Circutor CVM-E3-MINI
Compact three-phase power analyser with energy per tariff, per phase and harmonics up to the 31st.
The Circutor CVM-E3-MINI is a compact power analyser that measures three-phase voltage, current, power and energy in switchboards and distribution panels. This Modbus RTU template reads power, energy per tariff and per phase, THD and harmonics, and lets you reset counters and change transformer ratios and alarm settings from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 531, read and write
- Brand
- Circutor
- Key readings
- Phase voltages · Phase currents · Active power · Power factor · Frequency · Voltage and current THD · Active energy · Harmonics
- Available commands
- Transformer ratios · Measurement system · Alarm limits · Energy counter reset · Communication settings
- Compatible models
- CVM-E3-MINI-ITF · CVM-E3-MINI-MC · CVM-E3-MINI-FLEX · CVM-E3-MINI-ITF-WiEth · CVM-E3-MINI-MC-WiEth · CVM-E3-MINI-FLEX-WiEth
- Last updated
Registers (531)
519 read, 52 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| L1 Phase Voltage | V | Read | |||
| L1 Phase Voltage Max | V | Read | |||
| L1 Phase Voltage Min | V | Read | |||
| L1 Current | A | Read | |||
| L1 Current Max | A | Read | |||
| L1 Current Min | A | Read | |||
| L1 Active Power | W | Read | |||
| L1 Active Power Max | W | Read | |||
| L1 Active Power Min | W | Read | |||
| L1 Inductive Power | var | Read | |||
| L1 Inductive Power Max | var | Read | |||
| L1 Inductive Power Min | var | Read | |||
| L1 Capacitive Power | var | Read | |||
| L1 Capacitive Power Max | var | Read | |||
| L1 Capacitive Power Min | var | Read | |||
| L1 Apparent Power | VA | Read | |||
| L1 Apparent Power Max | VA | Read | |||
| L1 Apparent Power Min | VA | Read | |||
| L1 Power Factor | Read | ||||
| L1 Power Factor Max | Read | ||||
| L1 Power Factor Min | Read | ||||
| Cos Phi L1 | Read | ||||
| Cos Phi L1 Max | Read | ||||
| Cos Phi L1 Min | Read | ||||
| L2 Phase Voltage | V | Read | |||
| L2 Phase Voltage Max | V | Read | |||
| L2 Phase Voltage Min | V | Read | |||
| L2 Current | A | Read | |||
| L2 Current Max | A | Read | |||
| L2 Current Min | A | Read | |||
| L2 Active Power | W | Read | |||
| L2 Active Power Max | W | Read | |||
| L2 Active Power Min | W | Read | |||
| L2 Inductive Power | var | Read | |||
| L2 Inductive Power Max | var | Read | |||
| L2 Inductive Power Min | var | Read | |||
| L2 Capacitive Power | var | Read | |||
| L2 Capacitive Power Max | var | Read | |||
| L2 Capacitive Power Min | var | Read | |||
| L2 Apparent Power | VA | Read | |||
| L2 Apparent Power Max | VA | Read | |||
| L2 Apparent Power Min | VA | Read | |||
| L2 Power Factor | Read | ||||
| L2 Power Factor Max | Read | ||||
| L2 Power Factor Min | Read | ||||
| Cos Phi L2 | Read | ||||
| Cos Phi L2 Max | Read | ||||
| Cos Phi L2 Min | Read | ||||
| L3 Phase Voltage | V | Read | |||
| L3 Phase Voltage Max | V | Read | |||
| L3 Phase Voltage Min | V | Read | |||
| L3 Current | A | Read | |||
| L3 Current Max | A | Read | |||
| L3 Current Min | A | Read | |||
| L3 Active Power | W | Read | |||
| L3 Active Power Max | W | Read | |||
| L3 Active Power Min | W | Read | |||
| L3 Inductive Power | var | Read | |||
| L3 Inductive Power Max | var | Read | |||
| L3 Inductive Power Min | var | Read | |||
| L3 Capacitive Power | var | Read | |||
| L3 Capacitive Power Max | var | Read | |||
