ModbusCloud
Back to library
Carlo Gavazzi Carlo Gavazzi EM210 Modbus RTU template
Modbus RTU

Carlo Gavazzi EM210

Carlo Gavazzi

Three-phase energy meter via CTs: voltage, current, power, energy and THD.

Overview

The Carlo Gavazzi EM210 is a three-phase energy meter that measures electricity through current transformers in distribution boards of buildings, workshops and solar installations. This Modbus RTU template reads voltage, current, power, energy and THD, and lets you set the CT ratio and measuring system and reset the meters from ModbusCloud.

Key readings

  • Active power
  • Imported active energy
  • Exported active energy
  • Current per phase
  • Voltage per phase
  • Power factor
  • THD

Available commands

  • CT ratio
  • Measuring system
  • Meter reset

Use cases

  • Show active power and energy of a sub-distribution board or PV system on a dashboard.
  • Track imported and exported energy in the history to see self-consumption of solar panels.
  • Get an email when the current per phase rises above a threshold you set.
  • Watch THD per phase to find loads that pollute the grid.
  • Compare consumption between tenants or departments with one meter per group.

Installation

  1. 1Connect the RS485 terminals of the meter to the RS485 A and B terminals of the ModbusCloud Gateway and terminate the bus at both ends.
  2. 2On the meter, set the measuring system, the CT ratio and the Modbus address; the factory serial setting is 9600 baud, no parity, 1 stop bit.
  3. 3In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings, and import this template.
  4. 4Check that voltage, current and active energy match the display of the meter.

Things to watch for

The meter does not answer. What should I check?
Check address, baud rate and parity on the meter against the device in ModbusCloud; the factory setting is 9600 baud, no parity, 1 stop bit. Swap A and B if nothing comes back and terminate the bus at both ends.
Why are currents and energy too small?
The meter scales values with the CT ratio set on the meter. Check CT Ratio in the template against the current transformers you installed, for example 20 for 100/5 A. The CT ratio times the VT ratio is limited to avoid overflow.
Can several meters share one RS485 line?
Yes. Give each meter its own address from 1 to 247 and use the same baud rate and parity on all of them. Wire the bus as one line from meter to meter and terminate both ends.
What should I keep in mind when I write a setting?
Writes take effect immediately; an invalid value is replaced by the minimum valid value. A new address or baud rate applies right away, so change the device in ModbusCloud too. Reset Meters clears all energy and hour counters.

Registers (112)

