Circutor CVM-B100 / CVM-B150

Panel power analyzer that measures power, energy, power factor and THD on three-phase networks.

The Circutor CVM-B100 and CVM-B150 are panel power analyzers that measure voltage, current, power, energy and power quality in three-phase low and medium voltage installations. This Modbus RTU template reads all electrical values, energies, THD, cost and CO2 counters and the setup, and lets you send reset commands from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
367, read and write
Key readings
Phase voltage · Current · Active power · Power factor · Total active energy · Voltage and current THD · Frequency
Available commands
Reset energy counters · Reset maximum and minimum values · Delete logs
Compatible models
CVM-B100 · CVM-B150
Last updated

Registers (367)

345 read, 22 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Phase Voltage L1Read0FC04int32
Current L1Read2FC04int32
Active Power L1Read4FC04int32
Inductive Reactive Power L1Read6FC04int32
Capacitive Reactive Power L1Read8FC04int32
Apparent Power L1Read
Power Factor L1Read
Cos Phi L1Read
Phase Voltage L2Read
Current L2Read
Active Power L2Read
Inductive Reactive Power L2Read
Capacitive Reactive Power L2Read
Apparent Power L2Read
Power Factor L2Read
Cos Phi L2Read
Phase Voltage L3Read
Current L3Read
Active Power L3Read
Inductive Reactive Power L3Read
Capacitive Reactive Power L3Read
Apparent Power L3Read
Power Factor L3Read
Cos Phi L3Read
Neutral VoltageRead
Neutral CurrentRead
Frequency L1Read
Voltage L1-L2Read
Voltage L2-L3Read
Voltage L3-L1Read
Three-Phase Line VoltageRead
Three-Phase Phase VoltageRead
Three-Phase CurrentRead
Three-Phase Active PowerRead
Three-Phase Inductive Reactive PowerRead
Three-Phase Capacitive Reactive PowerRead
Three-Phase Apparent PowerRead
Three-Phase Power FactorRead
Three-Phase Cos PhiRead
Voltage THD L1Read
Voltage THD L2Read
Voltage THD L3Read
Voltage THD NeutralRead
Current THD L1Read
Current THD L2Read
Current THD L3Read
Current THD NeutralRead
Reactive Power L1Read
Reactive Power L2Read
Reactive Power L3Read
Three-Phase Reactive PowerRead
Reactive Power Consumed L1Read
Reactive Power Consumed L2Read
Reactive Power Consumed L3Read
Three-Phase Reactive Power ConsumedRead
Reactive Power Generated L1Read
Reactive Power Generated L2Read
Reactive Power Generated L3Read
Three-Phase Reactive Power GeneratedRead
Phase 1 QuadrantRead
Phase 2 QuadrantRead
Phase 3 QuadrantRead
Neutral QuadrantRead
Voltage UnitsRead
Current UnitsRead
Neutral Current UnitsRead
Frequency UnitsRead
Power and Energy UnitsRead
Harmonics UnitsRead
THD UnitsRead
Power Factor UnitsRead
Tariff Hours UnitsRead
CO2 Emissions UnitsRead
Cost UnitsRead
Total Active Energy Consumed L1kWhRead
Total Active Energy Consumed L1 DecimalWhRead
Total Active Energy Consumed L2kWhRead
Total Active Energy Consumed L2 DecimalWhRead
Total Active Energy Consumed L3kWhRead
Total Active Energy Consumed L3 DecimalWhRead
Total Active Energy Consumed Three-PhasekWhRead
Total Active Energy Consumed Three-Phase DecimalWhRead
Total Inductive Reactive Energy Consumed L1kvarhRead
Total Inductive Reactive Energy Consumed L1 DecimalvarhRead
Total Inductive Reactive Energy Consumed L2kvarhRead
Total Inductive Reactive Energy Consumed L2 DecimalvarhRead
Total Inductive Reactive Energy Consumed L3kvarhRead
Total Inductive Reactive Energy Consumed L3 DecimalvarhRead
Total Inductive Reactive Energy Consumed Three-PhasekvarhRead
Total Inductive Reactive Energy Consumed Three-Phase DecimalvarhRead