| L3 Capacitive Power Min | var | Read | |||
| L3 Apparent Power | VA | Read | |||
| L3 Apparent Power Max | VA | Read | |||
| L3 Apparent Power Min | VA | Read | |||
| L3 Power Factor | Read | ||||
| L3 Power Factor Max | Read | ||||
| L3 Power Factor Min | Read | ||||
| Cos Phi L3 | Read | ||||
| Cos Phi L3 Max | Read | ||||
| Cos Phi L3 Min | Read | ||||
| Three-phase Active Power | W | Read | |||
| Three-phase Active Power Max | W | Read | |||
| Three-phase Active Power Min | W | Read | |||
| Three-phase Inductive Power | var | Read | |||
| Three-phase Inductive Power Max | var | Read | |||
| Three-phase Inductive Power Min | var | Read | |||
| Three-phase Capacitive Power | var | Read | |||
| Three-phase Capacitive Power Max | var | Read | |||
| Three-phase Capacitive Power Min | var | Read | |||
| Three-phase Apparent Power | VA | Read | |||
| Three-phase Apparent Power Max | VA | Read | |||
| Three-phase Apparent Power Min | VA | Read | |||
| Three-phase Power Factor | Read | ||||
| Three-phase Power Factor Max | Read | ||||
| Three-phase Power Factor Min | Read | ||||
| Three-phase Cos Phi | Read | ||||
| Three-phase Cos Phi Max | Read | ||||
| Three-phase Cos Phi Min | Read | ||||
| L1 Frequency | Hz | Read | |||
| L1 Frequency Max | Hz | Read | |||
| L1 Frequency Min | Hz | Read | |||
| L1-L2 Voltage | V | Read | |||
| L1-L2 Voltage Max | V | Read | |||
| L1-L2 Voltage Min | V | Read | |||
| L2-L3 Voltage | V | Read | |||
| L2-L3 Voltage Max | V | Read | |||
| L2-L3 Voltage Min | V | Read | |||
| L3-L1 Voltage | V | Read | |||
| L3-L1 Voltage Max | V | Read | |||
| L3-L1 Voltage Min | V | Read | |||
| L1 Voltage THD | % | Read | |||
| L1 Voltage THD Max | % | Read | |||
| L1 Voltage THD Min | % | Read | |||
| L2 Voltage THD | % | Read | |||
| L2 Voltage THD Max | % | Read | |||
| L2 Voltage THD Min | % | Read | |||
| L3 Voltage THD | % | Read | |||
| L3 Voltage THD Max | % | Read | |||
| L3 Voltage THD Min | % | Read | |||
| L1 Current THD | % | Read | |||
| L1 Current THD Max | % | Read | |||
| L1 Current THD Min | % | Read | |||
| L2 Current THD | % | Read | |||
| L2 Current THD Max | % | Read | |||
| L2 Current THD Min | % | Read | |||
| L3 Current THD | % | Read | |||
| L3 Current THD Max | % | Read | |||
| L3 Current THD Min | % | Read | |||
| Maximum Demand KW III | W | Read | |||
| Maximum Demand KW III Max | W | Read | |||
| Maximum Demand KVA III | VA | Read | |||
| Maximum Demand KVA III Max | VA | Read | |||
| Maximum Demand KvarL III | var | Read | |||
| Maximum Demand KvarL III Max | var | Read | |||
| Maximum Demand KvarC III | var | Read | |||
| Maximum Demand KvarC III Max | var | Read | |||
| Maximum Demand I L1 | A | Read | |||
| Maximum Demand I L1 Max | A | Read | |||
| Maximum Demand I L2 | A | Read | |||
| Maximum Demand I L2 Max | A | Read | |||
| Maximum Demand I L3 | A | Read | |||
| Maximum Demand I L3 Max | A | Read | |||
| L1 Reactive Power | var | Read | |||
| L1 Reactive Power Max | var | Read | |||
| L1 Reactive Power Min | var | Read | |||
| L2 Reactive Power | var | Read | |||
| L2 Reactive Power Max | var | Read | |||
| L2 Reactive Power Min | var | Read | |||
| L3 Reactive Power | var | Read | |||
| L3 Reactive Power Max | var | Read | |||
| L3 Reactive Power Min | var | Read | |||
| Three-phase Current Average | A | Read | |||
| Three-phase Current Average Max | A | Read | |||
