Circutor CVM-C10
Three-phase power analyzer for panels: power, energy per tariff, power quality and harmonics.
The Circutor CVM-C10 is a panel-mount power analyzer that measures voltage, current, power, energy and harmonics in three-phase and single-phase installations. This Modbus RTU template reads all electrical values, energy per tariff and power quality, and lets you set transformer ratios, alarms and outputs from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 538, read and write
- Brand
- Circutor
- Key readings
- Phase voltage · Phase current · Active power · Reactive power · Power factor · Frequency · Active energy · Voltage and current THD
- Available commands
- Transformer ratios · Alarm limits · Pulse outputs · Energy and demand reset · Communication settings
- Compatible models
- CVM-C10-ITF · CVM-C10-ITF-IN · CVM-C10-MC · CVM-C10-MC-IN · CVM-C10-mV · CVM-C10-FLEX
- Last updated
Registers (538)
473 read, 65 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| L1 Voltage | V | Read | |||
| L1 Current | A | Read | |||
| L1 Active Power | W | Read | |||
| L1 Inductive Reactive Power | var | Read | |||
| L1 Capacitive Reactive Power | var | Read | |||
| L1 Apparent Power | VA | Read | |||
| L1 Power Factor | Read | ||||
| L1 Cos Phi | Read | ||||
| L2 Voltage | V | Read | |||
| L2 Current | A | Read | |||
| L2 Active Power | W | Read | |||
| L2 Inductive Reactive Power | var | Read | |||
| L2 Capacitive Reactive Power | var | Read | |||
| L2 Apparent Power | VA | Read | |||
| L2 Power Factor | Read | ||||
| L2 Cos Phi | Read | ||||
| L3 Voltage | V | Read | |||
| L3 Current | A | Read | |||
| L3 Active Power | W | Read | |||
| L3 Inductive Reactive Power | var | Read | |||
| L3 Capacitive Reactive Power | var | Read | |||
| L3 Apparent Power | VA | Read | |||
| L3 Power Factor | Read | ||||
| L3 Cos Phi | Read | ||||
| Total Active Power | W | Read | |||
| Total Inductive Reactive Power | var | Read | |||
| Total Capacitive Reactive Power | var | Read | |||
| Total Apparent Power | VA | Read | |||
| Total Power Factor | Read | ||||
| Total Cos Phi | Read | ||||
| Frequency | Hz | Read | |||
| L1-L2 Voltage | V | Read | |||
| L2-L3 Voltage | V | Read | |||
| L3-L1 Voltage | V | Read | |||
| Neutral Current | A | Read | |||
| L1 Voltage THD | % | Read | |||
| L2 Voltage THD | % | Read | |||
| L3 Voltage THD | % | Read | |||
| L1 Current THD | % | Read | |||
| L2 Current THD | % | Read | |||
| L3 Current THD | % | Read | |||
| Demand Active Power | W | Read | |||
| Demand Apparent Power | VA | Read | |||
| Demand Average Current | A | Read | |||
| Demand L1 Current | A | Read | |||
| Demand L2 Current | A | Read | |||
| Demand L3 Current | A | Read | |||
| Demand Inductive Reactive Power | kvar | Read | |||
| Demand Capacitive Reactive Power | kvar | Read | |||
| Power Status | Read | ||||
| Wrong Phase Rotation | Read | ||||
| Digital Inputs Status | Read | ||||
| Digital Outputs Status | Read | ||||
| Imported Active Energy kWh Tariff 1 | kWh | Read | |||
| Imported Active Energy kWh Tariff 2 | kWh | Read | |||
| Imported Active Energy kWh Tariff 3 | kWh | Read | |||
| Imported Active Energy kWh Total | kWh | Read | |||
| Imported Active Energy Wh Tariff 1 | Wh | Read | |||
| Imported Active Energy Wh Tariff 2 | Wh | Read | |||
| Imported Active Energy Wh Tariff 3 | Wh | Read | |||
