Belimo Belimo 6-way EPIV V4 Modbus RTU Modbus RTU template

Belimo 6-way EPIV V4 Modbus RTU

Controls 6-way pressure-independent valves with ultrasonic flow measurement and condensation monitoring.

Template for the Belimo 6-way EPIV V4 characterised control valve over Modbus RTU. Reads valve position, volumetric flow, temperature, humidity, condensation status, and accumulated volume. Controls setpoints per sequence, flow limits, control mode, and condensation protection settings.

Protocol
Modbus RTU
Connection
RS485, 38400 baud
Registers
58, read and write
Brand
Belimo
Key readings
Relative and absolute position · Relative and absolute volumetric flow · Flow body temperature · Accumulated volume · Relative humidity · Condensation protection status
Available commands
Setpoint relative per sequence · Control mode and setpoint source · Max flow limit per sequence · Condensation protection settings
Compatible models
EP..R6+BAC · EP..R6+BAC-HH1 · EP..R6+BAC-HH2 · EP..R6+BAC-HHM
Last updated

Registers (58)

32 read, 26 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Relative position%Read
Absolute position°CRead
Relative volumetric flow%Read
Absolute volumetric flow in selected unitl/hRead
Setpoint analog%Read
Temperature (flow body) in Celcius°CRead
Temperature (flow body) in Fahrenheit°FRead
Glycol concentration%Read
Series number 1st partRead
Series number 2nd partRead
Series number 4th partRead
Firmware versionRead
Error stateRead
Absolute volumetric flow in liter per secondl/sRead
Absolute volumetric flow in gpmgpmRead
Setpoint absolute flow in selected unitl/hRead
Nominal volumetric flow in selected unitl/hRead
Nominal volumetric flow in liter per secondl/sRead
Nominal volumetric flow in gpmgpmRead
Sensor 1 valuemVRead
Setpoint absolute flow in liter per secondl/sRead
Setpoint absolute flow in gpmgpmRead
Accumulated volume in cubic meterm³Read
Accumulated volume in gallongalRead
Accumulated volume in selected unitl/hRead
Bus TerminationRead
Flow meter serial number first digitsRead
Flow meter serial number last digitsRead
Device TypeRead
Actual sequenceRead
Relative humidity%Read
Condensation protection statusRead
Setpoint relative%Write
Override controlWrite
Control ModeWrite
Unit Selection FlowWrite
Setpoint sourceWrite
CommandWrite
Timeout for bus watchdogsWrite
Bus fail actionWrite
Sensor 1 typeWrite
Unit Selection VolumeWrite
Setpoint relative for sequence 1%Write
Setpoint relative for sequence 2%Write
Setpoint modeWrite
Invert sequencesWrite
Max. flow limit for sequence 1 in percent%Write
Max. flow limit for sequence 2 in percent%Write
Max. flow limit for sequence 1 in liter per secondl/sWrite
Max. flow limit for sequence 1 in gpmgpmWrite
Max. flow limit for sequence 1 in selected unitl/hWrite
Max. flow limit for sequence 2 in liter per secondl/sWrite
Max. flow limit for sequence 2 in gpmgpmWrite
Max. flow limit for sequence 2 in selected unitl/hWrite
Enable condensation protectionWrite
Condensation protection actionWrite
Condensation warning threshold%Write
Condensation action delaysWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time volumetric flow and valve position on a live dashboard to verify hydronic balancing across zones.
  • Create an alert when condensation protection activates so the installer can investigate cooling circuit conditions remotely.
  • Log accumulated volume per zone over time to analyse energy consumption patterns for heating and cooling.
  • Adjust maximum flow limits per sequence remotely to optimise comfort without a site visit.
  • Switch between heating and cooling setpoints based on room demand and schedule from the cloud interface.
  • Verify correct commissioning by comparing measured flow against design flow for each sequence after installation.

Installation

  1. Wire the Belimo EPIV actuator RS-485 terminals (A, B, GND) to the corresponding terminals on the ModbusCloud Gateway.

  2. Set the Modbus slave address on the actuator using the Belimo Assistant 2 app via NFC or through the on-device interface.

  3. Confirm the baud rate is set to 38400 on both the actuator and the gateway serial port configuration.

  4. Import the Belimo 6-way EPIV V4 template in the ModbusCloud platform and assign it to the correct gateway and serial port.

  5. Select the desired flow unit (l/s, gpm, or l/h) in the unit selection registers to match your project requirements.

  6. Power up the system and verify live data appears on the ModbusCloud dashboard before closing the installation.

Things to watch for

Why do I see zero or incorrect values for flow and accumulated volume registers?

These registers are uint32 values spanning two consecutive Modbus addresses. Make sure the template is correctly mapping both addresses. Also verify the byte order setting on the gateway matches the Belimo default (big-endian).

What baud rate should I use for the Belimo 6-way EPIV?

The default baud rate for this template is 38400. Both the actuator and the ModbusCloud gateway serial port must be configured to 38400 with matching parity and stop bit settings.

Can I mix multiple Belimo EPIV actuators on one RS-485 bus?

Yes. Each actuator must have a unique Modbus slave address. Use the Belimo Assistant 2 app to set the address on each device before connecting them to the shared bus.

How does condensation protection work through Modbus?

The actuator monitors relative humidity and flow body temperature internally. The template reads the condensation protection status register and allows you to adjust protection settings. Set up an alert in ModbusCloud to be notified when condensation risk is detected.

Want to see how it works?

Electrician working in an open distribution board