| Three-phase Current Average Min | A | Read | |||
| Power Status | Read | ||||
| Wrong Rotation Detected | Read | ||||
| Digital Inputs Status | Read | ||||
| Digital Outputs Status | Read | ||||
| Protocol | Read and write | ||||
| Peripheral Number | Read and write | ||||
| Baud Rate | Read and write | ||||
| Parity | Read and write | ||||
| Consumed Active Energy kWh T1 | kWh | Read | |||
| Consumed Active Energy kWh T2 | kWh | Read | |||
| Consumed Active Energy kWh Total | kWh | Read | |||
| Consumed Active Energy Wh T1 | Wh | Read | |||
| Consumed Active Energy Wh T2 | Wh | Read | |||
| Consumed Active Energy Wh Total | Wh | Read | |||
| Consumed Inductive Energy kvarh T1 | kvarh | Read | |||
| Consumed Inductive Energy kvarh T2 | kvarh | Read | |||
| Consumed Inductive Energy kvarh Total | kvarh | Read | |||
| Consumed Inductive Energy varh T1 | varh | Read | |||
| Consumed Inductive Energy varh T2 | varh | Read | |||
| Consumed Inductive Energy varh Total | varh | Read | |||
| Consumed Capacitive Energy kvarh T1 | kvarh | Read | |||
| Consumed Capacitive Energy kvarh T2 | kvarh | Read | |||
| Consumed Capacitive Energy kvarh Total | kvarh | Read | |||
| Consumed Capacitive Energy varh T1 | varh | Read | |||
| Consumed Capacitive Energy varh T2 | varh | Read | |||
| Consumed Capacitive Energy varh Total | varh | Read | |||
| Consumed Apparent Energy kVAh T1 | kVAh | Read | |||
| Consumed Apparent Energy kVAh T2 | kVAh | Read | |||
| Consumed Apparent Energy kVAh Total | kVAh | Read | |||
| Consumed Apparent Energy VAh T1 | VAh | Read | |||
| Consumed Apparent Energy VAh T2 | VAh | Read | |||
| Consumed Apparent Energy VAh Total | VAh | Read | |||
| Consumed CO2 Emissions T1 | kg | Read | |||
| Consumed CO2 Emissions T2 | kg | Read | |||
| Consumed CO2 Emissions Total | kg | Read | |||
| Consumption Cost T1 | Read | ||||
| Consumption Cost T2 | Read | ||||
| Consumption Cost Total | Read | ||||
| Generated Active Energy kWh T1 | kWh | Read | |||
| Generated Active Energy kWh T2 | kWh | Read | |||
| Generated Active Energy kWh Total | kWh | Read | |||
| Generated Active Energy Wh T1 | Wh | Read | |||
| Generated Active Energy Wh T2 | Wh | Read | |||
| Generated Active Energy Wh Total | Wh | Read | |||
| Generated Inductive Energy kvarh T1 | kvarh | Read | |||
| Generated Inductive Energy kvarh T2 | kvarh | Read | |||
| Generated Inductive Energy kvarh Total | kvarh | Read | |||
| Generated Inductive Energy varh T1 | varh | Read | |||
| Generated Inductive Energy varh T2 | varh | Read | |||
| Generated Inductive Energy varh Total | varh | Read | |||
| Generated Capacitive Energy kvarh T1 | kvarh | Read | |||
| Generated Capacitive Energy kvarh T2 | kvarh | Read | |||
| Generated Capacitive Energy kvarh Total | kvarh | Read | |||
| Generated Capacitive Energy varh T1 | varh | Read | |||
| Generated Capacitive Energy varh T2 | varh | Read | |||
| Generated Capacitive Energy varh Total | varh | Read | |||
| Generated Apparent Energy kVAh T1 | kVAh | Read | |||
| Generated Apparent Energy kVAh T2 | kVAh | Read | |||
| Generated Apparent Energy kVAh Total | kVAh | Read | |||
| Generated Apparent Energy VAh T1 | VAh | Read | |||
| Generated Apparent Energy VAh T2 | VAh | Read | |||
| Generated Apparent Energy VAh Total | VAh | Read | |||
| Generated CO2 Emissions T1 | kg | Read | |||
| Generated CO2 Emissions T2 | kg | Read | |||