| Imported Active Energy Wh Total | Wh | Read | |||
| Imported Inductive Energy kvarh Tariff 1 | kvarh | Read | |||
| Imported Inductive Energy kvarh Tariff 2 | kvarh | Read | |||
| Imported Inductive Energy kvarh Tariff 3 | kvarh | Read | |||
| Imported Inductive Energy kvarh Total | kvarh | Read | |||
| Imported Inductive Energy varh Tariff 1 | varh | Read | |||
| Imported Inductive Energy varh Tariff 2 | varh | Read | |||
| Imported Inductive Energy varh Tariff 3 | varh | Read | |||
| Imported Inductive Energy varh Total | varh | Read | |||
| Imported Capacitive Energy kvarh Tariff 1 | kvarh | Read | |||
| Imported Capacitive Energy kvarh Tariff 2 | kvarh | Read | |||
| Imported Capacitive Energy kvarh Tariff 3 | kvarh | Read | |||
| Imported Capacitive Energy kvarh Total | kvarh | Read | |||
| Imported Capacitive Energy varh Tariff 1 | varh | Read | |||
| Imported Capacitive Energy varh Tariff 2 | varh | Read | |||
| Imported Capacitive Energy varh Tariff 3 | varh | Read | |||
| Imported Capacitive Energy varh Total | varh | Read | |||
| Imported Apparent Energy kVAh Tariff 1 | kVAh | Read | |||
| Imported Apparent Energy kVAh Tariff 2 | kVAh | Read | |||
| Imported Apparent Energy kVAh Tariff 3 | kVAh | Read | |||
| Imported Apparent Energy kVAh Total | kVAh | Read | |||
| Imported Apparent Energy VAh Tariff 1 | VAh | Read | |||
| Imported Apparent Energy VAh Tariff 2 | VAh | Read | |||
| Imported Apparent Energy VAh Tariff 3 | VAh | Read | |||
| Imported Apparent Energy VAh Total | VAh | Read | |||
| Imported CO2 Emissions Tariff 1 | kg | Read | |||
| Imported CO2 Emissions Tariff 2 | kg | Read | |||
| Imported CO2 Emissions Tariff 3 | kg | Read | |||
| Imported CO2 Emissions Total | kg | Read | |||
| Consumption Cost Tariff 1 | Read | ||||
| Consumption Cost Tariff 2 | Read | ||||
| Consumption Cost Tariff 3 | Read | ||||
| Consumption Cost Total | Read | ||||
| Exported Active Energy kWh Tariff 1 | kWh | Read | |||
| Exported Active Energy kWh Tariff 2 | kWh | Read | |||
| Exported Active Energy kWh Tariff 3 | kWh | Read | |||
| Exported Active Energy kWh Total | kWh | Read | |||
| Exported Active Energy Wh Tariff 1 | Wh | Read | |||
| Exported Active Energy Wh Tariff 2 | Wh | Read | |||
| Exported Active Energy Wh Tariff 3 | Wh | Read | |||
| Exported Active Energy Wh Total | Wh | Read | |||
| Exported Inductive Energy kvarh Tariff 1 | kvarh | Read | |||
| Exported Inductive Energy kvarh Tariff 2 | kvarh | Read | |||
| Exported Inductive Energy kvarh Tariff 3 | kvarh | Read | |||
| Exported Inductive Energy kvarh Total | kvarh | Read | |||
| Exported Inductive Energy varh Tariff 1 | varh | Read | |||
| Exported Inductive Energy varh Tariff 2 | varh | Read | |||
| Exported Inductive Energy varh Tariff 3 | varh | Read | |||
| Exported Inductive Energy varh Total | varh | Read | |||
| Exported Capacitive Energy kvarh Tariff 1 | kvarh | Read | |||
| Exported Capacitive Energy kvarh Tariff 2 | kvarh | Read | |||
| Exported Capacitive Energy kvarh Tariff 3 | kvarh | Read | |||
| Exported Capacitive Energy kvarh Total | kvarh | Read | |||
| Exported Capacitive Energy varh Tariff 1 | varh | Read | |||
| Exported Capacitive Energy varh Tariff 2 | varh | Read | |||
| Exported Capacitive Energy varh Tariff 3 | varh | Read | |||
| Exported Capacitive Energy varh Total | varh | Read | |||
