Belimo Belimo 2-way EPIV Modbus RTU Modbus RTU template

Belimo 2-way EPIV Modbus RTU

Controls pressure-independent characterised valves for HVAC water-side modulating control

Template for the Belimo 2-way EPIV electronically pressure-independent characterised control valve via Modbus RTU. Reads flow measurement, valve position, and fault diagnostics. Allows setpoint control, override commands, and bus fail position configuration for HVAC water-side systems.

Protocol
Modbus RTU
Connection
RS485, 38400 baud
Registers
26, read and write
Brand
Belimo
Key readings
Relative and Absolute Position · Relative Volumetric Flow · Absolute Volumetric Flow · Sensor 1 Value · Malfunction and Service Information · Control Mode
Available commands
Setpoint · Override Control · Bus Fail Position · Maximum Flow Limit
Compatible models
EP..R+MOD · P6..W..E-MOD
Last updated

Registers (26)

16 read, 10 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Actuator TypeRead
Relative Position%Read
Absolute Position°CRead
Sensor 1 ValueRead
Setpoint Analog%Read
Series Number 1st PartRead
Series Number 2nd PartRead
Series Number 4th PartRead
Firmware VersionRead
Malfunction and Service InformationRead
Relative volumetric flow%Read
Absolute volumetric flow in liter per minl/minRead
Absolute volumetric flow in selected unitsl/minRead
Nominal volumetric flow in liter per minutel/minRead
Nominal volumetric flow in selected unitl/minRead
Control modeRead
Setpoint%Write
Override ControlWrite
CommandWrite
Bus TerminationWrite
Maximum%Write
Sensor 1 TypeWrite
Bus Fail PositionWrite
Timeout for Bus Watchdog in ssWrite
Setpoint SourceWrite
Unit selection flowWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time volumetric flow and valve position on a live dashboard for each HVAC zone.
  • Create an alert when a malfunction or service flag is raised on any connected EPIV valve.
  • Adjust flow setpoints remotely to balance heating or cooling distribution across multiple zones.
  • Configure the bus fail position to ensure safe actuator behavior during communication loss.
  • Track flow trends over time to identify valves that do not close tightly or consumers stuck in manual mode.
  • Set a maximum flow limit per valve to prevent overconsumption in peak demand periods.

Installation

  1. Wire the Modbus RTU A and B terminals of the Belimo EPIV actuator to the RS-485 port on the ModbusCloud Gateway, observing correct polarity.

  2. Set the baud rate on the EPIV actuator to 38400 and assign a unique Modbus slave address, ensuring no address conflicts on the bus.

  3. Connect a 120 ohm termination resistor at the last device on the RS-485 bus if the cable run exceeds a few meters or multiple devices are daisy-chained.

  4. In the ModbusCloud portal, add a new device connection using Modbus RTU and enter the slave address and baud rate matching the actuator configuration.

  5. Import the Belimo 2-way EPIV Modbus RTU template from the ModbusCloud template library and assign it to the device connection.

  6. Verify that live readings for valve position and volumetric flow appear on the dashboard, then configure the desired flow display unit via register 117 if needed.

Things to watch for

The gateway cannot communicate with the EPIV actuator. What should I check?

Verify that the baud rate is set to 38400 on both the gateway and the actuator. Confirm correct RS-485 wiring polarity (A to A, B to B). Check that the Modbus slave address configured in ModbusCloud matches the address set on the actuator.

Absolute volumetric flow readings look incorrect or show zero. Why?

Absolute volumetric flow at register 10 is a uint32 value spanning two consecutive registers. Ensure the template reads both registers and uses the correct byte order. Also verify the flow unit selection at register 117 matches your expected unit.

What happens to the valve if the Modbus connection drops?

The actuator moves to the position defined in the Bus Fail Position register. Configure this value during commissioning to ensure safe behavior, such as closing the valve or holding the last position, depending on your application requirements.

Can I use this template for a Belimo Energy Valve?

No. The EPIV template does not cover features specific to the Energy Valve, such as integrated temperature sensors, power monitoring registers, or Modbus TCP. Use the dedicated Belimo Energy Valve template if available.

Want to see how it works?

Electrician working in an open distribution board