112 read / 16 write

NameAddressFunctionTypeUnitAccess
Voltage L1-N•••••••••VR
Voltage L2-N•••••••••VR
Voltage L3-N•••••••••VR
Voltage L1-L2•••••••••VR
Voltage L2-L3•••••••••VR
Voltage L3-L1•••••••••VR
Current L1•••••••••AR
Current L2•••••••••AR
Current L3•••••••••AR
Active Power L1•••••••••WR
Active Power L2•••••••••WR
Active Power L3•••••••••WR
Apparent Power L1•••••••••VAR
Apparent Power L2•••••••••VAR
Apparent Power L3•••••••••VAR
Reactive Power L1•••••••••varR
Reactive Power L2•••••••••varR
Reactive Power L3•••••••••varR
Voltage L-N System•••••••••VR
Voltage L-L System•••••••••VR
Active Power Total•••••••••WR
Apparent Power Total•••••••••VAR
Reactive Power Total•••••••••varR
Power Factor L1•••••••••R
Power Factor L2•••••••••R
Power Factor L3•••••••••R
Power Factor Total•••••••••R
Phase Sequence•••••••••R
Frequency•••••••••HzR
Imported Active Energy•••••••••kWhR
Imported Reactive Energy•••••••••kvarhR
Exported Active Energy•••••••••kWhR
Hour Counter•••••••••hR
Hour Counter Negative•••••••••hR
THD Current L1•••••••••%R
THD Current L2•••••••••%R
THD Current L3•••••••••%R
THD Voltage L-N System•••••••••%R
THD Voltage V1-N•••••••••%R
THD Voltage V2-N•••••••••%R
THD Voltage V3-N•••••••••%R
THD Voltage L-L System•••••••••%R
THD Voltage V12•••••••••%R
THD Voltage V23•••••••••%R
THD Voltage V31•••••••••%R
Neutral Current•••••••••AR
Hour Counter Negative (Phase Table)•••••••••hR
Neutral Current (Phase Table)•••••••••AR
Hour Counter (Phase Table)•••••••••hR
Voltage L-N System (Phase Table)•••••••••VR
Voltage L-L System (Phase Table)•••••••••VR
Active Power Total (Phase Table)•••••••••WR
Apparent Power Total (Phase Table)•••••••••VAR
Reactive Power Total (Phase Table)•••••••••varR
Power Factor Total (Phase Table)•••••••••R
Phase Sequence (Phase Table)•••••••••R
Frequency (Phase Table)•••••••••HzR
Imported Active Energy (Phase Table)•••••••••kWhR
Imported Reactive Energy (Phase Table)•••••••••kvarhR
Exported Active Energy (Phase Table)•••••••••kWhR
Voltage L1-L2 (Phase Table)•••••••••VR
Voltage L1-N (Phase Table)•••••••••VR
Current L1 (Phase Table)•••••••••AR
Active Power L1 (Phase Table)•••••••••WR
Apparent Power L1 (Phase Table)•••••••••VAR
Reactive Power L1 (Phase Table)•••••••••varR
Power Factor L1 (Phase Table)•••••••••R
Voltage L2-L3 (Phase Table)•••••••••VR
Voltage L2-N (Phase Table)•••••••••VR
Current L2 (Phase Table)•••••••••AR
Active Power L2 (Phase Table)•••••••••WR
Apparent Power L2 (Phase Table)•••••••••VAR
Reactive Power L2 (Phase Table)•••••••••varR
Power Factor L2 (Phase Table)•••••••••R
Voltage L3-L1 (Phase Table)•••••••••VR
Voltage L3-N (Phase Table)•••••••••VR
Current L3 (Phase Table)•••••••••AR
Active Power L3 (Phase Table)•••••••••WR
Apparent Power L3 (Phase Table)•••••••••VAR
Reactive Power L3 (Phase Table)•••••••••varR
Power Factor L3 (Phase Table)•••••••••R
THD Current L1 (Phase Table)•••••••••%R
THD Voltage V1-N (Phase Table)•••••••••%R
THD Voltage V12 (Phase Table)•••••••••%R
THD Current L2 (Phase Table)•••••••••%R
THD Voltage V2-N (Phase Table)•••••••••%R
THD Voltage V23 (Phase Table)•••••••••%R
THD Current L3 (Phase Table)•••••••••%R
THD Voltage V3-N (Phase Table)•••••••••%R
THD Voltage V31 (Phase Table)•••••••••%R
Version Code•••••••••R
Revision Code•••••••••R
Programming Lock•••••••••R
Password•••••••••R/W
Measuring System•••••••••R/W
CT Ratio•••••••••R/W
VT Ratio•••••••••R/W
Wrong Connection Check•••••••••R/W
Wrong Connection Status•••••••••R/W
THD Calculation•••••••••R/W
Hour Counter Start Current•••••••••AR/W
Pulse Duration•••••••••R/W
kWh Per Pulse•••••••••kWhR/W
Application Type•••••••••R/W
RS485 Address•••••••••R/W
RS485 Baud Rate•••••••••R/W
RS485 Parity•••••••••R/W
RS485 Stop Bits•••••••••R/W
Reset Meters•••••••••R/W
Serial Number•••••••••R
Production Year•••••••••R
Secondary Address•••••••••R

Loading registers…

Read the Carlo Gavazzi EM210 remotely

We load the templates onto the gateway and set up your portal, you connect it at your customer's site. Tell us briefly what you need and we'll send a proposal.

From €295 + €149/year.

Prefer to configure it yourself? Order the gateway in the shop·Or see the live demo first

EU-hosted
Data in the Netherlands and Germany
Open standard
Based on Modbus RTU/TCP
Free to browse
No account or payment required
European company
Based in the Netherlands

More Carlo Gavazzi templates

More RTU templates