Total Capacitive Reactive Energy Consumed L1kvarhRead
Total Capacitive Reactive Energy Consumed L1 DecimalvarhRead
Total Capacitive Reactive Energy Consumed L2kvarhRead
Total Capacitive Reactive Energy Consumed L2 DecimalvarhRead
Total Capacitive Reactive Energy Consumed L3kvarhRead
Total Capacitive Reactive Energy Consumed L3 DecimalvarhRead
Total Capacitive Reactive Energy Consumed Three-PhasekvarhRead
Total Capacitive Reactive Energy Consumed Three-Phase DecimalvarhRead
Total Reactive Energy Consumed L1kvarhRead
Total Reactive Energy Consumed L1 DecimalvarhRead
Total Reactive Energy Consumed L2kvarhRead
Total Reactive Energy Consumed L2 DecimalvarhRead
Total Reactive Energy Consumed L3kvarhRead
Total Reactive Energy Consumed L3 DecimalvarhRead
Total Reactive Energy Consumed Three-PhasekvarhRead
Total Reactive Energy Consumed Three-Phase DecimalvarhRead
Total Apparent Energy Consumed L1kVAhRead
Total Apparent Energy Consumed L1 DecimalVAhRead
Total Apparent Energy Consumed L2kVAhRead
Total Apparent Energy Consumed L2 DecimalVAhRead
Total Apparent Energy Consumed L3kVAhRead
Total Apparent Energy Consumed L3 DecimalVAhRead
Total Apparent Energy Consumed Three-PhasekVAhRead
Total Apparent Energy Consumed Three-Phase DecimalVAhRead
Total Active Energy Generated L1kWhRead
Total Active Energy Generated L1 DecimalWhRead
Total Active Energy Generated L2kWhRead
Total Active Energy Generated L2 DecimalWhRead
Total Active Energy Generated L3kWhRead
Total Active Energy Generated L3 DecimalWhRead
Total Active Energy Generated Three-PhasekWhRead
Total Active Energy Generated Three-Phase DecimalWhRead
Total Inductive Reactive Energy Generated L1kvarhRead
Total Inductive Reactive Energy Generated L1 DecimalvarhRead
Total Inductive Reactive Energy Generated L2kvarhRead
Total Inductive Reactive Energy Generated L2 DecimalvarhRead
Total Inductive Reactive Energy Generated L3kvarhRead
Total Inductive Reactive Energy Generated L3 DecimalvarhRead
Total Inductive Reactive Energy Generated Three-PhasekvarhRead
Total Inductive Reactive Energy Generated Three-Phase DecimalvarhRead
Total Capacitive Reactive Energy Generated L1kvarhRead
Total Capacitive Reactive Energy Generated L1 DecimalvarhRead
Total Capacitive Reactive Energy Generated L2kvarhRead
Total Capacitive Reactive Energy Generated L2 DecimalvarhRead
Total Capacitive Reactive Energy Generated L3kvarhRead
Total Capacitive Reactive Energy Generated L3 DecimalvarhRead
Total Capacitive Reactive Energy Generated Three-PhasekvarhRead
Total Capacitive Reactive Energy Generated Three-Phase DecimalvarhRead
Total Reactive Energy Generated L1kvarhRead
Total Reactive Energy Generated L1 DecimalvarhRead
Total Reactive Energy Generated L2kvarhRead
Total Reactive Energy Generated L2 DecimalvarhRead
Total Reactive Energy Generated L3kvarhRead
Total Reactive Energy Generated L3 DecimalvarhRead
Total Reactive Energy Generated Three-PhasekvarhRead
Total Reactive Energy Generated Three-Phase DecimalvarhRead
Total Apparent Energy Generated L1kVAhRead
Total Apparent Energy Generated L1 DecimalVAhRead
Total Apparent Energy Generated L2kVAhRead
Total Apparent Energy Generated L2 DecimalVAhRead
Total Apparent Energy Generated L3kVAhRead
Total Apparent Energy Generated L3 DecimalVAhRead
Total Apparent Energy Generated Three-PhasekVAhRead
Total Apparent Energy Generated Three-Phase DecimalVAhRead
Active Energy Hours Consumed Tariff 1Read
Cost of Active Energy Consumed Tariff 1Read
CO2 Emissions Consumed Tariff 1Read