| Generated CO2 Emissions Total | kg | Read | |||
| Generation Cost T1 | Read | ||||
| Generation Cost T2 | Read | ||||
| Generation Cost Total | Read | ||||
| Tariff Time T1 | s | Read | |||
| Tariff Time T2 | s | Read | |||
| Tariff Time Total | s | Read | |||
| Active Energy Instantaneous | Wh | Read | |||
| Inductive Energy Instantaneous | varh | Read | |||
| Capacitive Energy Instantaneous | varh | Read | |||
| Apparent Energy Instantaneous | VAh | Read | |||
| Generated Active Energy Instantaneous | Wh | Read | |||
| Generated Inductive Energy Instantaneous | varh | Read | |||
| Generated Capacitive Energy Instantaneous | varh | Read | |||
| Generated Apparent Energy Instantaneous | VAh | Read | |||
| L1 Consumed Active Energy kWh T1 | kWh | Read | |||
| L2 Consumed Active Energy kWh T1 | kWh | Read | |||
| L3 Consumed Active Energy kWh T1 | kWh | Read | |||
| L1 Consumed Active Energy Wh T1 | Wh | Read | |||
| L2 Consumed Active Energy Wh T1 | Wh | Read | |||
| L3 Consumed Active Energy Wh T1 | Wh | Read | |||
| L1 Consumed Inductive Energy kvarh T1 | kvarh | Read | |||
| L2 Consumed Inductive Energy kvarh T1 | kvarh | Read | |||
| L3 Consumed Inductive Energy kvarh T1 | kvarh | Read | |||
| L1 Consumed Inductive Energy varh T1 | varh | Read | |||
| L2 Consumed Inductive Energy varh T1 | varh | Read | |||
| L3 Consumed Inductive Energy varh T1 | varh | Read | |||
| L1 Generated Active Energy kWh T1 | kWh | Read | |||
| L2 Generated Active Energy kWh T1 | kWh | Read | |||
| L3 Generated Active Energy kWh T1 | kWh | Read | |||
| L1 Generated Active Energy Wh T1 | Wh | Read | |||
| L2 Generated Active Energy Wh T1 | Wh | Read | |||
| L3 Generated Active Energy Wh T1 | Wh | Read | |||
| L1 Generated Inductive Energy kvarh T1 | kvarh | Read | |||
| L2 Generated Inductive Energy kvarh T1 | kvarh | Read | |||
| L3 Generated Inductive Energy kvarh T1 | kvarh | Read | |||
| L1 Generated Inductive Energy varh T1 | varh | Read | |||
| L2 Generated Inductive Energy varh T1 | varh | Read | |||
| L3 Generated Inductive Energy varh T1 | varh | Read | |||
| L1 Consumed Active Energy kWh T2 | kWh | Read | |||
| L2 Consumed Active Energy kWh T2 | kWh | Read | |||
| L3 Consumed Active Energy kWh T2 | kWh | Read | |||
| L1 Consumed Active Energy Wh T2 | Wh | Read | |||
| L2 Consumed Active Energy Wh T2 | Wh | Read | |||
| L3 Consumed Active Energy Wh T2 | Wh | Read | |||
| L1 Consumed Inductive Energy kvarh T2 | kvarh | Read | |||
| L2 Consumed Inductive Energy kvarh T2 | kvarh | Read | |||
| L3 Consumed Inductive Energy kvarh T2 | kvarh | Read | |||
| L1 Consumed Inductive Energy varh T2 | varh | Read | |||
| L2 Consumed Inductive Energy varh T2 | varh | Read | |||
| L3 Consumed Inductive Energy varh T2 | varh | Read | |||
| L1 Generated Active Energy kWh T2 | kWh | Read | |||
| L2 Generated Active Energy kWh T2 | kWh | Read | |||
| L3 Generated Active Energy kWh T2 | kWh | Read | |||
| L1 Generated Active Energy Wh T2 | Wh | Read | |||
| L2 Generated Active Energy Wh T2 | Wh | Read | |||
| L3 Generated Active Energy Wh T2 | Wh | Read | |||
| L1 Generated Inductive Energy kvarh T2 | kvarh | Read | |||
| L2 Generated Inductive Energy kvarh T2 | kvarh | Read | |||
| L3 Generated Inductive Energy kvarh T2 | kvarh | Read | |||
| L1 Generated Inductive Energy varh T2 | varh | Read | |||
| L2 Generated Inductive Energy varh T2 | varh | Read | |||
