Janitza Janitza UMG 96-EL Modbus TCP template

Janitza UMG 96-EL

Energy analyser with Ethernet: voltage, current, power, energy and power quality per phase.

The Janitza UMG 96-EL is an energy analyser that measures voltage, current, power, energy and power quality per phase in main and sub-distribution boards. This Modbus TCP template reads all measured, mean, minimum and maximum values and energy per tariff, and lets you set transformer ratios, tariffs and comparators from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
1123, read and write
Brand
Janitza
Key readings
Voltage · Current · Real power · Reactive and apparent power · Power factor · Frequency · Energy · THD
Available commands
Transformer ratios · Tariff settings · Comparator limits · Energy counter preset
Compatible models
UMG 96-EL 90-277V · UMG 96-EL 24-90V
Last updated

Registers (1123)

1123 read, 303 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Voltage L1-NVRead19000FC03float32
Voltage L2-NVRead19002FC03float32
Voltage L3-NVRead19004FC03float32
Voltage L1-L2VRead19006FC03float32
Voltage L2-L3VRead19008FC03float32
Voltage L3-L1VRead
Current I L1ARead
Current I L2ARead
Current I L3ARead
Neutral Current Vector SumARead
Real Power P1 L1NWRead
Real Power P2 L2NWRead
Real Power P3 L3NWRead
Real Power TotalWRead
Apparent Power S1 L1NVARead
Apparent Power S2 L2NVARead
Apparent Power S3 L3NVARead
Apparent Power TotalVARead
Fundamental Reactive Power Q1 L1NvarRead
Fundamental Reactive Power Q2 L2NvarRead
Fundamental Reactive Power Q3 L3NvarRead
Fundamental Reactive Power TotalvarRead
Cos Phi, UL1 I1Read
Cos Phi, UL2 I2Read
Cos Phi, UL3 I3Read
Measured Frequency 10secHzRead
Rotation FieldRead
Real Energy L1WhRead
Real Energy L2WhRead
Real Energy L3WhRead
Real Energy L1-L3WhRead
Real Energy L1, ConsumedWhRead
Real Energy L2, ConsumedWhRead
Real Energy L3, ConsumedWhRead
Real Energy L1-L3, ConsumedWhRead
Real Energy L1, DeliveredWhRead
Real Energy L2, DeliveredWhRead
Real Energy L3, DeliveredWhRead
Real Energy L1-L3, DeliveredWhRead
Apparent Energy L1VAhRead
Apparent Energy L2VAhRead
Apparent Energy L3VAhRead
Apparent Energy L1-L3VAhRead
Fundamental Reactive Energy L1varhRead
Fundamental Reactive Energy L2varhRead
Fundamental Reactive Energy L3varhRead
Fundamental Reactive Energy L1-L3varhRead
Fundamental Reactive Energy Ind. L1varhRead
Fundamental Reactive Energy Ind. L2varhRead
Fundamental Reactive Energy Ind. L3varhRead
Fundamental Reactive Energy Ind. L1-L3varhRead
Fundamental Reactive Energy Cap. L1varhRead
Fundamental Reactive Energy Cap. L2varhRead
Fundamental Reactive Energy Cap. L3varhRead
Fundamental Reactive Energy Cap. L1-L3varhRead
THD, U L1-N%Read
THD, U L2-N%Read
THD, U L3-N%Read
THD, I1%Read
THD, I2%Read
THD, I3%Read
Measured Frequency 10sec (Measured)HzRead
Voltage, Zero SequenceVRead
Voltage, Negative SequenceVRead
Voltage, Positive SequenceVRead
Voltage U1 L1-NVRead
Voltage U2 L2-NVRead
Voltage U3 L3-NVRead
Voltage U1 L1-L2VRead
Voltage U2 L2-L3VRead
Voltage U3 L3-L1VRead
Fundamental Power Factor, Cos Phi, ULN, I1Read
Fundamental Power Factor, Cos Phi, ULN, I2Read
Fundamental Power Factor, Cos Phi, ULN, I3Read
Fundamental Power Factor TotalRead
Power Factor, UL1N, I1Read
Power Factor, UL2N, I2Read
Power Factor, UL3N, I3Read
Power Factor TotalRead
THD, U L1N%Read
THD, U L2N%Read
THD, U L3N%Read
THD, U L1L2%Read
THD, U L2L3%Read
THD, U L3L1%Read
Voltage, Real Part U1 L1-NVRead
Voltage, Real Part U2 L2-NVRead
Voltage, Real Part U3 L3-NVRead
Voltage, Imaginary Part U L1-NVRead
Voltage, Imaginary Part U L2-NVRead
Voltage, Imaginary Part U L3-NVRead
Current I1 L1ARead
Current I2 L2ARead
Current I3 L3ARead
Neutral Current Vector Sum (Measured)ARead
Real Power P1 L1-NWRead
Real Power P2 L2-NWRead
Real Power P2 L3-NWRead
Real Power Total (Measured)WRead
Fundamental Reactive Power Q1 L1-NvarRead
Fundamental Reactive Power Q2 L2-NvarRead
Fundamental Reactive Power Q3 L3-NvarRead
Fundamental Reactive Power Total (Measured)varRead
Apparent Power S1 L1-NVARead
Apparent Power S2 L2-NVARead
Apparent Power S3 L3-NVARead
Apparent Power Total (Measured)VARead
Fundamental Real Power P01 L1-NWRead
Fundamental Real Power P02 L2-NWRead
Fundamental Real Power P03 L3-NWRead
Fundamental Real Power TotalWRead
Harmonic Distortion Power D1 L1-NvarRead
Harmonic Distortion Power D2 L2-NvarRead
Harmonic Distortion Power D3 L3-NvarRead
Distortion Power TotalvarRead
THD, I1 (Measured)%Read
THD, I2 (Measured)%Read
THD, I3 (Measured)%Read
TDD I1, with Reference to Nominal Current%Read
TDD I2, with Reference to Nominal Current%Read
TDD I3, with Reference to Nominal Current%Read
Current, Zero SequenceARead
Current, Negative SequenceARead
Current, Positive SequenceARead
Current, Real Part I L1ARead
Current, Real Part I L2ARead
Current, Real Part I L3ARead
Current, Imaginary Part I L1ARead
Current, Imaginary Part I L2ARead
Current, Imaginary Part I L3ARead
Rotation Field (Measured)Read
Frequency 200 MsHzRead
Crest Factor, U L1Read
Crest Factor, U L2Read
Crest Factor, U L3Read
Crest Factor, I L1Read
Crest Factor, I L2Read
Crest Factor, I L3Read
Measured Frequency 10sec (Short)HzRead
Voltage, Zero Sequence (Short)Read
Voltage, Negative Sequence (Short)Read
Voltage, Positive Sequence (Short)Read
Voltage U1 L1-N (Short)VRead
Voltage U2 L2-N (Short)VRead
Voltage U3 L3-N (Short)VRead
Voltage U1 L1-L2 (Short)VRead
Voltage U2 L2-L3 (Short)VRead
Voltage U3 L3-L1 (Short)VRead
Fundamental Power Factor, Cos Phi, UL1-N I1 (Short)Read
Fundamental Power Factor, Cos Phi, UL2-N I2 (Short)Read
Fundamental Power Factor, Cos Phi, UL3-N I3 (Short)Read
Fundamental Power Factor Total (Short)Read
Power Factor, UL1-N I1 (Short)Read
Power Factor, UL2-N I2 (Short)Read
Power Factor, UL3-N I3 (Short)Read
Power Factor Total (Short)Read
THD, U L1-N (Short)%Read
THD, U L2-N (Short)%Read
THD, U L3-N (Short)%Read
THD, U L1-L2 (Short)%Read
THD, U L2-L3 (Short)%Read
THD, U L3-L1 (Short)%Read
Voltage, Real Part U L1-N (Short)VRead
Voltage, Real Part U L2-N (Short)VRead
Voltage, Real Part U L3-N (Short)VRead
Voltage, Imaginary Part U L1-N (Short)VRead
Voltage, Imaginary Part U L2-N (Short)VRead
Voltage, Imaginary Part U L3-N (Short)VRead
Current I L1 (Short)ARead
Current I L2 (Short)ARead
Current I L3 (Short)ARead
Neutral Current Vector Sum (Short)ARead
Real Power P L1-N (Short)WRead
Real Power P L2-N (Short)WRead
Real Power P L3-N (Short)WRead
Real Power Total (Short)WRead
Fundamental Reactive Power Q L1-N (Short)varRead
Fundamental Reactive Power Q L2-N (Short)varRead
Fundamental Reactive Power Q L3-N (Short)varRead
Fundamental Reactive Power Total (Short)varRead
Apparent Power S L1-N (Short)VARead
Apparent Power S L2-N (Short)VARead
Apparent Power S L3-N (Short)VARead
Apparent Power Total (Short)VARead
Fundamental Real Power P0 L1-N (Short)WRead
Fundamental Real Power P0 L2-N (Short)WRead
Fundamental Real Power P0 L3-N (Short)WRead
Fundamental Power Factor Total (Short, W)Read