| Exported Apparent Energy kVAh Tariff 1 | kVAh | Read | |||
| Exported Apparent Energy kVAh Tariff 2 | kVAh | Read | |||
| Exported Apparent Energy kVAh Tariff 3 | kVAh | Read | |||
| Exported Apparent Energy kVAh Total | kVAh | Read | |||
| Exported Apparent Energy VAh Tariff 1 | VAh | Read | |||
| Exported Apparent Energy VAh Tariff 2 | VAh | Read | |||
| Exported Apparent Energy VAh Tariff 3 | VAh | Read | |||
| Exported Apparent Energy VAh Total | VAh | Read | |||
| Exported CO2 Emissions Tariff 1 | kg | Read | |||
| Exported CO2 Emissions Tariff 2 | kg | Read | |||
| Exported CO2 Emissions Tariff 3 | kg | Read | |||
| Exported CO2 Emissions Total | kg | Read | |||
| Generation Cost Tariff 1 | Read | ||||
| Generation Cost Tariff 2 | Read | ||||
| Generation Cost Tariff 3 | Read | ||||
| Generation Cost Total | Read | ||||
| Tariff Time Tariff 1 | s | Read | |||
| Tariff Time Tariff 2 | s | Read | |||
| Tariff Time Tariff 3 | s | Read | |||
| Tariff Time Total | s | Read | |||
| L1 Voltage Maximum | V | Read | |||
| L1 Current Maximum | A | Read | |||
| L1 Active Power Maximum | W | Read | |||
| L1 Inductive Reactive Power Maximum | var | Read | |||
| L1 Capacitive Reactive Power Maximum | var | Read | |||
| L1 Apparent Power Maximum | VA | Read | |||
| L1 Power Factor Maximum | Read | ||||
| L1 Cos Phi Maximum | Read | ||||
| L2 Voltage Maximum | V | Read | |||
| L2 Current Maximum | A | Read | |||
| L2 Active Power Maximum | W | Read | |||
| L2 Inductive Reactive Power Maximum | var | Read | |||
| L2 Capacitive Reactive Power Maximum | var | Read | |||
| L2 Apparent Power Maximum | VA | Read | |||
| L2 Power Factor Maximum | Read | ||||
| L2 Cos Phi Maximum | Read | ||||
| L3 Voltage Maximum | V | Read | |||
| L3 Current Maximum | A | Read | |||
| L3 Active Power Maximum | W | Read | |||
| L3 Inductive Reactive Power Maximum | var | Read | |||
| L3 Capacitive Reactive Power Maximum | var | Read | |||
| L3 Apparent Power Maximum | VA | Read | |||
| L3 Power Factor Maximum | Read | ||||
| L3 Cos Phi Maximum | Read | ||||
| Total Active Power Maximum | W | Read | |||
| Total Inductive Reactive Power Maximum | var | Read | |||
| Total Capacitive Reactive Power Maximum | var | Read | |||
| Total Apparent Power Maximum | VA | Read | |||
| Total Power Factor Maximum | Read | ||||
| Total Cos Phi Maximum | Read | ||||
| Frequency Maximum | Hz | Read | |||
| L1-L2 Voltage Maximum | V | Read | |||
| L2-L3 Voltage Maximum | V | Read | |||
| L3-L1 Voltage Maximum | V | Read | |||
| Neutral Current Maximum | A | Read | |||
| L1 Voltage THD Maximum | % | Read | |||
| L2 Voltage THD Maximum | % | Read | |||
| L3 Voltage THD Maximum | % | Read | |||
| L1 Current THD Maximum | % | Read | |||
| L2 Current THD Maximum | % | Read | |||
| L3 Current THD Maximum | % | Read | |||
| Demand Active Power Peak | W | Read | |||
| Demand Apparent Power Peak | VA | Read | |||
| Demand Average Current Peak | A | Read | |||
| Demand L1 Current Peak | A | Read | |||
| Demand L2 Current Peak | A | Read | |||
| Demand L3 Current Peak | A | Read | |||
| Demand Inductive Reactive Power Peak | kvar | Read | |||
| Demand Capacitive Reactive Power Peak | kvar | Read | |||
| L1 Voltage Minimum | V | Read | |||
| L1 Current Minimum | A | Read | |||
| L1 Active Power Minimum | W | Read | |||
| L1 Inductive Reactive Power Minimum | var | Read | |||