Active Energy Hours Generated Tariff 1Read
Cost of Active Energy Generated Tariff 1Read
CO2 Emissions Generated Tariff 1Read
Active Energy Hours Consumed Tariff 2Read
Cost of Active Energy Consumed Tariff 2Read
CO2 Emissions Consumed Tariff 2Read
Active Energy Hours Generated Tariff 2Read
Cost of Active Energy Generated Tariff 2Read
CO2 Emissions Generated Tariff 2Read
Active Energy Hours Consumed Tariff 3Read
Cost of Active Energy Consumed Tariff 3Read
CO2 Emissions Consumed Tariff 3Read
Active Energy Hours Generated Tariff 3Read
Cost of Active Energy Generated Tariff 3Read
CO2 Emissions Generated Tariff 3Read
Active Energy Hours Consumed TotalRead
Cost of Active Energy Consumed TotalRead
CO2 Emissions Consumed TotalRead
Active Energy Hours Generated TotalRead
Cost of Active Energy Generated TotalRead
CO2 Emissions Generated TotalRead
V1-V2 Angle°Read
V2-V3 Angle°Read
V3-V1 Angle°Read
V1-I1 Angle°Read
V2-I2 Angle°Read
V3-I3 Angle°Read
Internal Temperature°CRead
Firmware VersionRead
Last Calibration DayRead
Last Calibration MonthRead
Last Calibration YearRead
Last Calibration HourRead
Last Calibration MinuteRead
Last Calibration SecondRead
Digital Input 1 StatusRead
Digital Input 2 StatusRead
Current TariffRead
Relay Output 1 Alarm LatchRead
Relay Output 1 Connection Delay CounterRead
Relay Output 1 Disconnection Delay CounterRead
Relay Output 1 Alarm Activation YearRead
Relay Output 1 Alarm Activation MonthRead
Relay Output 1 Alarm Activation DayRead
Relay Output 1 Alarm Activation HourRead
Relay Output 1 Alarm Activation MinuteRead
Relay Output 1 Alarm Activation SecondRead
Relay Output 1 Alarm StatusRead
Relay Output 2 Alarm LatchRead
Relay Output 2 Connection Delay CounterRead
Relay Output 2 Disconnection Delay CounterRead
Relay Output 2 Alarm Activation YearRead
Relay Output 2 Alarm Activation MonthRead
Relay Output 2 Alarm Activation DayRead
Relay Output 2 Alarm Activation HourRead
Relay Output 2 Alarm Activation MinuteRead
Relay Output 2 Alarm Activation SecondRead
Relay Output 2 Alarm StatusRead
Transistor Output 1 Alarm LatchRead
Transistor Output 1 Connection Delay CounterRead
Transistor Output 1 Disconnection Delay CounterRead
Transistor Output 1 Alarm Activation YearRead
Transistor Output 1 Alarm Activation MonthRead
Transistor Output 1 Alarm Activation DayRead
Transistor Output 1 Alarm Activation HourRead
Transistor Output 1 Alarm Activation MinuteRead
Transistor Output 1 Alarm Activation SecondRead
Transistor Output 1 Alarm StatusRead
Transistor Output 1 StatusRead
Transistor Output 2 Alarm LatchRead
Transistor Output 2 Connection Delay CounterRead
Transistor Output 2 Disconnection Delay CounterRead
Transistor Output 2 Alarm Activation YearRead
Transistor Output 2 Alarm Activation MonthRead
Transistor Output 2 Alarm Activation DayRead
Transistor Output 2 Alarm Activation HourRead
Transistor Output 2 Alarm Activation MinuteRead
Transistor Output 2 Alarm Activation SecondRead
Transistor Output 2 Alarm StatusRead
Transistor Output 2 StatusRead
Clock YearRead
Clock MonthRead
Clock DayRead
Clock HourRead
Clock MinuteRead
Clock SecondRead
Local Time ZoneRead
Summer TimeRead
Display LanguageRead
Access Key EnabledRead
Access Key Digit 1Read
Access Key Digit 2Read
Access Key Digit 3Read
Access Key Digit 4Read
Measurement Connection ModeRead
Primary VoltageVRead
Secondary VoltageVRead
Primary CurrentARead
Secondary CurrentRead
Primary Neutral CurrentARead
Secondary Neutral CurrentRead
Rated VoltageVRead
Displayed VariablesRead
