Janitza UMG 96-EL
Energy analyser with Ethernet: voltage, current, power, energy and power quality per phase.
The Janitza UMG 96-EL is an energy analyser that measures voltage, current, power, energy and power quality per phase in main and sub-distribution boards. This Modbus TCP template reads all measured, mean, minimum and maximum values and energy per tariff, and lets you set transformer ratios, tariffs and comparators from ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 1123, read and write
- Brand
- Janitza
- Key readings
- Voltage · Current · Real power · Reactive and apparent power · Power factor · Frequency · Energy · THD
- Available commands
- Transformer ratios · Tariff settings · Comparator limits · Energy counter preset
- Compatible models
- UMG 96-EL 90-277V · UMG 96-EL 24-90V
- Last updated
Registers (1123)
1123 read, 303 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Voltage L1-N | V | Read | 19000 | FC03 | float32 |
| Voltage L2-N | V | Read | 19002 | FC03 | float32 |
| Voltage L3-N | V | Read | 19004 | FC03 | float32 |
| Voltage L1-L2 | V | Read | 19006 | FC03 | float32 |
| Voltage L2-L3 | V | Read | 19008 | FC03 | float32 |
| Voltage L3-L1 | V | Read | |||
| Current I L1 | A | Read | |||
| Current I L2 | A | Read | |||
| Current I L3 | A | Read | |||
| Neutral Current Vector Sum | A | Read | |||
| Real Power P1 L1N | W | Read | |||
| Real Power P2 L2N | W | Read | |||
| Real Power P3 L3N | W | Read | |||
| Real Power Total | W | Read | |||
| Apparent Power S1 L1N | VA | Read | |||
| Apparent Power S2 L2N | VA | Read | |||
| Apparent Power S3 L3N | VA | Read | |||
| Apparent Power Total | VA | Read | |||
| Fundamental Reactive Power Q1 L1N | var | Read | |||
| Fundamental Reactive Power Q2 L2N | var | Read | |||
| Fundamental Reactive Power Q3 L3N | var | Read | |||
| Fundamental Reactive Power Total | var | Read | |||
| Cos Phi, UL1 I1 | Read | ||||
| Cos Phi, UL2 I2 | Read | ||||
| Cos Phi, UL3 I3 | Read | ||||
| Measured Frequency 10sec | Hz | Read | |||
| Rotation Field | Read | ||||
| Real Energy L1 | Wh | Read | |||
| Real Energy L2 | Wh | Read | |||
| Real Energy L3 | Wh | Read | |||
| Real Energy L1-L3 | Wh | Read | |||
| Real Energy L1, Consumed | Wh | Read | |||
| Real Energy L2, Consumed | Wh | Read | |||
| Real Energy L3, Consumed | Wh | Read | |||
| Real Energy L1-L3, Consumed | Wh | Read | |||
| Real Energy L1, Delivered | Wh | Read | |||
| Real Energy L2, Delivered | Wh | Read | |||
| Real Energy L3, Delivered | Wh | Read | |||
| Real Energy L1-L3, Delivered | Wh | Read | |||
| Apparent Energy L1 | VAh | Read | |||
| Apparent Energy L2 | VAh | Read | |||
| Apparent Energy L3 | VAh | Read | |||
| Apparent Energy L1-L3 | VAh | Read | |||
| Fundamental Reactive Energy L1 | varh | Read | |||
| Fundamental Reactive Energy L2 | varh | Read | |||
| Fundamental Reactive Energy L3 | varh | Read | |||
| Fundamental Reactive Energy L1-L3 | varh | Read | |||
| Fundamental Reactive Energy Ind. L1 | varh | Read | |||
| Fundamental Reactive Energy Ind. L2 | varh | Read | |||
| Fundamental Reactive Energy Ind. L3 | varh | Read | |||
| Fundamental Reactive Energy Ind. L1-L3 | varh | Read | |||
| Fundamental Reactive Energy Cap. L1 | varh | Read | |||
| Fundamental Reactive Energy Cap. L2 | varh | Read | |||
| Fundamental Reactive Energy Cap. L3 | varh | Read | |||
| Fundamental Reactive Energy Cap. L1-L3 | varh | Read | |||
| THD, U L1-N | % | Read | |||
| THD, U L2-N | % | Read | |||
| THD, U L3-N | % | Read | |||
| THD, I1 | % | Read | |||
| THD, I2 | % | Read | |||