| L1 Capacitive Reactive Power Minimum | var | Read | |||
| L1 Apparent Power Minimum | VA | Read | |||
| L1 Power Factor Minimum | Read | ||||
| L1 Cos Phi Minimum | Read | ||||
| L2 Voltage Minimum | V | Read | |||
| L2 Current Minimum | A | Read | |||
| L2 Active Power Minimum | W | Read | |||
| L2 Inductive Reactive Power Minimum | var | Read | |||
| L2 Capacitive Reactive Power Minimum | var | Read | |||
| L2 Apparent Power Minimum | VA | Read | |||
| L2 Power Factor Minimum | Read | ||||
| L2 Cos Phi Minimum | Read | ||||
| L3 Voltage Minimum | V | Read | |||
| L3 Current Minimum | A | Read | |||
| L3 Active Power Minimum | W | Read | |||
| L3 Inductive Reactive Power Minimum | var | Read | |||
| L3 Capacitive Reactive Power Minimum | var | Read | |||
| L3 Apparent Power Minimum | VA | Read | |||
| L3 Power Factor Minimum | Read | ||||
| L3 Cos Phi Minimum | Read | ||||
| Total Active Power Minimum | W | Read | |||
| Total Inductive Reactive Power Minimum | var | Read | |||
| Total Capacitive Reactive Power Minimum | var | Read | |||
| Total Apparent Power Minimum | VA | Read | |||
| Total Power Factor Minimum | Read | ||||
| Total Cos Phi Minimum | Read | ||||
| Frequency Minimum | Hz | Read | |||
| L1-L2 Voltage Minimum | V | Read | |||
| L2-L3 Voltage Minimum | V | Read | |||
| L3-L1 Voltage Minimum | V | Read | |||
| Neutral Current Minimum | A | Read | |||
| L1 Voltage THD Minimum | % | Read | |||
| L2 Voltage THD Minimum | % | Read | |||
| L3 Voltage THD Minimum | % | Read | |||
| L1 Current THD Minimum | % | Read | |||
| L2 Current THD Minimum | % | Read | |||
| L3 Current THD Minimum | % | Read | |||
| L1 Voltage Fundamental | V | Read | |||
| L1 Voltage Harmonic 2 | % | Read | |||
| L1 Voltage Harmonic 3 | % | Read | |||
| L1 Voltage Harmonic 4 | % | Read | |||
| L1 Voltage Harmonic 5 | % | Read | |||
| L1 Voltage Harmonic 6 | % | Read | |||
| L1 Voltage Harmonic 7 | % | Read | |||
| L1 Voltage Harmonic 8 | % | Read | |||
| L1 Voltage Harmonic 9 | % | Read | |||
| L1 Voltage Harmonic 10 | % | Read | |||
| L1 Voltage Harmonic 11 | % | Read | |||
| L1 Voltage Harmonic 12 | % | Read | |||
| L1 Voltage Harmonic 13 | % | Read | |||
| L1 Voltage Harmonic 14 | % | Read | |||
| L1 Voltage Harmonic 15 | % | Read | |||
| L1 Voltage Harmonic 16 | % | Read | |||
| L1 Voltage Harmonic 17 | % | Read | |||
| L1 Voltage Harmonic 18 | % | Read | |||
| L1 Voltage Harmonic 19 | % | Read | |||
| L1 Voltage Harmonic 20 | % | Read | |||
| L1 Voltage Harmonic 21 | % | Read | |||
| L1 Voltage Harmonic 22 | % | Read | |||
| L1 Voltage Harmonic 23 | % | Read | |||
| L1 Voltage Harmonic 24 | % | Read | |||
| L1 Voltage Harmonic 25 | % | Read | |||
| L1 Voltage Harmonic 26 | % | Read | |||
| L1 Voltage Harmonic 27 | % | Read | |||
| L1 Voltage Harmonic 28 | % | Read | |||
| L1 Voltage Harmonic 29 | % | Read | |||
| L1 Voltage Harmonic 30 | % | Read | |||
| L1 Voltage Harmonic 31 | % | Read | |||
| L2 Voltage Fundamental | V | Read | |||
| L2 Voltage Harmonic 2 | % | Read | |||
| L2 Voltage Harmonic 3 | % | Read | |||
| L2 Voltage Harmonic 4 | % | Read | |||
| L2 Voltage Harmonic 5 | % | Read | |||
| L2 Voltage Harmonic 6 | % | Read | |||
| L2 Voltage Harmonic 7 | % | Read | |||
| L2 Voltage Harmonic 8 | % | Read | |||
| L2 Voltage Harmonic 9 | % | Read | |||
| L2 Voltage Harmonic 10 | % | Read | |||
| L2 Voltage Harmonic 11 | % | Read | |||