Demand Integration TimeminRead
Demand Integration TypeRead
Demand SynchronisationRead
Demand Synchronisation InputRead
Nominal FrequencyRead
Number of QuadrantsRead
Cost per kWh Tariff 1 ConsumptionRead
Cost per kWh Tariff 2 ConsumptionRead
Cost per kWh Tariff 3 ConsumptionRead
Cost per kWh Tariff 1 GenerationRead
Cost per kWh Tariff 2 GenerationRead
Cost per kWh Tariff 3 GenerationRead
CurrencyRead
CO2 Ratio Tariff 1 ConsumptionRead
CO2 Ratio Tariff 2 ConsumptionRead
CO2 Ratio Tariff 3 ConsumptionRead
CO2 Ratio Tariff 1 GenerationRead
CO2 Ratio Tariff 2 GenerationRead
CO2 Ratio Tariff 3 GenerationRead
Relay Output 1 Maximum ValueRead
Relay Output 1 Minimum ValueRead
Relay Output 1 Connection DelaysRead
Relay Output 1 Disconnection DelaysRead
Relay Output 1 Pre-Alarm Value%Read
Relay Output 1 Contact TypeRead
Relay Output 1 InterlockingRead
Relay Output 1 Variable CodeRead
Relay Output 1 Module NumberRead
Relay Output 2 Maximum ValueRead
Relay Output 2 Minimum ValueRead
Relay Output 2 Connection DelaysRead
Relay Output 2 Disconnection DelaysRead
Relay Output 2 Pre-Alarm Value%Read
Relay Output 2 Contact TypeRead
Relay Output 2 InterlockingRead
Relay Output 2 Variable CodeRead
Relay Output 2 Module NumberRead
Transistor Output 1 Maximum ValueRead
Transistor Output 1 Minimum ValueRead
Transistor Output 1 Connection DelayRead
Transistor Output 1 Disconnection DelayRead
Transistor Output 1 Pre-Alarm Value%Read
Transistor Output 1 Contact TypeRead
Transistor Output 1 InterlockingRead
Transistor Output 1 Variable CodeRead
Transistor Output 1 Module NumberRead
Transistor Output 2 Maximum ValueRead
Transistor Output 2 Minimum ValueRead
Transistor Output 2 Connection DelayRead
Transistor Output 2 Disconnection DelayRead
Transistor Output 2 Pre-Alarm Value%Read
Transistor Output 2 Contact TypeRead
Transistor Output 2 InterlockingRead
Transistor Output 2 Variable CodeRead
Transistor Output 2 Module NumberRead
Digital Input 1 ModeRead
Digital Input 1 LogicRead
Digital Input 1 Impulse DecimalsRead
Digital Input 1 NameRead
Digital Input 1 Impulse UnitsRead
Digital Input 2 ModeRead
Digital Input 2 LogicRead
Digital Input 2 Impulse DecimalsRead
Digital Input 2 NameRead
Digital Input 2 Impulse UnitsRead
Communication ProtocolRead
Peripheral NumberRead
Baud Rate SettingRead
Parity SettingRead
Data Length SettingRead
Stop Bits SettingRead
Key SensitivityRead
Backlight Off TimeminRead
Decimal MarkRead
Date FormatRead
Default ScreenRead
Position of Input ChannelsRead
Relay Output 1 Manual ProgrammingRead
Relay Output 1 Manual ValueRead
Relay Output 2 Manual ProgrammingRead
Relay Output 2 Manual ValueRead
Transistor Output 1 Manual ProgrammingRead
Transistor Output 1 Manual ValueRead
Transistor Output 2 Manual ProgrammingRead
Transistor Output 2 Manual ValueRead
System ResetWrite
Delete EnergiesWrite
Delete Maximum and Minimum ValuesWrite
Delete Tariff 1 Partial Energy ConsumedWrite
Delete Tariff 2 Partial Energy ConsumedWrite
Delete Tariff 3 Partial Energy ConsumedWrite
Delete Tariff 1 Partial Energy GeneratedWrite
Delete Tariff 2 Partial Energy GeneratedWrite
Delete Tariff 3 Partial Energy GeneratedWrite
Initialise Maximum DemandWrite
Delete Maximum Demand Max and Min ValuesWrite
Delete Alarm LogsWrite
Delete Event LogsWrite
Delete Energy ClosesWrite
Full DeletionWrite
Default Setup 50 HzWrite
Default Setup Second EntryWrite
Display TestWrite
Expansion Module 1 TestWrite
Expansion Module 2 TestWrite
Expansion Module 3 TestWrite
Expansion Module 4 TestWrite

