and remote start, stop and setpoint.
The Siemens SINAMICS V20 is a compact frequency converter that controls the speed of motors for pumps, fans, conveyors and mixers. This Modbus RTU template reads frequency, current, power, energy and faults, and lets you start and stop the motor, write the frequency setpoint and change ramp times from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 262, read and write
- Brand
- Siemens
- Key readings
- Output frequency · Motor speed · Output current · Actual power · Energy consumption · Last fault · DC bus voltage
- Available commands
- Start and stop · Frequency setpoint · Direction · Ramp times · Fixed frequencies · PID setpoint
- Compatible models
- SINAMICS V20 (all frame sizes, 1AC 230 V and 3AC 400 V)
- Last updated
Registers (262)
262 read, 186 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Watchdog Time | ms | Read and write | 0 | FC03 / FC06 | uint16 |
| Watchdog Action | Read and write | 1 | FC03 / FC06 | uint16 | |
| Frequency Setpoint | % | Read and write | 2 | FC03 / FC06 | uint16 |
| Run Enable | Read and write | 3 | FC03 / FC06 | uint16 | |
| Forward/Reverse Command | Read and write | 4 | FC03 / FC06 | uint16 | |
| Start Command | Read and write | ||||
| Fault Acknowledgement | Read and write | ||||
| PID Setpoint Reference | % | Read and write | |||
| PID Enable | Read and write | ||||
| Current Limit | % | Read and write | |||
| Acceleration Time | s | Read and write | |||
| Deceleration Time | s | Read and write | |||
| Digital Output 1 | Read and write | ||||
| Digital Output 2 | Read and write | ||||
| Reference Frequency | Hz | Read and write | |||
| PID Upper Limit | % | Read and write | |||
| PID Lower Limit | % | Read and write | |||
| Proportional Gain | Read and write | ||||
| Integral Gain | s | Read and write | |||
| Differential Gain | Read and write | ||||
| Feedback Gain | % | Read and write | |||
| Low Pass | Read and write | ||||
| Frequency Output | Hz | Read | |||
| Speed | rpm | Read | |||
| Current Filtered | A | Read | |||
| Torque | Nm | Read | |||
| Actual Power | kW | Read | |||
| Total kWh | kWh | Read | |||
| DC Bus Voltage | V | Read | |||
| Reference | Hz | Read | |||
| Rated Power | kW | Read | |||
| Voltage Output | V | Read | |||
| Forward/Reverse | Read | ||||
| Stop/Run | Read | ||||
| Run At Maximum Frequency | Read | ||||
| Control Mode | Read | ||||
| Enabled | Read | ||||
| Ready To Run | Read | ||||
| Analog Input 1 | % | Read | |||
| Analog Input 2 | % | Read | |||
| Analog Output 1 | % | Read | |||
| Actual Frequency | % | Read | |||
| PID Setpoint Output | % | Read | |||
| PID Output | % | Read | |||
| PID Feedback | % | Read | |||
| Digital Input 1 | Read | ||||
| Digital Input 2 | Read | ||||
| Digital Input 3 | Read | ||||
| Digital Input 4 | Read | ||||
| Fault | Read | ||||
| Last Fault | Read | ||||
| Fault 1 | Read | ||||
| Fault 2 | Read | ||||
| Fault 3 | Read | ||||
| Warning | Read | ||||
| Last Warning | Read | ||||
| Converter Version | Read | ||||
| Converter Model | Read | ||||
| Control Word | Read and write | ||||
| Main Setpoint | Read and write | ||||
| Status Word | Read | ||||
| Main Actual Value | Read | ||||
| Digital Output 1 (Reg 40200) | Read and write | ||||
| Digital Output 2 (Reg 40201) | Read and write | ||||
| Digital Output 3 | Read and write | ||||
| Digital Output 4 | Read and write | ||||
| Analog Output 1 (Reg 40220) | % | Read | |||