Harmonic Distortion Power D L1-N (Short)varRead
Harmonic Distortion Power D L2-N (Short)varRead
Harmonic Distortion Power D L3-N (Short)varRead
Distortion Power Total (Short)varRead
THD, I1 (Short)%Read
THD, I2 (Short)%Read
THD, I3 (Short)%Read
TDD I1 (Short)%Read
TDD I2 (Short)%Read
TDD I3 (Short)%Read
Current, Zero Sequence (Short)ARead
Current, Negative Sequence (Short)ARead
Current, Positive Sequence (Short)ARead
Current, Real Part I L1 (Short)ARead
Current, Real Part I L2 (Short)ARead
Current, Real Part I L3 (Short)ARead
Current, Imaginary Part I L1 (Short)ARead
Current, Imaginary Part I L2 (Short)ARead
Current, Imaginary Part I L3 (Short)ARead
Rotation Field (Short)Read
Frequency 200 Ms, Integer (Short)HzRead
Real Energy, L1WhRead and write
Real Energy, L1, Tariff 1WhRead and write
Real Energy, L1, Tariff 2WhRead and write
Real Energy, L1, Tariff 3WhRead and write
Real Energy, L1, Tariff 4WhRead and write
Real Energy, L1, Tariff 5WhRead and write
Real Energy, L1, Tariff 6WhRead and write
Real Energy, L1, Tariff 7WhRead and write
Real Energy, L1, ConsumedWhRead and write
Real Energy, L1, Consumed, Tariff 1WhRead and write
Real Energy, L1, Consumed, Tariff 2WhRead and write
Real Energy, L1, Consumed, Tariff 3WhRead and write
Real Energy, L1, Consumed, Tariff 4WhRead and write
Real Energy, L1, Consumed, Tariff 5WhRead and write
Real Energy, L1, Consumed, Tariff 6WhRead and write
Real Energy, L1, Consumed, Tariff 7WhRead and write
Real Energy, L1, DeliveredWhRead and write
Real Energy, L1, Delivered, Tariff 1WhRead and write
Real Energy, L1, Delivered, Tariff 2WhRead and write
Real Energy, L1, Delivered, Tariff 3WhRead and write
Real Energy, L1, Delivered, Tariff 4WhRead and write
Real Energy, L1, Delivered, Tariff 5WhRead and write
Real Energy, L1, Delivered, Tariff 6WhRead and write
Real Energy, L1, Delivered, Tariff 7WhRead and write
Fundamental Reactive Energy, L1varhRead and write
Fundamental Reactive Energy, L1, Tariff 1varhRead and write
Fundamental Reactive Energy, L1, Tariff 2varhRead and write
Fundamental Reactive Energy, L1, Tariff 3varhRead and write
Fundamental Reactive Energy, L1, Tariff 4varhRead and write
Fundamental Reactive Energy, L1, Tariff 5varhRead and write
Fundamental Reactive Energy, L1, Tariff 6varhRead and write
Fundamental Reactive Energy, L1, Tariff 7varhRead and write
Fundamental Reactive Energy, L1, Ind.varhRead and write
Fundamental Reactive Energy, L1, Ind., Tariff 1varhRead and write
Fundamental Reactive Energy, L1, Ind., Tariff 2varhRead and write
Fundamental Reactive Energy, L1, Ind., Tariff 3varhRead and write
Fundamental Reactive Energy, L1, Ind., Tariff 4varhRead and write
Fundamental Reactive Energy, L1, Ind., Tariff 5varhRead and write
Fundamental Reactive Energy, L1, Ind., Tariff 6varhRead and write
Fundamental Reactive Energy, L1, Ind., Tariff 7varhRead and write
Fundamental Reactive Energy, L1, Cap.varhRead and write
Fundamental Reactive Energy, L1, Cap., Tariff 1varhRead and write
Fundamental Reactive Energy, L1, Cap., Tariff 2varhRead and write
Fundamental Reactive Energy, L1, Cap., Tariff 3varhRead and write
Fundamental Reactive Energy, L1, Cap., Tariff 4varhRead and write
Fundamental Reactive Energy, L1, Cap., Tariff 5varhRead and write
Fundamental Reactive Energy, L1, Cap., Tariff 6varhRead and write
Fundamental Reactive Energy, L1, Cap., Tariff 7varhRead and write
Apparent Energy, L1VAhRead and write
Apparent Energy, L1, Tariff 1VAhRead and write
Apparent Energy, L1, Tariff 2VAhRead and write
Apparent Energy, L1, Tariff 3VAhRead and write
Apparent Energy, L1, Tariff 4VAhRead and write
Apparent Energy, L1, Tariff 5VAhRead and write
Apparent Energy, L1, Tariff 6VAhRead and write
Apparent Energy, L1, Tariff 7VAhRead and write
Real Energy, L2WhRead and write
Real Energy, L2, Tariff 1WhRead and write
Real Energy, L2, Tariff 2WhRead and write
Real Energy, L2, Tariff 3WhRead and write
Real Energy, L2, Tariff 4WhRead and write
Real Energy, L2, Tariff 5WhRead and write
Real Energy, L2, Tariff 6WhRead and write
Real Energy, L2, Tariff 7WhRead and write
Real Energy, L2, ConsumedWhRead and write
Real Energy, L2, Consumed, Tariff 1WhRead and write
Real Energy, L2, Consumed, Tariff 2WhRead and write
Real Energy, L2, Consumed, Tariff 3WhRead and write
Real Energy, L2, Consumed, Tariff 4WhRead and write
Real Energy, L2, Consumed, Tariff 5WhRead and write
Real Energy, L2, Consumed, Tariff 6WhRead and write
Real Energy, L2, Consumed, Tariff 7WhRead and write
Real Energy, L2, DeliveredWhRead and write
Real Energy, L2, Delivered, Tariff 1WhRead and write
Real Energy, L2, Delivered, Tariff 2WhRead and write
Real Energy, L2, Delivered, Tariff 3WhRead and write
Real Energy, L2, Delivered, Tariff 4WhRead and write
Real Energy, L2, Delivered, Tariff 5WhRead and write
Real Energy, L2, Delivered, Tariff 6WhRead and write
Real Energy, L2, Delivered, Tariff 7WhRead and write
Fundamental Reactive Energy, L2varhRead and write
Fundamental Reactive Energy, L2, Tariff 1varhRead and write
Fundamental Reactive Energy, L2, Tariff 2varhRead and write
Fundamental Reactive Energy, L2, Tariff 3varhRead and write
Fundamental Reactive Energy, L2, Tariff 4varhRead and write
Fundamental Reactive Energy, L2, Tariff 5varhRead and write
Fundamental Reactive Energy, L2, Tariff 6varhRead and write
Fundamental Reactive Energy, L2, Tariff 7varhRead and write
Fundamental Reactive Energy, L2, Ind.varhRead and write
Fundamental Reactive Energy, L2, Ind., Tariff 1varhRead and write
Fundamental Reactive Energy, L2, Ind., Tariff 2varhRead and write
Fundamental Reactive Energy, L2, Ind., Tariff 3varhRead and write
Fundamental Reactive Energy, L2, Ind., Tariff 4varhRead and write
Fundamental Reactive Energy, L2, Ind., Tariff 5varhRead and write
Fundamental Reactive Energy, L2, Ind., Tariff 6varhRead and write
Fundamental Reactive Energy, L2, Ind., Tariff 7varhRead and write
Fundamental Reactive Energy, L2, Cap.varhRead and write
Fundamental Reactive Energy, L2, Cap., Tariff 1varhRead and write
Fundamental Reactive Energy, L2, Cap., Tariff 2varhRead and write
Fundamental Reactive Energy, L2, Cap., Tariff 3varhRead and write
Fundamental Reactive Energy, L2, Cap., Tariff 4varhRead and write
Fundamental Reactive Energy, L2, Cap., Tariff 5varhRead and write
Fundamental Reactive Energy, L2, Cap., Tariff 6varhRead and write
Fundamental Reactive Energy, L2, Cap., Tariff 7varhRead and write
Apparent Energy, L2VAhRead and write
Apparent Energy, L2, Tariff 1VAhRead and write
Apparent Energy, L2, Tariff 2VAhRead and write
Apparent Energy, L2, Tariff 3VAhRead and write
Apparent Energy, L2, Tariff 4VAhRead and write
Apparent Energy, L2, Tariff 5VAhRead and write
Apparent Energy, L2, Tariff 6VAhRead and write
Apparent Energy, L2, Tariff 7VAhRead and write
Real Energy, L3WhRead and write
Real Energy, L3, Tariff 1WhRead and write
Real Energy, L3, Tariff 2WhRead and write
Real Energy, L3, Tariff 3WhRead and write
