Belimo Belimo Air-Water Actuator Modbus RTU Modbus RTU template

Belimo Air-Water Actuator Modbus RTU

Controls communicative damper and valve actuators via Modbus RTU.

Modbus RTU template for Belimo communicative damper and valve actuators. Reads position feedback, sensor values, and actuator status. Allows setpoint control, override commands, and configuration of position limits and bus fail behavior.

Protocol
Modbus RTU
Connection
RS485, 38400 baud
Registers
20, read and write
Brand
Belimo
Key readings
Relative Position (%) · Absolute Position (°) · Sensor 1 Value · Setpoint Analog (%) · Actuator Type · Malfunction and Service Information
Available commands
Setpoint (%) · Override Control · Min/Max Position (%) · Bus Fail Position
Compatible models
..M(C)24A-MOD · ..R24A-MOD · ..V(K)24A-MOD · ..F24A-MOD · ..RF24A-MOD
Last updated

Registers (20)

10 read, 10 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Actuator TypeRead
Relative Position%Read
Absolute Position°CRead
Sensor 1 ValueRead
Setpoint Analog%Read
Series Number 1st PartRead
Series Number 2nd PartRead
Series Number 4th PartRead
Firmware VersionRead
Malfunction and Service InformationRead
Setpoint%Write
Override ControlWrite
CommandWrite
Bus TerminationWrite
Minimum Position in Percent%Write
Maximum Position in Percent%Write
Sensor 1 TypeWrite
Bus Fail PositionWrite
Timeout for Bus Watchdog in ssWrite
Setpoint SourceWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor actuator position and sensor values on a live cloud dashboard for remote HVAC oversight.
  • Create an alert when the actuator reports a malfunction or service flag to speed up maintenance response.
  • Adjust damper or valve setpoints remotely without an on-site visit, reducing travel time and cost.
  • Log actuator position data over time to verify correct modulating behavior and diagnose control issues.
  • Configure bus fail position and watchdog timeout remotely to ensure safe actuator behavior on communication loss.
  • Track multiple Belimo actuators across sites in a single ModbusCloud project for centralized building management.

Installation

  1. Wire the Modbus RTU bus (A and B terminals) from your ModbusCloud Gateway to the Belimo actuator, observing correct polarity.

  2. Set the actuator Modbus address to a unique value on the bus and configure the baud rate to 38400 to match the template.

  3. Enable bus termination on the last device by writing to register 99, or use a physical termination resistor at the end of the bus.

  4. Configure the setpoint source register (address 118) so the actuator accepts setpoint commands from the Modbus bus.

  5. Import the Belimo Air-Water Actuator Modbus RTU template in the ModbusCloud portal and assign it to the correct gateway and slave address.

  6. Optionally configure the bus watchdog timeout (address 109) and bus fail position (address 108) for safe behavior on communication loss.

Things to watch for

The actuator does not respond on the Modbus bus. What should I check?

Verify that the baud rate on the actuator matches 38400 as required by this template. Also confirm the Modbus slave address is unique and that A/B wiring polarity is correct.

Setpoint commands are sent but the actuator does not move. Why?

The setpoint source register (address 118) must be configured to select the Modbus bus as the active setpoint input. If it is set to another source, the actuator ignores Modbus setpoint writes.

Do I need a physical termination resistor on the bus?

Belimo actuators support software-based bus termination via register 99. Write the appropriate value to enable termination on the last device. A physical resistor is not required if software termination is active.

What happens if the gateway loses communication with the actuator?

The actuator moves to the position defined in the bus fail position register (address 108) after the watchdog timeout (address 109) expires. Configure both registers to ensure safe damper or valve behavior during communication loss.