| L2 Voltage Harmonic 12 | % | Read | |||
| L2 Voltage Harmonic 13 | % | Read | |||
| L2 Voltage Harmonic 14 | % | Read | |||
| L2 Voltage Harmonic 15 | % | Read | |||
| L2 Voltage Harmonic 16 | % | Read | |||
| L2 Voltage Harmonic 17 | % | Read | |||
| L2 Voltage Harmonic 18 | % | Read | |||
| L2 Voltage Harmonic 19 | % | Read | |||
| L2 Voltage Harmonic 20 | % | Read | |||
| L2 Voltage Harmonic 21 | % | Read | |||
| L2 Voltage Harmonic 22 | % | Read | |||
| L2 Voltage Harmonic 23 | % | Read | |||
| L2 Voltage Harmonic 24 | % | Read | |||
| L2 Voltage Harmonic 25 | % | Read | |||
| L2 Voltage Harmonic 26 | % | Read | |||
| L2 Voltage Harmonic 27 | % | Read | |||
| L2 Voltage Harmonic 28 | % | Read | |||
| L2 Voltage Harmonic 29 | % | Read | |||
| L2 Voltage Harmonic 30 | % | Read | |||
| L2 Voltage Harmonic 31 | % | Read | |||
| L3 Voltage Fundamental | V | Read | |||
| L3 Voltage Harmonic 2 | % | Read | |||
| L3 Voltage Harmonic 3 | % | Read | |||
| L3 Voltage Harmonic 4 | % | Read | |||
| L3 Voltage Harmonic 5 | % | Read | |||
| L3 Voltage Harmonic 6 | % | Read | |||
| L3 Voltage Harmonic 7 | % | Read | |||
| L3 Voltage Harmonic 8 | % | Read | |||
| L3 Voltage Harmonic 9 | % | Read | |||
| L3 Voltage Harmonic 10 | % | Read | |||
| L3 Voltage Harmonic 11 | % | Read | |||
| L3 Voltage Harmonic 12 | % | Read | |||
| L3 Voltage Harmonic 13 | % | Read | |||
| L3 Voltage Harmonic 14 | % | Read | |||
| L3 Voltage Harmonic 15 | % | Read | |||
| L3 Voltage Harmonic 16 | % | Read | |||
| L3 Voltage Harmonic 17 | % | Read | |||
| L3 Voltage Harmonic 18 | % | Read | |||
| L3 Voltage Harmonic 19 | % | Read | |||
| L3 Voltage Harmonic 20 | % | Read | |||
| L3 Voltage Harmonic 21 | % | Read | |||
| L3 Voltage Harmonic 22 | % | Read | |||
| L3 Voltage Harmonic 23 | % | Read | |||
| L3 Voltage Harmonic 24 | % | Read | |||
| L3 Voltage Harmonic 25 | % | Read | |||
| L3 Voltage Harmonic 26 | % | Read | |||
| L3 Voltage Harmonic 27 | % | Read | |||
| L3 Voltage Harmonic 28 | % | Read | |||
| L3 Voltage Harmonic 29 | % | Read | |||
| L3 Voltage Harmonic 30 | % | Read | |||
| L3 Voltage Harmonic 31 | % | Read | |||
| L1 Current Fundamental | A | Read | |||
| L1 Current Harmonic 2 | % | Read | |||
| L1 Current Harmonic 3 | % | Read | |||
| L1 Current Harmonic 4 | % | Read | |||
| L1 Current Harmonic 5 | % | Read | |||
| L1 Current Harmonic 6 | % | Read | |||
| L1 Current Harmonic 7 | % | Read | |||
| L1 Current Harmonic 8 | % | Read | |||
| L1 Current Harmonic 9 | % | Read | |||
| L1 Current Harmonic 10 | % | Read | |||
| L1 Current Harmonic 11 | % | Read | |||
| L1 Current Harmonic 12 | % | Read | |||
| L1 Current Harmonic 13 | % | Read | |||
| L1 Current Harmonic 14 | % | Read | |||
| L1 Current Harmonic 15 | % | Read | |||
| L1 Current Harmonic 16 | % | Read | |||
| L1 Current Harmonic 17 | % | Read | |||
| L1 Current Harmonic 18 | % | Read | |||
| L1 Current Harmonic 19 | % | Read | |||
| L1 Current Harmonic 20 | % | Read | |||
| L1 Current Harmonic 21 | % | Read | |||
| L1 Current Harmonic 22 | % | Read | |||
| L1 Current Harmonic 23 | % | Read | |||
| L1 Current Harmonic 24 | % | Read | |||
| L1 Current Harmonic 25 | % | Read | |||
| L1 Current Harmonic 26 | % | Read | |||
| L1 Current Harmonic 27 | % | Read | |||
| L1 Current Harmonic 28 | % | Read | |||
| L1 Current Harmonic 29 | % | Read | |||