| Digital Input 1 (Reg 40240) | Read | ||||
| Digital Input 2 (Reg 40241) | Read | ||||
| Digital Input 3 (Reg 40242) | Read | ||||
| Digital Input 4 (Reg 40243) | Read | ||||
| Digital Input 5 | Read | ||||
| Digital Input 6 | Read | ||||
| Analog Input 1 (Reg 40260) | % | Read | |||
| Analog Input 2 (Reg 40261) | % | Read | |||
| Converter Model (Reg 40300) | Read | ||||
| Converter Version (Reg 40301) | Read | ||||
| Rated Power (Reg 40320) | kW | Read | |||
| Current Limit (Reg 40321) | % | Read and write | |||
| Acceleration Time (Reg 40322) | s | Read and write | |||
| Deceleration Time (Reg 40323) | s | Read and write | |||
| Reference Frequency (Reg 40324) | Hz | Read and write | |||
| Fixed Frequency 1 | Hz | Read and write | |||
| Fixed Frequency 2 | Hz | Read and write | |||
| Fixed Frequency 3 | Hz | Read and write | |||
| Fixed Frequency 4 | Hz | Read and write | |||
| Fixed Setpoint 1 | % | Read and write | |||
| Fixed Setpoint 2 | % | Read and write | |||
| Fixed Frequency 5 | Hz | Read and write | |||
| Fixed Frequency 6 | Hz | Read and write | |||
| Fixed Frequency 7 | Hz | Read and write | |||
| Fixed Frequency 8 | Hz | Read and write | |||
| Reference (Reg 40340) | Hz | Read | |||
| Speed (Reg 40341) | rpm | Read | |||
| Frequency Output (Reg 40342) | Hz | Read | |||
| Voltage Output (Reg 40343) | V | Read | |||
| DC Bus Voltage (Reg 40344) | V | Read | |||
| Current Filtered (Reg 40345) | A | Read | |||
| Torque (Reg 40346) | Nm | Read | |||
| Actual Power (Reg 40347) | kW | Read | |||
| Total kWh (Reg 40348) | kWh | Read | |||
| Hand/Auto | Read | ||||
| Current Unfiltered | A | Read | |||
| Continuous Boost | % | Read and write | |||
| Minimum Frequency | Hz | Read and write | |||
| Maximum Frequency | Hz | Read and write | |||
| JOG Frequency Index 0 | Hz | Read and write | |||
| JOG Frequency Index 1 | Hz | Read and write | |||
| JOG Frequency Index 2 | Hz | Read and write | |||
| JOG Frequency Left Index 0 | Hz | Read and write | |||
| JOG Frequency Left Index 1 | Hz | Read and write | |||
| JOG Frequency Left Index 2 | Hz | Read and write | |||
| Fault 1 (Reg 40400) | Read | ||||
| Fault 2 (Reg 40401) | Read | ||||
| Fault 3 (Reg 40402) | Read | ||||
| Fault 4 | Read | ||||
| Fault 5 | Read | ||||
| Fault 6 | Read | ||||
| Fault 7 | Read | ||||
| Fault 8 | Read | ||||
| Warning (Reg 40408) | Read | ||||
| Parameter Error Code | Read | ||||
| PID Enable (Reg 40500) | Read and write | ||||
| PID Setpoint Reference (Reg 40501) | % | Read and write | |||
| Low Pass (Reg 40510) | Read and write | ||||
| Feedback Gain (Reg 40511) | % | Read and write | |||
| Proportional Gain (Reg 40512) | Read and write | ||||
| Integral Gain (Reg 40513) | s | Read and write | |||
| Differential Gain (Reg 40514) | Read and write | ||||
| PID Upper Limit (Reg 40515) | % | Read and write | |||
| PID Lower Limit (Reg 40516) | % | Read and write | |||
| PID Setpoint Output (Reg 40520) | % | Read | |||
| PID Feedback (Reg 40521) | % | Read | |||
| PID Output (Reg 40522) | % | Read | |||
| Parameter Number | Read and write | ||||
| Parameter Index | Read and write | ||||
| Parameter Upper Word | Read and write | ||||
| Parameter Lower Word | Read and write | ||||
| Parameter Upper Word (Reg 40558) | Read | ||||
| Parameter Lower Word (Reg 40559) | Read | ||||
| DS47 Control | Read and write | ||||
| DS47 Header | Read and write | ||||
| DS47 Data 1 | Read and write | ||||
| DS47 Data 2 | Read and write | ||||