Real Energy, L3, Tariff 4WhRead and write
Real Energy, L3, Tariff 5WhRead and write
Real Energy, L3, Tariff 6WhRead and write
Real Energy, L3, Tariff 7WhRead and write
Real Energy, L3, ConsumedWhRead and write
Real Energy, L3, Consumed, Tariff 1WhRead and write
Real Energy, L3, Consumed, Tariff 2WhRead and write
Real Energy, L3, Consumed, Tariff 3WhRead and write
Real Energy, L3, Consumed, Tariff 4WhRead and write
Real Energy, L3, Consumed, Tariff 5WhRead and write
Real Energy, L3, Consumed, Tariff 6WhRead and write
Real Energy, L3, Consumed, Tariff 7WhRead and write
Real Energy, L3, DeliveredWhRead and write
Real Energy, L3, Delivered, Tariff 1WhRead and write
Real Energy, L3, Delivered, Tariff 2WhRead and write
Real Energy, L3, Delivered, Tariff 3WhRead and write
Real Energy, L3, Delivered, Tariff 4WhRead and write
Real Energy, L3, Delivered, Tariff 5WhRead and write
Real Energy, L3, Delivered, Tariff 6WhRead and write
Real Energy, L3, Delivered, Tariff 7WhRead and write
Fundamental Reactive Energy, L3varhRead and write
Fundamental Reactive Energy, L3, Tariff 1varhRead and write
Fundamental Reactive Energy, L3, Tariff 2varhRead and write
Fundamental Reactive Energy, L3, Tariff 3varhRead and write
Fundamental Reactive Energy, L3, Tariff 4varhRead and write
Fundamental Reactive Energy, L3, Tariff 5varhRead and write
Fundamental Reactive Energy, L3, Tariff 6varhRead and write
Fundamental Reactive Energy, L3, Tariff 7varhRead and write
Fundamental Reactive Energy, L3, Ind.varhRead and write
Fundamental Reactive Energy, L3, Ind., Tariff 1varhRead and write
Fundamental Reactive Energy, L3, Ind., Tariff 2varhRead and write
Fundamental Reactive Energy, L3, Ind., Tariff 3varhRead and write
Fundamental Reactive Energy, L3, Ind., Tariff 4varhRead and write
Fundamental Reactive Energy, L3, Ind., Tariff 5varhRead and write
Fundamental Reactive Energy, L3, Ind., Tariff 6varhRead and write
Fundamental Reactive Energy, L3, Ind., Tariff 7varhRead and write
Fundamental Reactive Energy, L3, Cap.varhRead and write
Fundamental Reactive Energy, L3, Cap., Tariff 1varhRead and write
Fundamental Reactive Energy, L3, Cap., Tariff 2varhRead and write
Fundamental Reactive Energy, L3, Cap., Tariff 3varhRead and write
Fundamental Reactive Energy, L3, Cap., Tariff 4varhRead and write
Fundamental Reactive Energy, L3, Cap., Tariff 5varhRead and write
Fundamental Reactive Energy, L3, Cap., Tariff 6varhRead and write
Fundamental Reactive Energy, L3, Cap., Tariff 7varhRead and write
Apparent Energy, L3VAhRead and write
Apparent Energy, L3, Tariff 1VAhRead and write
Apparent Energy, L3, Tariff 2VAhRead and write
Apparent Energy, L3, Tariff 3VAhRead and write
Apparent Energy, L3, Tariff 4VAhRead and write
Apparent Energy, L3, Tariff 5VAhRead and write
Apparent Energy, L3, Tariff 6VAhRead and write
Apparent Energy, L3, Tariff 7VAhRead and write
Real Energy, Sum L1-L3WhRead and write
Real Energy, Sum L1-L3, Tariff 1WhRead and write
Real Energy, Sum L1-L3, Tariff 2WhRead and write
Real Energy, Sum L1-L3, Tariff 3WhRead and write
Real Energy, Sum L1-L3, Tariff 4WhRead and write
Real Energy, Sum L1-L3, Tariff 5WhRead and write
Real Energy, Sum L1-L3, Tariff 6WhRead and write
Real Energy, Sum L1-L3, Tariff 7WhRead and write
Real Energy, Sum L1-L3, ConsumedWhRead and write
Real Energy, Sum L1-L3, Consumed, Tariff 1WhRead and write
Real Energy, Sum L1-L3, Consumed, Tariff 2WhRead and write
Real Energy, Sum L1-L3, Consumed, Tariff 3WhRead and write
Real Energy, Sum L1-L3, Consumed, Tariff 4WhRead and write
Real Energy, Sum L1-L3, Consumed, Tariff 5WhRead and write
Real Energy, Sum L1-L3, Consumed, Tariff 6WhRead and write
Real Energy, Sum L1-L3, Consumed, Tariff 7WhRead and write
Real Energy, Sum L1-L3, DeliveredWhRead and write
Real Energy, Sum L1-L3, Delivered, Tariff 1WhRead and write
Real Energy, Sum L1-L3, Delivered, Tariff 2WhRead and write
Real Energy, Sum L1-L3, Delivered, Tariff 3WhRead and write
Real Energy, Sum L1-L3, Delivered, Tariff 4WhRead and write
Real Energy, Sum L1-L3, Delivered, Tariff 5WhRead and write
Real Energy, Sum L1-L3, Delivered, Tariff 6WhRead and write
Real Energy, Sum L1-L3, Delivered, Tariff 7WhRead and write
Fundamental Reactive Energy, Sum L1-L3varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Tariff 1varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Tariff 2varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Tariff 3varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Tariff 4varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Tariff 5varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Tariff 6varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Tariff 7varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind.varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 1varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 2varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 3varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 4varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 5varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 6varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 7varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap.varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 1varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 2varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 3varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 4varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 5varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 6varhRead and write
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 7varhRead and write
Apparent Energy, Sum L1-L3VAhRead and write
Apparent Energy, Sum L1-L3, Tariff 1VAhRead and write
Apparent Energy, Sum L1-L3, Tariff 2VAhRead and write
Apparent Energy, Sum L1-L3, Tariff 3VAhRead and write
Apparent Energy, Sum L1-L3, Tariff 4VAhRead and write
Apparent Energy, Sum L1-L3, Tariff 5VAhRead and write
Apparent Energy, Sum L1-L3, Tariff 6VAhRead and write
Apparent Energy, Sum L1-L3, Tariff 7VAhRead and write
Real Energy, L1 (Int)WhRead
Real Energy, L1, Tariff 1 (Int)WhRead
Real Energy, L1, Tariff 2 (Int)WhRead
Real Energy, L1, Tariff 3 (Int)WhRead
Real Energy, L1, Tariff 4 (Int)WhRead
Real Energy, L1, Tariff 5 (Int)WhRead
Real Energy, L1, Tariff 6 (Int)WhRead
Real Energy, L1, Tariff 7 (Int)WhRead
Real Energy, L1, Consumed (Int)WhRead
Real Energy, L1, Consumed, Tariff 1 (Int)WhRead
Real Energy, L1, Consumed, Tariff 2 (Int)WhRead
Real Energy, L1, Consumed, Tariff 3 (Int)WhRead
Real Energy, L1, Consumed, Tariff 4 (Int)WhRead
Real Energy, L1, Consumed, Tariff 5 (Int)WhRead
Real Energy, L1, Consumed, Tariff 6 (Int)WhRead
Real Energy, L1, Consumed, Tariff 7 (Int)WhRead
Real Energy, L1, Delivered (Int)WhRead
Real Energy, L1, Delivered, Tariff 1 (Int)WhRead
Real Energy, L1, Delivered, Tariff 2 (Int)WhRead
Real Energy, L1, Delivered, Tariff 3 (Int)WhRead
Real Energy, L1, Delivered, Tariff 4 (Int)WhRead