| L3 Generated Inductive Energy varh T2 | varh | Read | |||
| L1 Consumed Active Energy kWh Total | kWh | Read | |||
| L2 Consumed Active Energy kWh Total | kWh | Read | |||
| L3 Consumed Active Energy kWh Total | kWh | Read | |||
| L1 Consumed Active Energy Wh Total | Wh | Read | |||
| L2 Consumed Active Energy Wh Total | Wh | Read | |||
| L3 Consumed Active Energy Wh Total | Wh | Read | |||
| L1 Consumed Inductive Energy kvarh Total | kvarh | Read | |||
| L2 Consumed Inductive Energy kvarh Total | kvarh | Read | |||
| L3 Consumed Inductive Energy kvarh Total | kvarh | Read | |||
| L1 Consumed Inductive Energy varh Total | varh | Read | |||
| L2 Consumed Inductive Energy varh Total | varh | Read | |||
| L3 Consumed Inductive Energy varh Total | varh | Read | |||
| L1 Generated Active Energy kWh Total | kWh | Read | |||
| L2 Generated Active Energy kWh Total | kWh | Read | |||
| L3 Generated Active Energy kWh Total | kWh | Read | |||
| L1 Generated Active Energy Wh Total | Wh | Read | |||
| L2 Generated Active Energy Wh Total | Wh | Read | |||
| L3 Generated Active Energy Wh Total | Wh | Read | |||
| L1 Generated Inductive Energy kvarh Total | kvarh | Read | |||
| L2 Generated Inductive Energy kvarh Total | kvarh | Read | |||
| L3 Generated Inductive Energy kvarh Total | kvarh | Read | |||
| L1 Generated Inductive Energy varh Total | varh | Read | |||
| L2 Generated Inductive Energy varh Total | varh | Read | |||
| L3 Generated Inductive Energy varh Total | varh | Read | |||
| L1 Voltage Fundamental | V | Read | |||
| L1 Voltage Harmonic 2 | % | Read | |||
| L1 Voltage Harmonic 3 | % | Read | |||
| L1 Voltage Harmonic 4 | % | Read | |||
| L1 Voltage Harmonic 5 | % | Read | |||
| L1 Voltage Harmonic 6 | % | Read | |||
| L1 Voltage Harmonic 7 | % | Read | |||
| L1 Voltage Harmonic 8 | % | Read | |||
| L1 Voltage Harmonic 9 | % | Read | |||
| L1 Voltage Harmonic 10 | % | Read | |||
| L1 Voltage Harmonic 11 | % | Read | |||
| L1 Voltage Harmonic 12 | % | Read | |||
| L1 Voltage Harmonic 13 | % | Read | |||
| L1 Voltage Harmonic 14 | % | Read | |||
| L1 Voltage Harmonic 15 | % | Read | |||
| L1 Voltage Harmonic 16 | % | Read | |||
| L1 Voltage Harmonic 17 | % | Read | |||
| L1 Voltage Harmonic 18 | % | Read | |||
| L1 Voltage Harmonic 19 | % | Read | |||
| L1 Voltage Harmonic 20 | % | Read | |||
| L1 Voltage Harmonic 21 | % | Read | |||
| L1 Voltage Harmonic 22 | % | Read | |||
| L1 Voltage Harmonic 23 | % | Read | |||
| L1 Voltage Harmonic 24 | % | Read | |||
| L1 Voltage Harmonic 25 | % | Read | |||
| L1 Voltage Harmonic 26 | % | Read | |||
| L1 Voltage Harmonic 27 | % | Read | |||
| L1 Voltage Harmonic 28 | % | Read | |||
| L1 Voltage Harmonic 29 | % | Read | |||
| L1 Voltage Harmonic 30 | % | Read | |||
| L1 Voltage Harmonic 31 | % | Read | |||
| L2 Voltage Fundamental | V | Read | |||
| L2 Voltage Harmonic 2 | % | Read | |||
| L2 Voltage Harmonic 3 | % | Read | |||
| L2 Voltage Harmonic 4 | % | Read | |||
| L2 Voltage Harmonic 5 | % | Read | |||
| L2 Voltage Harmonic 6 | % | Read | |||
| L2 Voltage Harmonic 7 | % | Read | |||
| L2 Voltage Harmonic 8 | % | Read | |||
| L2 Voltage Harmonic 9 | % | Read | |||
| L2 Voltage Harmonic 10 | % | Read | |||
| L2 Voltage Harmonic 11 | % | Read | |||
| L2 Voltage Harmonic 12 | % | Read | |||
| L2 Voltage Harmonic 13 | % | Read | |||
| L2 Voltage Harmonic 14 | % | Read | |||
| L2 Voltage Harmonic 15 | % | Read | |||