| DS47 Data 3 | Read and write | ||||
| DS47 Data 4 | Read and write | ||||
| DS47 Data 5 | Read and write | ||||
| DS47 Data 6 | Read and write | ||||
| DS47 Data 7 | Read and write | ||||
| DS47 Data 8 | Read and write | ||||
| DS47 Data 9 | Read and write | ||||
| DS47 Data 10 | Read and write | ||||
| DS47 Data 11 | Read and write | ||||
| DS47 Data 12 | Read and write | ||||
| DS47 Data 13 | Read and write | ||||
| DS47 Data 14 | Read and write | ||||
| DS47 Data 15 | Read and write | ||||
| DS47 Data 16 | Read and write | ||||
| DS47 Data 17 | Read and write | ||||
| DS47 Data 18 | Read and write | ||||
| DS47 Data 19 | Read and write | ||||
| DS47 Data 20 | Read and write | ||||
| DS47 Data 21 | Read and write | ||||
| DS47 Data 22 | Read and write | ||||
| DS47 Data 23 | Read and write | ||||
| DS47 Data 24 | Read and write | ||||
| DS47 Data 25 | Read and write | ||||
| DS47 Data 26 | Read and write | ||||
| DS47 Data 27 | Read and write | ||||
| DS47 Data 28 | Read and write | ||||
| DS47 Data 29 | Read and write | ||||
| DS47 Data 30 | Read and write | ||||
| DS47 Data 31 | Read and write | ||||
| DS47 Data 32 | Read and write | ||||
| DS47 Data 33 | Read and write | ||||
| DS47 Data 34 | Read and write | ||||
| DS47 Data 35 | Read and write | ||||
| DS47 Data 36 | Read and write | ||||
| DS47 Data 37 | Read and write | ||||
| DS47 Data 38 | Read and write | ||||
| DS47 Data 39 | Read and write | ||||
| DS47 Data 40 | Read and write | ||||
| DS47 Data 41 | Read and write | ||||
| DS47 Data 42 | Read and write | ||||
| DS47 Data 43 | Read and write | ||||
| DS47 Data 44 | Read and write | ||||
| DS47 Data 45 | Read and write | ||||
| DS47 Data 46 | Read and write | ||||
| DS47 Data 47 | Read and write | ||||
| DS47 Data 48 | Read and write | ||||
| DS47 Data 49 | Read and write | ||||
| DS47 Data 50 | Read and write | ||||
| DS47 Data 51 | Read and write | ||||
| DS47 Data 52 | Read and write | ||||
| DS47 Data 53 | Read and write | ||||
| DS47 Data 54 | Read and write | ||||
| DS47 Data 55 | Read and write | ||||
| DS47 Data 56 | Read and write | ||||
| DS47 Data 57 | Read and write | ||||
| DS47 Data 58 | Read and write | ||||
| DS47 Data 59 | Read and write | ||||
| DS47 Data 60 | Read and write | ||||
| DS47 Data 61 | Read and write | ||||
| DS47 Data 62 | Read and write | ||||
| DS47 Data 63 | Read and write | ||||
| DS47 Data 64 | Read and write | ||||
| DS47 Data 65 | Read and write | ||||
| DS47 Data 66 | Read and write | ||||
| DS47 Data 67 | Read and write | ||||
| DS47 Data 68 | Read and write | ||||
| DS47 Data 69 | Read and write | ||||
| DS47 Data 70 | Read and write | ||||
| DS47 Data 71 | Read and write | ||||
| DS47 Data 72 | Read and write | ||||
| DS47 Data 73 | Read and write | ||||
| DS47 Data 74 | Read and write | ||||
| DS47 Data 75 | Read and write | ||||
| DS47 Data 76 | Read and write | ||||
| DS47 Data 77 | Read and write | ||||
| DS47 Data 78 | Read and write | ||||
| DS47 Data 79 | Read and write | ||||
| DS47 Data 80 | Read and write | ||||
| DS47 Data 81 | Read and write | ||||
| DS47 Data 82 | Read and write | ||||
| DS47 Data 83 | Read and write | ||||
| DS47 Data 84 | Read and write | ||||
| DS47 Data 85 | Read and write | ||||
| DS47 Data 86 | Read and write | ||||
| DS47 Data 87 | Read and write | ||||
| DS47 Data 88 | Read and write | ||||
| DS47 Data 89 | Read and write | ||||
| DS47 Data 90 | Read and write | ||||
