Agrowtek Agrowtek PHX pH Sensor Modbus RTU template

Agrowtek PHX pH Sensor

pH and temperature transmitter for nutrient solution, with ORP or oxygen on the PHX+.

The Agrowtek PHX is a hydroponics transmitter that measures pH and temperature, and on the PHX+ also ORP or dissolved oxygen, in nutrient tanks and fertigation systems. This Modbus RTU template reads all sensor values and identification, and lets you write pH and temperature calibration and the device address from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
24, read and write
Key readings
pH · Temperature · ORP or dissolved oxygen
Available commands
pH calibration · Temperature calibration · Analog output calibration · Device address
Compatible models
PHX · PHXM · PHX+ · Agrowtek PHX and PHX+ hydroponics sensor transmitter, temperature and pH (+ORP or DO)
Last updated

Registers (24)

14 read, 11 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
pHpHRead
Temperature°CRead
ORP or DORead
pH FloatpHRead
Temperature Float°CRead
ORP or DO FloatRead
Temperature Offset Calibration°CWrite
pH Offset CalibrationpHWrite
ORP Offset CalibrationWrite
Temperature Span Calibration°CWrite
pH Span CalibrationpHWrite
ORP Span CalibrationWrite
Temperature Analog Output CalibrationWrite
pH Analog Output CalibrationWrite
ORP Analog Output CalibrationWrite
Clear CalibrationWrite
Device AddressRead and write
Baud RateRead
Data FormatRead
Serial NumberRead
Date of ManufactureRead
Hardware VersionRead
Firmware VersionRead
Device ModelRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Send an alert when the pH of a nutrient tank leaves its target band.
  • Show pH and solution temperature of every tank on one dashboard.
  • Compare pH drift over 365 days of history to plan probe cleaning or replacement.
  • Check after a pH 7 and pH 4 calibration that the reading is back on track.
  • Watch ORP in a disinfection loop on the PHX+ and alert on low values.

Installation

  1. Fit the pH and temperature probes and connect the PHX GrowNET RJ45 port to an Agrowtek LX2 ModLINK, never to an Ethernet network.

  2. Wire TX/RX+ and TX/RX- of the LX2 to RS485 A and B of the ModbusCloud Gateway, with termination at the bus ends.

  3. Give the PHX a unique address in the SETUP menu and leave the LX2 at 19200 baud, 8 data bits, no parity, 1 stop bit.

  4. In ModbusCloud, add a Modbus RTU device with that address and import this template.

  5. Check pH in a pH 7 buffer and compare temperature with a reference.

Things to watch for

The transmitter does not answer Modbus requests.

The PHX speaks Modbus only through an LX2 ModLINK on its GrowNET port. Check the RJ45 cable, the LX2 power, A and B wiring and the address. Do not connect the GrowNET port to an Ethernet switch.

The pH reading is slow or off by more than 0.2 pH.

Clean and recondition the pH probe as described for the probe, then calibrate: pH 7 first, then pH 4.01 or 10. A probe that stays slow after cleaning is worn and needs replacing.

How do I calibrate pH from ModbusCloud?

With the probe in pH 7 buffer write 700 to pH Offset Calibration. Then rinse, put it in pH 4.01 buffer and write 401 to pH Span Calibration. Always do the offset first. Writing 1 to Clear Calibration restores the factory values.