| L2 Voltage Harmonic 16 | % | Read | |||
| L2 Voltage Harmonic 17 | % | Read | |||
| L2 Voltage Harmonic 18 | % | Read | |||
| L2 Voltage Harmonic 19 | % | Read | |||
| L2 Voltage Harmonic 20 | % | Read | |||
| L2 Voltage Harmonic 21 | % | Read | |||
| L2 Voltage Harmonic 22 | % | Read | |||
| L2 Voltage Harmonic 23 | % | Read | |||
| L2 Voltage Harmonic 24 | % | Read | |||
| L2 Voltage Harmonic 25 | % | Read | |||
| L2 Voltage Harmonic 26 | % | Read | |||
| L2 Voltage Harmonic 27 | % | Read | |||
| L2 Voltage Harmonic 28 | % | Read | |||
| L2 Voltage Harmonic 29 | % | Read | |||
| L2 Voltage Harmonic 30 | % | Read | |||
| L2 Voltage Harmonic 31 | % | Read | |||
| L3 Voltage Fundamental | V | Read | |||
| L3 Voltage Harmonic 2 | % | Read | |||
| L3 Voltage Harmonic 3 | % | Read | |||
| L3 Voltage Harmonic 4 | % | Read | |||
| L3 Voltage Harmonic 5 | % | Read | |||
| L3 Voltage Harmonic 6 | % | Read | |||
| L3 Voltage Harmonic 7 | % | Read | |||
| L3 Voltage Harmonic 8 | % | Read | |||
| L3 Voltage Harmonic 9 | % | Read | |||
| L3 Voltage Harmonic 10 | % | Read | |||
| L3 Voltage Harmonic 11 | % | Read | |||
| L3 Voltage Harmonic 12 | % | Read | |||
| L3 Voltage Harmonic 13 | % | Read | |||
| L3 Voltage Harmonic 14 | % | Read | |||
| L3 Voltage Harmonic 15 | % | Read | |||
| L3 Voltage Harmonic 16 | % | Read | |||
| L3 Voltage Harmonic 17 | % | Read | |||
| L3 Voltage Harmonic 18 | % | Read | |||
| L3 Voltage Harmonic 19 | % | Read | |||
| L3 Voltage Harmonic 20 | % | Read | |||
| L3 Voltage Harmonic 21 | % | Read | |||
| L3 Voltage Harmonic 22 | % | Read | |||
| L3 Voltage Harmonic 23 | % | Read | |||
| L3 Voltage Harmonic 24 | % | Read | |||
| L3 Voltage Harmonic 25 | % | Read | |||
| L3 Voltage Harmonic 26 | % | Read | |||
| L3 Voltage Harmonic 27 | % | Read | |||
| L3 Voltage Harmonic 28 | % | Read | |||
| L3 Voltage Harmonic 29 | % | Read | |||
| L3 Voltage Harmonic 30 | % | Read | |||
| L3 Voltage Harmonic 31 | % | Read | |||
| L1 Current Fundamental | mA | Read | |||
| L1 Current Harmonic 2 | % | Read | |||
| L1 Current Harmonic 3 | % | Read | |||
| L1 Current Harmonic 4 | % | Read | |||
| L1 Current Harmonic 5 | % | Read | |||
| L1 Current Harmonic 6 | % | Read | |||
| L1 Current Harmonic 7 | % | Read | |||
| L1 Current Harmonic 8 | % | Read | |||
| L1 Current Harmonic 9 | % | Read | |||
| L1 Current Harmonic 10 | % | Read | |||
| L1 Current Harmonic 11 | % | Read | |||
| L1 Current Harmonic 12 | % | Read | |||
| L1 Current Harmonic 13 | % | Read | |||
| L1 Current Harmonic 14 | % | Read | |||
| L1 Current Harmonic 15 | % | Read | |||
| L1 Current Harmonic 16 | % | Read | |||
| L1 Current Harmonic 17 | % | Read | |||
| L1 Current Harmonic 18 | % | Read | |||
| L1 Current Harmonic 19 | % | Read | |||
| L1 Current Harmonic 20 | % | Read | |||
| L1 Current Harmonic 21 | % | Read | |||
| L1 Current Harmonic 22 | % | Read | |||
| L1 Current Harmonic 23 | % | Read | |||
| L1 Current Harmonic 24 | % | Read | |||
| L1 Current Harmonic 25 | % | Read | |||
| L1 Current Harmonic 26 | % | Read | |||
| L1 Current Harmonic 27 | % | Read | |||
| L1 Current Harmonic 28 | % | Read | |||
| L1 Current Harmonic 29 | % | Read | |||
| L1 Current Harmonic 30 | % | Read | |||
| L1 Current Harmonic 31 | % | Read | |||
| L2 Current Fundamental | mA | Read | |||
| L2 Current Harmonic 2 | % | Read | |||
| L2 Current Harmonic 3 | % | Read | |||