Real Energy, L1, Delivered, Tariff 5 (Int)WhRead
Real Energy, L1, Delivered, Tariff 6 (Int)WhRead
Real Energy, L1, Delivered, Tariff 7 (Int)WhRead
Fundamental Reactive Energy, L1 (Int)varhRead
Fundamental Reactive Energy, L1, Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L1, Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L1, Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L1, Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L1, Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L1, Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L1, Tariff 7 (Int)varhRead
Fundamental Reactive Energy, L1, Ind. (Int)varhRead
Fundamental Reactive Energy, L1, Ind., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L1, Ind., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L1, Ind., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L1, Ind., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L1, Ind., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L1, Ind., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L1, Ind., Tariff 7 (Int)varhRead
Fundamental Reactive Energy, L1, Cap. (Int)varhRead
Fundamental Reactive Energy, L1, Cap., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L1, Cap., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L1, Cap., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L1, Cap., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L1, Cap., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L1, Cap., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L1, Cap., Tariff 7 (Int)varhRead
Apparent Energy, L1 (Int)VAhRead
Apparent Energy, L1, Tariff 1 (Int)VAhRead
Apparent Energy, L1, Tariff 2 (Int)VAhRead
Apparent Energy, L1, Tariff 3 (Int)VAhRead
Apparent Energy, L1, Tariff 4 (Int)VAhRead
Apparent Energy, L1, Tariff 5 (Int)VAhRead
Apparent Energy, L1, Tariff 6 (Int)VAhRead
Apparent Energy, L1, Tariff 7 (Int)VAhRead
Real Energy, L2 (Int)WhRead
Real Energy, L2, Tariff 1 (Int)WhRead
Real Energy, L2, Tariff 2 (Int)WhRead
Real Energy, L2, Tariff 3 (Int)WhRead
Real Energy, L2, Tariff 4 (Int)WhRead
Real Energy, L2, Tariff 5 (Int)WhRead
Real Energy, L2, Tariff 6 (Int)WhRead
Real Energy, L2, Tariff 7 (Int)WhRead
Real Energy, L2, Consumed (Int)WhRead
Real Energy, L2, Consumed, Tariff 1 (Int)WhRead
Real Energy, L2, Consumed, Tariff 2 (Int)WhRead
Real Energy, L2, Consumed, Tariff 3 (Int)WhRead
Real Energy, L2, Consumed, Tariff 4 (Int)WhRead
Real Energy, L2, Consumed, Tariff 5 (Int)WhRead
Real Energy, L2, Consumed, Tariff 6 (Int)WhRead
Real Energy, L2, Consumed, Tariff 7 (Int)WhRead
Real Energy, L2, Delivered (Int)WhRead
Real Energy, L2, Delivered, Tariff 1 (Int)WhRead
Real Energy, L2, Delivered, Tariff 2 (Int)WhRead
Real Energy, L2, Delivered, Tariff 3 (Int)WhRead
Real Energy, L2, Delivered, Tariff 4 (Int)WhRead
Real Energy, L2, Delivered, Tariff 5 (Int)WhRead
Real Energy, L2, Delivered, Tariff 6 (Int)WhRead
Real Energy, L2, Delivered, Tariff 7 (Int)WhRead
Fundamental Reactive Energy, L2 (Int)varhRead
Fundamental Reactive Energy, L2, Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L2, Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L2, Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L2, Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L2, Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L2, Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L2, Tariff 7 (Int)varhRead
Fundamental Reactive Energy, L2, Ind. (Int)varhRead
Fundamental Reactive Energy, L2, Ind., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L2, Ind., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L2, Ind., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L2, Ind., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L2, Ind., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L2, Ind., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L2, Ind., Tariff 7 (Int)varhRead
Fundamental Reactive Energy, L2, Cap. (Int)varhRead
Fundamental Reactive Energy, L2, Cap., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L2, Cap., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L2, Cap., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L2, Cap., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L2, Cap., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L2, Cap., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L2, Cap., Tariff 7 (Int)varhRead
Apparent Energy, L2 (Int)VAhRead
Apparent Energy, L2, Tariff 1 (Int)VAhRead
Apparent Energy, L2, Tariff 2 (Int)VAhRead
Apparent Energy, L2, Tariff 3 (Int)VAhRead
Apparent Energy, L2, Tariff 4 (Int)VAhRead
Apparent Energy, L2, Tariff 5 (Int)VAhRead
Apparent Energy, L2, Tariff 6 (Int)VAhRead
Apparent Energy, L2, Tariff 7 (Int)VAhRead
Real Energy, L3 (Int)WhRead
Real Energy, L3, Tariff 1 (Int)WhRead
Real Energy, L3, Tariff 2 (Int)WhRead
Real Energy, L3, Tariff 3 (Int)WhRead
Real Energy, L3, Tariff 4 (Int)WhRead
Real Energy, L3, Tariff 5 (Int)WhRead
Real Energy, L3, Tariff 6 (Int)WhRead
Real Energy, L3, Tariff 7 (Int)WhRead
Real Energy, L3, Consumed (Int)WhRead
Real Energy, L3, Consumed, Tariff 1 (Int)WhRead
Real Energy, L3, Consumed, Tariff 2 (Int)WhRead
Real Energy, L3, Consumed, Tariff 3 (Int)WhRead
Real Energy, L3, Consumed, Tariff 4 (Int)WhRead
Real Energy, L3, Consumed, Tariff 5 (Int)WhRead
Real Energy, L3, Consumed, Tariff 6 (Int)WhRead
Real Energy, L3, Consumed, Tariff 7 (Int)WhRead
Real Energy, L3, Delivered (Int)WhRead
Real Energy, L3, Delivered, Tariff 1 (Int)WhRead
Real Energy, L3, Delivered, Tariff 2 (Int)WhRead
Real Energy, L3, Delivered, Tariff 3 (Int)WhRead
Real Energy, L3, Delivered, Tariff 4 (Int)WhRead
Real Energy, L3, Delivered, Tariff 5 (Int)WhRead
Real Energy, L3, Delivered, Tariff 6 (Int)WhRead
Real Energy, L3, Delivered, Tariff 7 (Int)WhRead
Fundamental Reactive Energy, L3 (Int)varhRead
Fundamental Reactive Energy, L3, Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L3, Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L3, Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L3, Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L3, Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L3, Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L3, Tariff 7 (Int)varhRead
Fundamental Reactive Energy, L3, Ind. (Int)varhRead
Fundamental Reactive Energy, L3, Ind., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L3, Ind., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L3, Ind., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L3, Ind., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L3, Ind., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L3, Ind., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L3, Ind., Tariff 7 (Int)varhRead
Fundamental Reactive Energy, L3, Cap. (Int)varhRead