| DS47 Data 91 | Read and write | ||||
| DS47 Data 92 | Read and write | ||||
| DS47 Data 93 | Read and write | ||||
| DS47 Data 94 | Read and write | ||||
| DS47 Data 95 | Read and write | ||||
| DS47 Data 96 | Read and write | ||||
| DS47 Data 97 | Read and write | ||||
| DS47 Data 98 | Read and write | ||||
| DS47 Data 99 | Read and write | ||||
| DS47 Data 100 | Read and write | ||||
| DS47 Data 101 | Read and write | ||||
| DS47 Data 102 | Read and write | ||||
| DS47 Data 103 | Read and write | ||||
| DS47 Data 104 | Read and write | ||||
| DS47 Data 105 | Read and write | ||||
| DS47 Data 106 | Read and write | ||||
| DS47 Data 107 | Read and write | ||||
| DS47 Data 108 | Read and write | ||||
| DS47 Data 109 | Read and write | ||||
| DS47 Data 110 | Read and write | ||||
| DS47 Data 111 | Read and write | ||||
| DS47 Data 112 | Read and write | ||||
| DS47 Data 113 | Read and write | ||||
| DS47 Data 114 | Read and write | ||||
| DS47 Data 115 | Read and write | ||||
| DS47 Data 116 | Read and write | ||||
| DS47 Data 117 | Read and write | ||||
| DS47 Data 118 | Read and write | ||||
| DS47 Data 119 | Read and write | ||||
| DS47 Data 120 | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show frequency, current and power of every pump and fan drive on one dashboard.
- Get an email when the fault bit is set or the output current rises above a threshold you set.
- Track energy consumption per drive in the history to compare motors and running hours.
- Lower the frequency setpoint of a fan at night with an automation on a schedule.
- Adjust ramp times, fixed frequencies or the PID setpoint remotely after commissioning.
Installation
Wire the RS485 terminals P+ and N- of the converter to the RS485 A and B terminals of the ModbusCloud Gateway and terminate the bus at both ends.
On the converter, set P0003 = 3, P2023 = 2 (Modbus) and P0700 = 5 for control over RS485; check P2021 (address 1) and P2010 (9600 baud).
Switch the converter off, wait until the display is blank, and switch it on again so the protocol change takes effect.
In ModbusCloud, add a Modbus device (RTU) with address 1, 9600 baud, 8 data bits, even parity and 1 stop bit, and import this template.
Check that DC bus voltage and converter version show plausible values.
Things to watch for
The converter does not answer. What should I check?
Check P2023 = 2 and power-cycle the converter after changing it; wait until the display is blank before switching on. Check address P2021, baud rate P2010, parity P2034 and stop bits P2035 against the device in ModbusCloud. Swap P+ and N- if nothing comes back.
Why does the converter trip with fault F72?
When the controller sends process data, the converter monitors the time between telegrams with P2014. If no new telegram arrives in time, it trips with F72. Increase P2014 or set it to 0 when the converter is only monitored.
Can several converters share one RS485 line?
Yes. Give each converter its own address in P2021 (1 to 247) and use the same baud rate and parity on all of them. Wire the bus as one line from converter to converter and terminate both ends.
What should I keep in mind when I write settings?
Start, stop and setpoint only work when P0700 = 5. Writes take effect immediately. Writing a digital output sets its interconnection to a fixed 0 or 1 and the previous link is lost. Read the current value first and change one setting at a time.
Want to see how it works?