| L2 Current Harmonic 4 | % | Read | |||
| L2 Current Harmonic 5 | % | Read | |||
| L2 Current Harmonic 6 | % | Read | |||
| L2 Current Harmonic 7 | % | Read | |||
| L2 Current Harmonic 8 | % | Read | |||
| L2 Current Harmonic 9 | % | Read | |||
| L2 Current Harmonic 10 | % | Read | |||
| L2 Current Harmonic 11 | % | Read | |||
| L2 Current Harmonic 12 | % | Read | |||
| L2 Current Harmonic 13 | % | Read | |||
| L2 Current Harmonic 14 | % | Read | |||
| L2 Current Harmonic 15 | % | Read | |||
| L2 Current Harmonic 16 | % | Read | |||
| L2 Current Harmonic 17 | % | Read | |||
| L2 Current Harmonic 18 | % | Read | |||
| L2 Current Harmonic 19 | % | Read | |||
| L2 Current Harmonic 20 | % | Read | |||
| L2 Current Harmonic 21 | % | Read | |||
| L2 Current Harmonic 22 | % | Read | |||
| L2 Current Harmonic 23 | % | Read | |||
| L2 Current Harmonic 24 | % | Read | |||
| L2 Current Harmonic 25 | % | Read | |||
| L2 Current Harmonic 26 | % | Read | |||
| L2 Current Harmonic 27 | % | Read | |||
| L2 Current Harmonic 28 | % | Read | |||
| L2 Current Harmonic 29 | % | Read | |||
| L2 Current Harmonic 30 | % | Read | |||
| L2 Current Harmonic 31 | % | Read | |||
| L3 Current Fundamental | mA | Read | |||
| L3 Current Harmonic 2 | % | Read | |||
| L3 Current Harmonic 3 | % | Read | |||
| L3 Current Harmonic 4 | % | Read | |||
| L3 Current Harmonic 5 | % | Read | |||
| L3 Current Harmonic 6 | % | Read | |||
| L3 Current Harmonic 7 | % | Read | |||
| L3 Current Harmonic 8 | % | Read | |||
| L3 Current Harmonic 9 | % | Read | |||
| L3 Current Harmonic 10 | % | Read | |||
| L3 Current Harmonic 11 | % | Read | |||
| L3 Current Harmonic 12 | % | Read | |||
| L3 Current Harmonic 13 | % | Read | |||
| L3 Current Harmonic 14 | % | Read | |||
| L3 Current Harmonic 15 | % | Read | |||
| L3 Current Harmonic 16 | % | Read | |||
| L3 Current Harmonic 17 | % | Read | |||
| L3 Current Harmonic 18 | % | Read | |||
| L3 Current Harmonic 19 | % | Read | |||
| L3 Current Harmonic 20 | % | Read | |||
| L3 Current Harmonic 21 | % | Read | |||
| L3 Current Harmonic 22 | % | Read | |||
| L3 Current Harmonic 23 | % | Read | |||
| L3 Current Harmonic 24 | % | Read | |||
| L3 Current Harmonic 25 | % | Read | |||
| L3 Current Harmonic 26 | % | Read | |||
| L3 Current Harmonic 27 | % | Read | |||
| L3 Current Harmonic 28 | % | Read | |||
| L3 Current Harmonic 29 | % | Read | |||
| L3 Current Harmonic 30 | % | Read | |||
| L3 Current Harmonic 31 | % | Read | |||
| Delete Maximum Values | Write | ||||
| Delete Minimum Values | Write | ||||
| Reset Maximum Demand | Write | ||||
| Delete Hour Counter Tariff 1 | Write | ||||
| Delete Hour Counter Tariff 2 | Write | ||||
| Delete All Energies | Write | ||||
| Delete Three-phase Energies | Write | ||||
| Delete Energies Per Phase | Write | ||||
| Delete Energies L1 | Write | ||||
| Delete Energies L2 | Write | ||||
| Delete Energies L3 | Write | ||||
| Delete All Parameters | Write | ||||
| Voltage Primary | Read and write | ||||
| Voltage Secondary | Read and write | ||||
| Current Primary | Read and write | ||||
| Current Secondary | Read and write | ||||
| Flex Sensor Type | Read and write | ||||
| Number Of Quadrants | Read and write | ||||
| Measurement Convention | Read and write | ||||
| Measurement System | Read and write | ||||
| Demand Integration Period | min | Read and write | |||
| Backlight Time | s | Read and write | |||