Fundamental Reactive Energy, L3, Cap., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, L3, Cap., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, L3, Cap., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, L3, Cap., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, L3, Cap., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, L3, Cap., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, L3, Cap., Tariff 7 (Int)varhRead
Apparent Energy, L3 (Int)VAhRead
Apparent Energy, L3, Tariff 1 (Int)VAhRead
Apparent Energy, L3, Tariff 2 (Int)VAhRead
Apparent Energy, L3, Tariff 3 (Int)VAhRead
Apparent Energy, L3, Tariff 4 (Int)VAhRead
Apparent Energy, L3, Tariff 5 (Int)VAhRead
Apparent Energy, L3, Tariff 6 (Int)VAhRead
Apparent Energy, L3, Tariff 7 (Int)VAhRead
Real Energy, Sum L1-L3 (Int)WhRead
Real Energy, Sum L1-L3, Tariff 1 (Int)WhRead
Real Energy, Sum L1-L3, Tariff 2 (Int)WhRead
Real Energy, Sum L1-L3, Tariff 3 (Int)WhRead
Real Energy, Sum L1-L3, Tariff 4 (Int)WhRead
Real Energy, Sum L1-L3, Tariff 5 (Int)WhRead
Real Energy, Sum L1-L3, Tariff 6 (Int)WhRead
Real Energy, Sum L1-L3, Tariff 7 (Int)WhRead
Real Energy, Sum L1-L3, Consumed (Int)WhRead
Real Energy, Sum L1-L3, Consumed, Tariff 1 (Int)WhRead
Real Energy, Sum L1-L3, Consumed, Tariff 2 (Int)WhRead
Real Energy, Sum L1-L3, Consumed, Tariff 3 (Int)WhRead
Real Energy, Sum L1-L3, Consumed, Tariff 4 (Int)WhRead
Real Energy, Sum L1-L3, Consumed, Tariff 5 (Int)WhRead
Real Energy, Sum L1-L3, Consumed, Tariff 6 (Int)WhRead
Real Energy, Sum L1-L3, Consumed, Tariff 7 (Int)WhRead
Real Energy, Sum L1-L3, Delivered (Int)WhRead
Real Energy, Sum L1-L3, Delivered, Tariff 1 (Int)WhRead
Real Energy, Sum L1-L3, Delivered, Tariff 2 (Int)WhRead
Real Energy, Sum L1-L3, Delivered, Tariff 3 (Int)WhRead
Real Energy, Sum L1-L3, Delivered, Tariff 4 (Int)WhRead
Real Energy, Sum L1-L3, Delivered, Tariff 5 (Int)WhRead
Real Energy, Sum L1-L3, Delivered, Tariff 6 (Int)WhRead
Real Energy, Sum L1-L3, Delivered, Tariff 7 (Int)WhRead
Fundamental Reactive Energy, Sum L1-L3 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Tariff 1 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Tariff 2 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Tariff 3 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Tariff 4 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Tariff 5 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Tariff 6 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Tariff 7 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind. (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 7 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap. (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 1 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 2 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 3 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 4 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 5 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 6 (Int)varhRead
Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 7 (Int)varhRead
Apparent Energy, Sum L1-L3 (Int)VAhRead
Apparent Energy, Sum L1-L3, Tariff 1 (Int)VAhRead
Apparent Energy, Sum L1-L3, Tariff 2 (Int)VAhRead
Apparent Energy, Sum L1-L3, Tariff 3 (Int)VAhRead
Apparent Energy, Sum L1-L3, Tariff 4 (Int)VAhRead
Apparent Energy, Sum L1-L3, Tariff 5 (Int)VAhRead
Apparent Energy, Sum L1-L3, Tariff 6 (Int)VAhRead
Apparent Energy, Sum L1-L3, Tariff 7 (Int)VAhRead
Operation Hours Meter (Int)sRead
Comparator Running Time 1sRead
Comparator Running Time 2sRead
Comparator Running Time 3sRead
Comparator Running Time 4sRead
Comparator Running Time 5sRead
Comparator Running Time 6sRead
Mean Measured Frequency 10secHzRead
Mean Voltage, Zero SequenceVRead
Mean Voltage, Negative SequenceVRead
Mean Voltage, Positive SequenceVRead
Mean Voltage L1-NVRead
Mean Voltage L2-NVRead
Mean Voltage L3-NVRead
Mean Voltage L1-L2VRead
Mean Voltage L2-L3VRead
Mean Voltage L3-L1VRead
Mean Fundamental Power Factor, Cos Phi, UL1-N I1Read
Mean Fundamental Power Factor, Cos Phi, UL2-N I2Read
Mean Fundamental Power Factor, Cos Phi, UL3-N I3Read
Mean Fundamental Power Factor TotalRead
Mean Power Factor, UL1-N I1Read
Mean Power Factor, UL2-N I2Read
Mean Power Factor, UL3-N I3Read
Mean Power Factor TotalRead
Mean THD, U L1-N%Read
Mean THD, U L2-N%Read
Mean THD, U L3-N%Read
Mean THD, U L1-L2%Read
Mean THD, U L2-L3%Read
Mean THD, U L3-L1%Read
Mean Voltage, Real Part U L1-NVRead
Mean Voltage, Real Part U L2-NVRead
Mean Voltage, Real Part U L3-NVRead
Mean Voltage, Imaginary Part U L1-NVRead
Mean Voltage, Imaginary Part U L2-NVRead
Mean Voltage, Imaginary Part U L3-NVRead
Mean Current I1ARead
Mean Current I2ARead
Mean Current I3ARead
Mean Neutral Current Vector SumARead
Mean Real Power P L1-NWRead
Mean Real Power P L2-NWRead
Mean Real Power P L3-NWRead
Mean Real Power TotalWRead
Mean Fundamental Reactive Power Q L1-NvarRead
Mean Fundamental Reactive Power Q L2-NvarRead
Mean Fundamental Reactive Power Q L3-NvarRead
Mean Fundamental Reactive Power TotalvarRead
Mean Apparent Power S L1-NVARead
Mean Apparent Power S L2-NVARead
Mean Apparent Power S L3-NVARead
Mean Apparent Power TotalVARead
Mean Fundamental Real Power P0 L1-NWRead
Mean Fundamental Real Power P0 L2-NWRead
Mean Fundamental Real Power P0 L3-NWRead
Mean Fundamental Real Power TotalWRead
Mean Harmonic Distortion Power D L1-NvarRead
Mean Harmonic Distortion Power D L2-NvarRead
Mean Harmonic Distortion Power D L3-NvarRead
Mean Distortion Power TotalvarRead
Mean THD I1%Read
Mean THD I2%Read
Mean THD I3%Read
Mean TDD I1%Read
Mean TDD I2%Read
Mean TDD I3%Read
Mean Current, Zero SequenceARead
Mean Current, Negative SequenceARead
Mean Current, Positive SequenceARead
Mean Current, Real Part I L1ARead
Mean Current, Real Part I L2ARead
Mean Current, Real Part I L3ARead
Mean Current, Imaginary Part I1ARead
Mean Current, Imaginary Part I2ARead
Mean Current, Imaginary Part I3ARead
Average Frequency 200 MsHzRead
Mean Crest Factor, U L1Read
Mean Crest Factor, U L2Read
Mean Crest Factor, U L3Read
Mean Crest Factor, I L1Read
Mean Crest Factor, I L2Read
Mean Crest Factor, I L3Read
Mean Measured Frequency 10sec (Short)HzRead
Mean Voltage, Zero Sequence (Short)Read
Mean Voltage, Negative Sequence (Short)Read
Mean Voltage, Positive Sequence (Short)Read
Mean Voltage L1-N (Short)VRead
Mean Voltage L2-N (Short)VRead
Mean Voltage L3-N (Short)VRead
Mean Voltage L1-L2 (Short)VRead
Mean Voltage L2-L3 (Short)VRead
Mean Voltage L3-L1 (Short)VRead
Mean Fundamental Power Factor, Cos Phi, UL1-N I1 (Short)Read
Mean Fundamental Power Factor, Cos Phi, UL2-N I2 (Short)Read
Mean Fundamental Power Factor, Cos Phi, UL3-N I3 (Short)Read
Mean Fundamental Power Factor Total (Short)Read
Mean Power Factor, UL1-N I1 (Short)Read
Mean Power Factor, UL2-N I2 (Short)Read
Mean Power Factor, UL3-N I3 (Short)Read
Mean Power Factor Total (Short)Read
Mean THD U L1-N (Short)%Read
Mean THD U L2-N (Short)%Read
Mean THD U L3-N (Short)%Read
Mean THD U L1-L2 (Short)%Read
Mean THD U L2-L3 (Short)%Read
Mean THD U L3-L1 (Short)%Read
Mean Real Part U L1-N (Short)VRead
Mean Real Part U L2-N (Short)VRead