| L1 Current Harmonic 30 | % | Read | |||
| L1 Current Harmonic 31 | % | Read | |||
| L2 Current Fundamental | A | Read | |||
| L2 Current Harmonic 2 | % | Read | |||
| L2 Current Harmonic 3 | % | Read | |||
| L2 Current Harmonic 4 | % | Read | |||
| L2 Current Harmonic 5 | % | Read | |||
| L2 Current Harmonic 6 | % | Read | |||
| L2 Current Harmonic 7 | % | Read | |||
| L2 Current Harmonic 8 | % | Read | |||
| L2 Current Harmonic 9 | % | Read | |||
| L2 Current Harmonic 10 | % | Read | |||
| L2 Current Harmonic 11 | % | Read | |||
| L2 Current Harmonic 12 | % | Read | |||
| L2 Current Harmonic 13 | % | Read | |||
| L2 Current Harmonic 14 | % | Read | |||
| L2 Current Harmonic 15 | % | Read | |||
| L2 Current Harmonic 16 | % | Read | |||
| L2 Current Harmonic 17 | % | Read | |||
| L2 Current Harmonic 18 | % | Read | |||
| L2 Current Harmonic 19 | % | Read | |||
| L2 Current Harmonic 20 | % | Read | |||
| L2 Current Harmonic 21 | % | Read | |||
| L2 Current Harmonic 22 | % | Read | |||
| L2 Current Harmonic 23 | % | Read | |||
| L2 Current Harmonic 24 | % | Read | |||
| L2 Current Harmonic 25 | % | Read | |||
| L2 Current Harmonic 26 | % | Read | |||
| L2 Current Harmonic 27 | % | Read | |||
| L2 Current Harmonic 28 | % | Read | |||
| L2 Current Harmonic 29 | % | Read | |||
| L2 Current Harmonic 30 | % | Read | |||
| L2 Current Harmonic 31 | % | Read | |||
| L3 Current Fundamental | A | Read | |||
| L3 Current Harmonic 2 | % | Read | |||
| L3 Current Harmonic 3 | % | Read | |||
| L3 Current Harmonic 4 | % | Read | |||
| L3 Current Harmonic 5 | % | Read | |||
| L3 Current Harmonic 6 | % | Read | |||
| L3 Current Harmonic 7 | % | Read | |||
| L3 Current Harmonic 8 | % | Read | |||
| L3 Current Harmonic 9 | % | Read | |||
| L3 Current Harmonic 10 | % | Read | |||
| L3 Current Harmonic 11 | % | Read | |||
| L3 Current Harmonic 12 | % | Read | |||
| L3 Current Harmonic 13 | % | Read | |||
| L3 Current Harmonic 14 | % | Read | |||
| L3 Current Harmonic 15 | % | Read | |||
| L3 Current Harmonic 16 | % | Read | |||
| L3 Current Harmonic 17 | % | Read | |||
| L3 Current Harmonic 18 | % | Read | |||
| L3 Current Harmonic 19 | % | Read | |||
| L3 Current Harmonic 20 | % | Read | |||
| L3 Current Harmonic 21 | % | Read | |||
| L3 Current Harmonic 22 | % | Read | |||
| L3 Current Harmonic 23 | % | Read | |||
| L3 Current Harmonic 24 | % | Read | |||
| L3 Current Harmonic 25 | % | Read | |||
| L3 Current Harmonic 26 | % | Read | |||
| L3 Current Harmonic 27 | % | Read | |||
| L3 Current Harmonic 28 | % | Read | |||
| L3 Current Harmonic 29 | % | Read | |||
| L3 Current Harmonic 30 | % | Read | |||
| L3 Current Harmonic 31 | % | Read | |||
| Reset Energies | Write | ||||
| Reset Maximum and Minimum Values | Write | ||||
| Restart Maximum Demand | Write | ||||
| Reset Tariff Hour Counters | Write | ||||
| Reset Peak Maximum Demand | Write | ||||
| Reset Energies Demand and Max Min | Write | ||||
| Voltage Primary Setting | Write | ||||
| Voltage Secondary Setting | Write | ||||
| Current Primary Setting | Write | ||||
| Current Secondary Setting | Write | ||||
| Neutral Current Primary Setting | Write | ||||
| Neutral Current Secondary Setting | Write | ||||
| CO2 Ratio Consumption Tariff 1 Setting | Write | ||||
| CO2 Ratio Consumption Tariff 2 Setting | Write | ||||
| CO2 Ratio Consumption Tariff 3 Setting | Write | ||||