| Harmonics Display | Read and write | ||||
| CO2 Ratio Consumption T1 | Read and write | ||||
| CO2 Ratio Consumption T2 | Read and write | ||||
| CO2 Ratio Generation T1 | Read and write | ||||
| CO2 Ratio Generation T2 | Read and write | ||||
| Cost Per kWh Consumption T1 | Read and write | ||||
| Cost Per kWh Consumption T2 | Read and write | ||||
| Cost Per kWh Generation T1 | Read and write | ||||
| Cost Per kWh Generation T2 | Read and write | ||||
| Alarm Maximum Value | Read and write | ||||
| Alarm Minimum Value | Read and write | ||||
| Output Variable Code | Read and write | ||||
| Alarm Connection Delay | s | Read and write | |||
| Alarm Hysteresis | % | Read and write | |||
| Alarm Latch | Read and write | ||||
| Alarm Disconnection Delay | s | Read and write | |||
| Output Contact Status | Read and write | ||||
| kWh Per Pulse | Read and write | ||||
| Pulse Width | ms | Read and write | |||
| Input Mode Or Tariff | Read and write | ||||
| Data Bits | Read and write | ||||
| Stop Bits | Read and write | ||||
| BACnet Device ID | Read and write | ||||
| BACnet MAC | Read and write | ||||
| Password | Read and write | ||||
| Programming Lock | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show voltages, currents and power of each feeder on a dashboard per switchboard.
- Send an email when the voltage THD on a phase rises above a limit you choose.
- Compare consumed and generated energy per tariff and per phase over months in the 365-day history.
- Track maximum demand to see whether a connection is close to its contracted capacity.
- Clear the energy counters remotely after a change of tenant or installation.
Installation
Connect RS485 A(+), B(-) and the shield S of the meter to the ModbusCloud Gateway and terminate both ends of the line.
In the setup menu, choose protocol Modbus and set peripheral number, speed and parity. Defaults are 1, 19200 baud, no parity, 8 data bits, 1 stop bit.
In ModbusCloud, add a Modbus device with the same settings and import the Circutor CVM-E3-MINI template.
Check that L1 Phase Voltage and L1 Frequency show plausible values and that the currents match the load.
Things to watch for
The meter does not answer. What should I check?
Check in the setup menu that the protocol is Modbus and not BACnet, and that peripheral number, speed and parity match the Modbus device in ModbusCloud; the default is 19200 baud without parity. Then swap A and B and check the termination at both ends of the line.
Why does a single setting not change when I write it?
The meter only accepts writes with function 10 and applies new settings after a reset. The five transformer ratio registers must be written together in one message; a single register is rejected. Change ratios on the meter itself if a group write is not possible.
Why are there kWh and Wh registers for the same energy?
The meter gives each energy counter as a register in kWh (or kvarh, kVAh) and a register in Wh (varh, VAh). Use the k-unit register for dashboards and history; compare both on the display if you need finer resolution.
What should I watch out for with the delete commands?
Delete commands clear maximum values, maximum demand, hour counters or energy counters at once and cannot be undone. Read the counters you need first. Writes to the configuration also restart parts of the measurement after the reset, so plan them outside critical moments.