Mean Real Part U L3-N (Short)VRead
Mean Imaginary Part U L1-N (Short)VRead
Mean Imaginary Part U L2-N (Short)VRead
Mean Imaginary Part U L3-N (Short)VRead
Mean Current I1 (Short)ARead
Mean Current I2 (Short)ARead
Mean Current I3 (Short)ARead
Mean Neutral Current Vector Sum (Short)ARead
Mean Real Power P L1-N (Short)WRead
Mean Real Power P L2-N (Short)WRead
Mean Real Power P L3-N (Short)WRead
Mean Real Power Total (Short)WRead
Mean Fundamental Reactive Power Q L1-N (Short)varRead
Mean Fundamental Reactive Power Q L2-N (Short)varRead
Mean Fundamental Reactive Power Q L3-N (Short)varRead
Mean Fundamental Reactive Power Total (Short)varRead
Mean Apparent Power S L1-N (Short)VARead
Mean Apparent Power S L2-N (Short)VARead
Mean Apparent Power S L3-N (Short)VARead
Mean Apparent Power Total (Short)VARead
Mean Fundamental Real Power P0 L1-N (Short)WRead
Mean Fundamental Real Power P0 L2-N (Short)WRead
Mean Fundamental Real Power P0 L3-N (Short)WRead
Mean Fundamental Power Factor Total (Short, W)Read
Mean Harmonic Distortion Power D L1-N (Short)varRead
Mean Harmonic Distortion Power D L2-N (Short)varRead
Mean Harmonic Distortion Power D L3-N (Short)varRead
Mean Distortion Power Total (Short)varRead
Mean THD I1 (Short)%Read
Mean THD I2 (Short)%Read
Mean THD I3 (Short)%Read
Mean TDD I1 (Short)%Read
Mean TDD I2 (Short)%Read
Mean TDD I3 (Short)%Read
Mean Current, Zero Sequence (Short)ARead
Mean Current, Negative Sequence (Short)ARead
Mean Current, Positive Sequence (Short)ARead
Mean Current, Real Part I L1 (Short)ARead
Mean Current, Real Part I L2 (Short)ARead
Mean Current, Real Part I L3 (Short)ARead
Mean Current, Imaginary Part I L1 (Short)ARead
Mean Current, Imaginary Part I L2 (Short)ARead
Mean Current, Imaginary Part I L3 (Short)ARead
Average Frequency 200 Ms, Integer (Short)HzRead
Max Mean Current I1ARead
Max Mean Current I2ARead
Max Mean Current I3ARead
Max Mean Neutral Current Vector SumARead
Max Mean Real Power P L1-NWRead
Max Mean Real Power P L2-NWRead
Max Mean Real Power P L3-NWRead
Max Mean Real Power TotalWRead
Max Mean Current I1 (Short)ARead
Max Mean Current I2 (Short)ARead
Max Mean Current I3 (Short)ARead
Max Mean Neutral Current Vector Sum (Short)ARead
Max Mean Real Power P L1-N (Short)WRead
Max Mean Real Power P L2-N (Short)WRead
Max Mean Real Power P L3-N (Short)WRead
Max Mean Real Power Total (Short)WRead
Min Measured Frequency 10secHzRead
Min Voltage, Zero SequenceVRead
Min Voltage, Negative SequenceVRead
Min Voltage, Positive SequenceVRead
Min Voltage L1-NVRead
Min Voltage L2-NVRead
Min Voltage L3-NVRead
Min Voltage L1-L2VRead
Min Voltage L2-L3VRead
Min Voltage L3-L1VRead
Min Fundamental Power Factor, Cos Phi, UL1-N I1Read
Min Fundamental Power Factor, Cos Phi, UL2-N I2Read
Min Fundamental Power Factor, Cos Phi, UL3-N I3Read
Min Fundamental Power Factor TotalRead
Min Power Factor, UL1-N I1Read
Min Power Factor, UL2-N I2Read
Min Power Factor, UL3-N I3Read
Min Power Factor TotalRead
Min THD U L1-N%Read
Min THD U L2-N%Read
Min THD U L3-N%Read
Min THD U L1-L2%Read
Min THD U L2-L3%Read
Min THD U L3-L1%Read
Min Voltage, Real Part U L1-NVRead
Min Voltage, Real Part U L2-NVRead
Min Voltage, Real Part U L3-NVRead
Min Voltage, Imaginary Part U L1-NVRead
Min Voltage, Imaginary Part U L2-NVRead
Min Voltage, Imaginary Part U L3-NVRead
Min Frequency 200 MsHzRead
Min Measured Frequency 10sec (Short)HzRead
Min Voltage, Zero Sequence (Short)Read
Min Voltage, Negative Sequence (Short)Read
Min Voltage, Positive Sequence (Short)Read
Min Voltage L1-N (Short)VRead
Min Voltage L2-N (Short)VRead
Min Voltage L3-N (Short)VRead
Min Voltage L1-L2 (Short)VRead
Min Voltage L2-L3 (Short)VRead
Min Voltage L3-L1 (Short)VRead
Min Fundamental Power Factor, Cos Phi, UL1-N I1 (Short)Read
Min Fundamental Power Factor, Cos Phi, UL2-N I2 (Short)Read
Min Fundamental Power Factor, Cos Phi, UL3-N I3 (Short)Read
Min Fundamental Power Factor Total (Short)Read
Min Power Factor, UL1-N I1 (Short)Read
Min Power Factor, UL2-N I2 (Short)Read
Min Power Factor, UL3-N I3 (Short)Read
Min Power Factor Total (Short)Read
Min THD U L1-N (Short)%Read
Min THD U L2-N (Short)%Read
Min THD U L3-N (Short)%Read
Min THD U L1-L2 (Short)%Read
Min THD U L2-L3 (Short)%Read
Min THD U L3-L1 (Short)%Read
Min Voltage, Real Part U L1-N (Short)VRead
Min Voltage, Real Part U L2-N (Short)VRead
Min Voltage, Real Part U L3-N (Short)VRead
Min Voltage, Imaginary Part U L1-N (Short)VRead
Min Voltage, Imaginary Part U L2-N (Short)VRead
Min Voltage, Imaginary Part U L3-N (Short)VRead
Min Frequency 200 Ms, Integer (Short)HzRead
Max Measured Frequency 10secHzRead
Max Voltage, Zero SequenceVRead
Max Voltage, Negative SequenceVRead
Max Voltage, Positive SequenceVRead
Max Voltage L1-NVRead
Max Voltage L2-NVRead
Max Voltage L3-NVRead
Max Voltage L1-L2VRead
Max Voltage L2-L3VRead
Max Voltage L3-L1VRead
Max Fundamental Power Factor, Cos Phi, UL1-N I1Read
Max Fundamental Power Factor, Cos Phi, UL2-N I2Read
Max Fundamental Power Factor, Cos Phi, UL3-N I3Read
Max Fundamental Power Factor TotalRead
Max Power Factor, UL1-N I1Read
Max Power Factor, UL2-N I2Read
Max Power Factor, UL3-N I3Read
Max Sum, Power Factor SumRead
Max THD, U L1-N%Read
Max THD, U L2-N%Read
Max THD, U L3-N%Read
Max THD, U L1-L2%Read
Max THD, U L2-L3%Read
Max THD, U L3-L1%Read
Max Voltage, Real Part U L1-NVRead
Max Voltage, Real Part U L2-NVRead
Max Voltage, Real Part U L3-NVRead
Max Voltage, Imaginary Part U L1-NVRead
Max Voltage, Imaginary Part U L2-NVRead
Max Voltage, Imaginary Part U L3-NVRead
Max Current I L1ARead
Max Current I L2ARead
Max Current I L3ARead
Max Neutral Current Vector SumARead
Max Real Power P L1-NWRead
Max Real Power P L2-NWRead
Max Real Power P L3-NWRead
Max Real Power TotalWRead
Max Fundamental Reactive Power Q L1-NvarRead
Max Fundamental Reactive Power Q L2-NvarRead
Max Fundamental Reactive Power Q L3-NvarRead
Max Fundamental Reactive Power TotalvarRead
Max Apparent Power S L1-NVARead
Max Apparent Power S L2-NVARead
Max Apparent Power S L3-NVARead
Max Apparent Power TotalVARead
Max Fundamental Real Power P0 L1-NWRead
Max Fundamental Real Power P0 L2-NWRead
Max Fundamental Real Power P0 L3-NWRead
Max Fundamental Real Power TotalWRead
Max Harmonic Distortion Power D L1-NvarRead
Max Harmonic Distortion Power D L2-NvarRead
Max Harmonic Distortion Power D L3-NvarRead
Max Distortion Power TotalvarRead
Max THD I1%Read
Max THD I2%Read
Max THD I3%Read
Max TDD I1%Read
Max TDD I2%Read
Max TDD I3%Read
Max Current, Zero SequenceARead
Max Current, Negative SequenceARead
Max Positive SequenceARead
Max Real Part I L1ARead
Max Real Part I L2ARead
Max Real Part I L3ARead
Max Imaginary Part I L1ARead
Max Imaginary Part I L2ARead
Max Imaginary Part I L3ARead
Max Frequency 200 MsHzRead
Max Measured Frequency 10sec (Short)HzRead
Max Voltage, Zero Sequence (Short)Read
Max Voltage, Negative Sequence (Short)Read
Max Voltage, Positive Sequence (Short)Read
Max Voltage L1-N (Short)VRead
Max Voltage L2-N (Short)VRead