| THD, I3 | % | Read | |||
| Measured Frequency 10sec (Measured) | Hz | Read | |||
| Voltage, Zero Sequence | V | Read | |||
| Voltage, Negative Sequence | V | Read | |||
| Voltage, Positive Sequence | V | Read | |||
| Voltage U1 L1-N | V | Read | |||
| Voltage U2 L2-N | V | Read | |||
| Voltage U3 L3-N | V | Read | |||
| Voltage U1 L1-L2 | V | Read | |||
| Voltage U2 L2-L3 | V | Read | |||
| Voltage U3 L3-L1 | V | Read | |||
| Fundamental Power Factor, Cos Phi, ULN, I1 | Read | ||||
| Fundamental Power Factor, Cos Phi, ULN, I2 | Read | ||||
| Fundamental Power Factor, Cos Phi, ULN, I3 | Read | ||||
| Fundamental Power Factor Total | Read | ||||
| Power Factor, UL1N, I1 | Read | ||||
| Power Factor, UL2N, I2 | Read | ||||
| Power Factor, UL3N, I3 | Read | ||||
| Power Factor Total | Read | ||||
| THD, U L1N | % | Read | |||
| THD, U L2N | % | Read | |||
| THD, U L3N | % | Read | |||
| THD, U L1L2 | % | Read | |||
| THD, U L2L3 | % | Read | |||
| THD, U L3L1 | % | Read | |||
| Voltage, Real Part U1 L1-N | V | Read | |||
| Voltage, Real Part U2 L2-N | V | Read | |||
| Voltage, Real Part U3 L3-N | V | Read | |||
| Voltage, Imaginary Part U L1-N | V | Read | |||
| Voltage, Imaginary Part U L2-N | V | Read | |||
| Voltage, Imaginary Part U L3-N | V | Read | |||
| Current I1 L1 | A | Read | |||
| Current I2 L2 | A | Read | |||
| Current I3 L3 | A | Read | |||
| Neutral Current Vector Sum (Measured) | A | Read | |||
| Real Power P1 L1-N | W | Read | |||
| Real Power P2 L2-N | W | Read | |||
| Real Power P2 L3-N | W | Read | |||
| Real Power Total (Measured) | W | Read | |||
| Fundamental Reactive Power Q1 L1-N | var | Read | |||
| Fundamental Reactive Power Q2 L2-N | var | Read | |||
| Fundamental Reactive Power Q3 L3-N | var | Read | |||
| Fundamental Reactive Power Total (Measured) | var | Read | |||
| Apparent Power S1 L1-N | VA | Read | |||
| Apparent Power S2 L2-N | VA | Read | |||
| Apparent Power S3 L3-N | VA | Read | |||
| Apparent Power Total (Measured) | VA | Read | |||
| Fundamental Real Power P01 L1-N | W | Read | |||
| Fundamental Real Power P02 L2-N | W | Read | |||
| Fundamental Real Power P03 L3-N | W | Read | |||
| Fundamental Real Power Total | W | Read | |||
| Harmonic Distortion Power D1 L1-N | var | Read | |||
| Harmonic Distortion Power D2 L2-N | var | Read | |||
| Harmonic Distortion Power D3 L3-N | var | Read | |||
| Distortion Power Total | var | Read | |||
| THD, I1 (Measured) | % | Read | |||
| THD, I2 (Measured) | % | Read | |||
| THD, I3 (Measured) | % | Read | |||
| TDD I1, with Reference to Nominal Current | % | Read | |||
| TDD I2, with Reference to Nominal Current | % | Read | |||
| TDD I3, with Reference to Nominal Current | % | Read | |||
| Current, Zero Sequence | A | Read | |||
| Current, Negative Sequence | A | Read | |||
| Current, Positive Sequence | A | Read | |||
| Current, Real Part I L1 | A | Read | |||
| Current, Real Part I L2 | A | Read | |||
| Current, Real Part I L3 | A | Read | |||
| Current, Imaginary Part I L1 | A | Read | |||
| Current, Imaginary Part I L2 | A | Read | |||
| Current, Imaginary Part I L3 | A | Read | |||
| Rotation Field (Measured) | Read | ||||
| Frequency 200 Ms | Hz | Read | |||
| Crest Factor, U L1 | Read | ||||
| Crest Factor, U L2 | Read | ||||
| Crest Factor, U L3 | Read | ||||
| Crest Factor, I L1 | Read | ||||
| Crest Factor, I L2 | Read | ||||
| Crest Factor, I L3 | Read | ||||
| Measured Frequency 10sec (Short) | Hz | Read | |||
| Voltage, Zero Sequence (Short) | Read | ||||
| Voltage, Negative Sequence (Short) | