Belimo JR Actuator Modbus RTU
Controls rotary actuators for butterfly valves via Modbus RTU.
Template for Belimo JR rotary actuators used with butterfly valves via Modbus RTU. Reads position feedback, temperature sensors, and malfunction status. Allows remote control of position setpoints, override mode, and bus watchdog configuration.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 29, read and write
- Brand
- Belimo
- Key readings
- Relative position (%) · Absolute position (°) · Sensor 1 temperature · Sensor 2 temperature · Analog setpoint (%) · Malfunction and service info
- Available commands
- Relative setpoint (%) · Override control · Maximum limit (%) · Bus watchdog settings
- Compatible models
- Belimo JR
- Last updated
Registers (29)
18 read, 11 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Device type | Read | ||||
| Relative position | % | Read | |||
| Absolute position | °C | Read | |||
| Analog setpoint | % | Read | |||
| Sensor 1 value | Read | ||||
| Sensor 1 temperature in Celcius | °C | Read | |||
| Sensor 1 temperature in Fahrenheit | °F | Read | |||
| Sensor 1 temperature in selected unit | °C | Read | |||
| Sensor 2 value | Read | ||||
| Sensor 2 temperature in Celcius | °C | Read | |||
| Sensor 2 temperature in Fahrenheit | °F | Read | |||
| Sensor 2 temperature in selected unit | °C | Read | |||
| Bus termination | Read | ||||
| Seies number 1st part | Read | ||||
| Series number 2nd part | Read | ||||
| Series number 4th part | Read | ||||
| Firmware version | Read | ||||
| Malfunction and service information | Read | ||||
| Relative setpoint | % | Write | |||
| Override control | Write | ||||
| Maximum limit | % | Write | |||
| Bus watchdog fail action | Write | ||||
| Timeout for bus watchdog | s | Write | |||
| Setpoint source | Write | ||||
| Sensor type | Write | ||||
| Sensor 1 passive type | Write | ||||
| Sensor 2 type | Write | ||||
| Sensor 2 passive type | Write | ||||
| Select temperature unit | Write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Monitor real-time valve position and temperature sensor readings on a cloud dashboard for remote HVAC sites.
- Create an alert when a malfunction flag is raised so the installer can respond before comfort is affected.
- Adjust the relative position setpoint of a butterfly valve remotely to rebalance a chilled water circuit.
- Configure the bus watchdog timeout and fail action to ensure safe valve behavior during communication loss.
- Track actuator service information over time to plan preventive maintenance across multiple buildings.
Installation
Wire the ModbusCloud Gateway to the Belimo JR actuator using a shielded RS-485 cable, connecting A, B, and GND terminals.
Set a unique Modbus RTU address on the Belimo JR actuator using the device's configuration interface or DIP switches.
Confirm the baud rate is set to 19200 on both the actuator and the ModbusCloud gateway.
Check bus termination by reading register 99 and enable termination on the last device of the RS-485 daisy chain.
Import the Belimo JR Actuator Modbus RTU template in the ModbusCloud platform and assign it to the correct gateway and Modbus address.
Verify live data in the ModbusCloud dashboard by confirming position feedback and temperature values are updating correctly.
Things to watch for
The gateway cannot communicate with the Belimo JR actuator. What should I check?
Verify that the RS-485 wiring is correct (A to A, B to B, GND to GND). Confirm the baud rate is set to 19200 on both the gateway and the actuator, and ensure the Modbus address is unique on the bus.
How do I verify bus termination?
Read register 99 on the actuator to check the current bus termination status. Enable termination only on the first and last device of the RS-485 bus segment.
What happens if the Modbus connection is lost?
The bus watchdog feature defines the actuator behavior on communication loss. Configure the watchdog fail action and timeout registers through the template to set a safe fallback position for the valve.
Can I connect multiple Belimo JR actuators to one gateway?
Yes, daisy-chain multiple actuators on the same RS-485 bus. Each actuator must have a unique Modbus address. Add a separate template instance in ModbusCloud for each device.