Max Voltage L3-N (Short)VRead
Max Voltage L1-L2 (Short)VRead
Max Voltage L2-L3 (Short)VRead
Max Voltage L3-L1 (Short)VRead
Max Fundamental Power Factor, Cos Phi, UL1-N I1 (Short)Read
Max Fundamental Power Factor, Cos Phi, UL2-N I2 (Short)Read
Max Fundamental Power Factor, Cos Phi, UL3-N I3 (Short)Read
Max Fundamental Power Factor Total (Short)Read
Max Power Factor, UL1-N I1 (Short)Read
Max Power Factor, UL2-N I2 (Short)Read
Max Power Factor, UL3-N I3 (Short)Read
Max Power Factor Total (Short)Read
Max THD U L1-N (Short)%Read
Max THD U L2-N (Short)%Read
Max THD U L3-N (Short)%Read
Max THD U L1-L2 (Short)%Read
Max THD U L2-L3 (Short)%Read
Max THD U L3-L1 (Short)%Read
Max Real Part U L1-N (Short)VRead
Max Real Part U L2-N (Short)VRead
Max Real Part U L3-N (Short)VRead
Max Imaginary Part U L1-N (Short)VRead
Max Imaginary Part U L2-N (Short)VRead
Max Imaginary Part U L3-N (Short)VRead
Max Current I L1 (Short)ARead
Max Current I L2 (Short)ARead
Max Current I L3 (Short)ARead
Max Neutral Current Vector Sum (Short)ARead
Max Real Power P L1-N (Short)WRead
Max Real Power P L2-N (Short)WRead
Max Real Power P L3-N (Short)WRead
Max Real Power Total (Short)WRead
Max Fundamental Reactive Power Q L1-N (Short)varRead
Max Fundamental Reactive Power Q L2-N (Short)varRead
Max Fundamental Reactive Power Q L3-N (Short)varRead
Max Fundamental Reactive Power Total (Short)varRead
Max Apparent Power S L1-N (Short)VARead
Max Apparent Power S L2-N (Short)VARead
Max Apparent Power S L3-N (Short)VARead
Max Apparent Power Total (Short)VARead
Max Fundamental Real Power P0 L1-N (Short)WRead
Max Fundamental Real Power P0 L2-N (Short)WRead
Max Fundamental Real Power P0 L3-N (Short)WRead
Max Fundamental Real Power Total (Short)WRead
Max Harmonic Distortion Power D L1-N (Short)varRead
Max Harmonic Distortion Power D L2-N (Short)varRead
Max Harmonic Distortion Power D L3-N (Short)varRead
Max Distortion Power Total (Short)varRead
Max THD I1 (Short)%Read
Max THD I2 (Short)%Read
Max THD I3 (Short)%Read
Max TDD I1 (Short)%Read
Max TDD I2 (Short)%Read
Max TDD I3 (Short)%Read
Max Current, Zero Sequence (Short)ARead
Max Current, Negative Sequence (Short)ARead
Max Current, Positive Sequence (Short)ARead
Max Current, Real Part I1 (Short)ARead
Max Current, Real Part I2 (Short)ARead
Max Current, Real Part I3 (Short)ARead
Max Current, Imaginary Part I L1 (Short)ARead
Max Current, Imaginary Part I L2 (Short)ARead
Max Current, Imaginary Part I L3 (Short)ARead
Max Frequency 200 Ms, Integer (Short)HzRead
Current Transformer I1, PrimaryARead and write
Current Transformer I1, SecARead and write
Voltage Transformer V1, PrimaryVRead and write
Voltage Transformer V1, Sec.VRead and write
Current Transformer I2, PrimaryARead and write
Current Transformer I2, SecARead and write
Voltage Transformer V2, PrimaryVRead and write
Voltage Transformer V2, Sec.VRead and write
Current Transformer I3, PrimaryARead and write
Current Transformer I3, SecARead and write
Voltage Transformer V3, PrimaryVRead and write
Voltage Transformer V3, Sec.VRead and write
Frequency DeterminationHzRead and write
Display ContrastRead and write
Background LightingRead and write
Display ProfileRead and write
Display Change ProfileRead and write
Changeover Time for Measured Value DisplayssRead and write
Averaging Time, IRead and write
Averaging Time, PRead and write
Averaging Time, URead and write
Nominal Current TDDARead and write
Minimum Response CurrentmARead and write
PasswordRead and write
Results of the Comparator Group 1 Combine A, B, CRead and write
Comparator 1A, LimitRead and write
Comparator 1A, Address of Measurement ValueRead and write
Comparator 1A, Min. on TimesRead and write
Comparator 1A, Lead TimesRead and write
Comparator 1A, OperatorRead and write
Comparator 1B, LimitRead and write
Comparator 1B, Address of Measurement ValueRead and write
Comparator 1B, Min. on TimesRead and write
Comparator 1B, Lead TimesRead and write
Comparator 1B, OperatorRead and write
Comparator 1C, LimitRead and write
Comparator 1C, Address of Measurement ValueRead and write
Comparator 1C, Min. on TimesRead and write
Comparator 1C, Lead TimesRead and write
Comparator 1C, OperatorRead and write
Results of the Comparator Group 2 Combine A, B, CRead and write
Comparator 2A, LimitRead and write
Comparator 2A, Address of Measurement ValueRead and write
Comparator 2A, Min. on TimesRead and write
Comparator 2A, Lead TimesRead and write
Comparator 2A, OperatorRead and write
Comparator 2B, LimitRead and write
Comparator 2B, Address of Measurement ValueRead and write
Comparator 2B, Min. on TimesRead and write
Comparator 2B, Lead TimesRead and write
Comparator 2B, OperatorRead and write
Comparator 2C, LimitRead and write
Comparator 2C, Address of Measurement ValueRead and write
Comparator 2C, Min. on TimesRead and write
Comparator 2C, Lead TimesRead and write
Comparator 2C, OperatorRead and write
Connection Configuration, I L1Read and write
Connection Configuration, I L2Read and write
Connection Configuration, I L3Read and write
Connection Configuration, U L1Read and write
Connection Configuration, U L2Read and write
Connection Configuration, U L3Read and write
Delete Min. and Maximum ValuesRead and write
Delete Energy ValuesRead and write
Write in EEPROMRead and write
Connection Diagram VoltageRead and write
Connection Diagram CurrentRead and write
Voltages Used for THD and Harmonics on the DisplayRead and write
OverrangeRead
Comparator 1 Output ARead
Comparator 1 Output BRead
Comparator 1 Output CRead
Comparator 2 Output ARead
Comparator 2 Output BRead
Comparator 2 Output CRead
Linkage Result of Comparator Group 1Read
Linkage Result of Comparator Group 2Read
Tariff Settings, Real EnergyRead and write
Tariff Settings, Real Energy ConsumedRead and write
Tariff Settings, Real Energy DeliveredRead and write
Tariff Settings, Fundamental Reactive EnergyRead and write
Tariff Settings, Fundamental Reactive Energy Ind.Read and write
Tariff Settings, Fundamental Reactive Energy Cap.Read and write
Tariff Settings, Apparent EnergyRead and write
Firmware Release, Major VersionRead
Firmware Release, Minor VersionRead
Firmware Release, Patch VersionRead
Period After Which the Device Switches to StandbysRead and write
Background Lighting in Standby ModeRead and write
Serial NumberRead
Production NumberRead
MQTT Connection StatusRead
Error Code of Last MQTT ErrorRead
Device NameRead and write
Device DescriptionRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Build a dashboard per distribution board with voltage, current and power per phase.
  • Get an alarm when a phase voltage drops below a limit, so a blown fuse is noticed quickly.
  • Compare the currents of L1, L2 and L3 to find an unbalanced board.
  • Report monthly consumption and feed-in per board from the energy counters.
  • Track THD per phase to see the effect of drives, chargers and LED drivers.
  • Check the highest mean power of a board before you add a new load.