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show voltage, current, power and power factor of a switchboard on one ModbusCloud dashboard.
  • Track total active energy consumed and generated per phase for monthly energy reports.
  • Get an alert when voltage or current THD rises above a limit you choose.
  • Watch the alarm status of the relay and transistor outputs next to the measured values.
  • Reset the energy counters remotely at the start of a new billing period.

Installation

  1. Connect A(+), B(-) and the shield of the RS-485 port to the RS485 port of the ModbusCloud Gateway. Terminate both ends of the bus.

  2. On the analyzer, check in the communications setup that the protocol is Modbus and note the address, speed and parity.

  3. In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings, and import this template.

  4. Read Voltage Units, Current Units and Power and Energy Units once and set the scale of the matching registers.

  5. Check that Phase Voltage L1 and Frequency L1 show plausible values.

Things to watch for

The analyzer does not answer on the bus. What should I check?

Make sure the protocol in the communications setup is Modbus, not BACnet, and that address, speed and parity match ModbusCloud. The factory setting is 19200 baud, no parity, 8 data bits, 1 stop bit, address 1. Check A(+) and B(-) and the termination at both ends.

Why is the voltage ten times too high?

The values are raw numbers with a separate unit register that holds a power of ten. With Voltage Units at -1, a raw 2125 means 212.5 V. Read the unit registers once and set the scale of each value to match, for example 0.1.

Why does the energy look rounded?

Each energy has a whole part in kWh and a decimal part in Wh in the next register. Add both, or use the whole part for daily reports. When Power and Energy Units reads -3, the whole part is in Wh.

Can I change the setup or alarms from ModbusCloud?

The setup registers are read with function code 04 and the analyzer only accepts changes as a complete group, so they are read-only in this template. Change settings on the display or with the Circutor software. The reset commands can be written; a reset clears counters for good, so use them only when you mean to.

Some status registers return an error.

The alarm status of each output has to be read as a group of 14 registers. If a single register returns an exception, read the complete group of that output in one request.

Want to see how it works?