| CO2 Ratio Generation Tariff 1 Setting | Write | ||||
| CO2 Ratio Generation Tariff 2 Setting | Write | ||||
| CO2 Ratio Generation Tariff 3 Setting | Write | ||||
| Price Consumption Tariff 1 Setting | Write | ||||
| Price Consumption Tariff 2 Setting | Write | ||||
| Price Consumption Tariff 3 Setting | Write | ||||
| Price Generation Tariff 1 Setting | Write | ||||
| Price Generation Tariff 2 Setting | Write | ||||
| Price Generation Tariff 3 Setting | Write | ||||
| Protocol Setting | Write | ||||
| Peripheral Number Setting | Write | ||||
| Baud Rate Setting | Write | ||||
| Parity Setting | Write | ||||
| Data Bits Setting | Write | ||||
| Stop Bits Setting | Write | ||||
| Demand Integration Period Setting | min | Write | |||
| Relay 1 Alarm Maximum Setting | Write | ||||
| Relay 1 Alarm Minimum Setting | Write | ||||
| Relay 1 Alarm Variable Setting | Write | ||||
| Relay 1 Connection Delay Setting | s | Write | |||
| Relay 1 Hysteresis Setting | % | Write | |||
| Relay 1 Latch Setting | Write | ||||
| Relay 1 Disconnection Delay Setting | s | Write | |||
| Relay 1 Contact State Setting | Write | ||||
| Relay 2 Alarm Maximum Setting | Write | ||||
| Relay 2 Alarm Minimum Setting | Write | ||||
| Relay 2 Alarm Variable Setting | Write | ||||
| Relay 2 Connection Delay Setting | s | Write | |||
| Relay 2 Hysteresis Setting | % | Write | |||
| Relay 2 Latch Setting | Write | ||||
| Relay 2 Disconnection Delay Setting | s | Write | |||
| Relay 2 Contact State Setting | Write | ||||
| Output T1 Energy per Pulse Setting | Write | ||||
| Output T1 Variable Setting | Write | ||||
| Output T1 Pulse Width Setting | ms | Write | |||
| Output T2 Energy per Pulse Setting | Write | ||||
| Output T2 Variable Setting | Write | ||||
| Output T2 Pulse Width Setting | ms | Write | |||
| Installation Type Setting | Write | ||||
| Backlight Setting | s | Write | |||
| Operating Profile Setting | Write | ||||
| Harmonics Display Setting | Write | ||||
| Number of Quadrants Setting | Write | ||||
| Input 1 Mode Setting | Write | ||||
| Input 2 Mode Setting | Write | ||||
| Password Setting | Write | ||||
| Menu Lock Setting | Write | ||||
| Measurement Convention Setting | Write | ||||
| BACnet Device ID Setting | Write | ||||
| BACnet MAC Setting | Write | ||||
| Voltage Primary | Read | ||||
| Voltage Secondary | Read | ||||
| Current Primary | Read | ||||
| Current Secondary | Read | ||||
| Neutral Current Primary | Read | ||||
| Neutral Current Secondary | Read | ||||
| CO2 Ratio Consumption Tariff 1 | Read | ||||
| CO2 Ratio Consumption Tariff 2 | Read | ||||
| CO2 Ratio Consumption Tariff 3 | Read | ||||
| CO2 Ratio Generation Tariff 1 | Read | ||||
| CO2 Ratio Generation Tariff 2 | Read | ||||
| CO2 Ratio Generation Tariff 3 | Read | ||||
| Price Consumption Tariff 1 | Read | ||||
| Price Consumption Tariff 2 | Read | ||||
| Price Consumption Tariff 3 | Read | ||||
| Price Generation Tariff 1 | Read | ||||
| Price Generation Tariff 2 | Read | ||||
| Price Generation Tariff 3 | Read | ||||
| Protocol | Read | ||||
| Peripheral Number | Read | ||||
| Baud Rate | Read | ||||
| Parity | Read | ||||
| Data Bits | Read | ||||
| Stop Bits | Read | ||||
| Demand Integration Period | min | Read | |||
| Relay 1 Alarm Maximum | Read | ||||
| Relay 1 Alarm Minimum | Read | ||||
| Relay 1 Alarm Variable | Read | ||||