Installation

  1. Connect the RJ45 port of the meter to the network of the ModbusCloud Gateway, or directly to its LAN port.

  2. Give the meter a fixed IP address or a DHCP reservation, and set the current and voltage transformer ratios on the device.

  3. In ModbusCloud, add a Modbus TCP device with that IP address, port 502 and unit ID 1, and import this template.

  4. Check that the phase voltages show the mains voltage and the frequency is about 50 Hz.

Things to watch for

The UMG 96-EL does not answer. What should I check?

Check that the meter and the ModbusCloud Gateway are in the same network and that you can reach the IP address of the meter. Use port 502. If the meter gets its address by DHCP, it may have a new address after a restart; give it a fixed address or a DHCP reservation.

Why do the 16-bit values differ from the float values?

The 16-bit values do not include the current and voltage transformer ratio, the float values do. With transformers, use the float values or multiply the 16-bit value by the ratio yourself. Also set the transformer ratios correctly on the device.

Some values stay at zero. Is the template wrong?

Tariff counters stay at zero until a tariff is active, and minimum and maximum values start again after they are deleted. Below the minimum response current the meter shows zero current. Check the connection diagram settings if one phase stays at zero.

Can I write the energy counters and settings?

Yes. The float energy counters, transformer ratios, tariffs and comparators can be written. A write changes the meter right away and cannot be undone, so read the current value first and only write when you are sure. Wrong transformer ratios make every reading wrong.

Want to see how it works?

Electrician working in an open distribution board