| Relay 1 Connection Delay | s | Read | |||
| Relay 1 Hysteresis | % | Read | |||
| Relay 1 Latch | Read | ||||
| Relay 1 Disconnection Delay | s | Read | |||
| Relay 1 Contact State | Read | ||||
| Relay 2 Alarm Maximum | Read | ||||
| Relay 2 Alarm Minimum | Read | ||||
| Relay 2 Alarm Variable | Read | ||||
| Relay 2 Connection Delay | s | Read | |||
| Relay 2 Hysteresis | % | Read | |||
| Relay 2 Latch | Read | ||||
| Relay 2 Disconnection Delay | s | Read | |||
| Relay 2 Contact State | Read | ||||
| Output T1 Energy per Pulse | Read | ||||
| Output T1 Variable | Read | ||||
| Output T1 Pulse Width | ms | Read | |||
| Output T2 Energy per Pulse | Read | ||||
| Output T2 Variable | Read | ||||
| Output T2 Pulse Width | ms | Read | |||
| Installation Type | Read | ||||
| Backlight | s | Read | |||
| Operating Profile | Read | ||||
| Harmonics Display | Read | ||||
| Number of Quadrants | Read | ||||
| Input 1 Mode | Read | ||||
| Input 2 Mode | Read | ||||
| Password | Read | ||||
| Menu Lock | Read | ||||
| Measurement Convention | Read | ||||
| BACnet Device ID | Read | ||||
| BACnet MAC | Read | ||||
| Serial Number | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show voltage, current and power per phase on a dashboard for each distribution board.
- Track imported and exported energy per tariff in the history and compare months.
- Get an alarm by email when current THD or the power factor crosses a limit you choose.
- Watch maximum demand to see when a connection gets close to its contracted capacity.
- Adjust the current transformer ratio remotely after a transformer is replaced.
Installation
Connect RS485 A(+), B(-) and GND of the CVM-C10 to the RS485 port of the ModbusCloud Gateway, with a 120 ohm termination at both ends of the bus.
In the communication menu of the analyzer, set protocol Modbus, the peripheral number, 9600 or 19200 baud, parity and stop bits. Restart the analyzer.
In ModbusCloud, add a Modbus device with the same address and serial settings and import this template.
Check that phase voltages and frequency come in with plausible values, then set up dashboards and alarms.
Things to watch for
The analyzer does not answer on the bus. What should I check?
Check that the protocol is set to Modbus and not BACnet, and that address, speed, parity and stop bits match on both sides. The analyzer uses new communication settings only after a restart. Then swap A and B, and check the 120 ohm termination at both ends of the bus.
Why is the active energy split over two registers?
The analyzer keeps energy as a whole kWh counter plus a Wh counter for the part below 1 kWh. For the exact value add both: kWh plus Wh divided by 1000. For daily or monthly totals the kWh register is usually enough.
The currents are a factor off. What is wrong?
The current transformer ratio in the analyzer does not match the installed transformers. Check the primary and secondary current settings. The analyzer applies the ratio itself, so the values in ModbusCloud follow it directly.
Can I change the settings by writing registers?
Yes, the setup registers can be written from ModbusCloud. Transformer ratios and the password are meant to be written together, and a new setting only takes effect after a restart. Write a wrong ratio and every measured value follows it, so check each value before you write it.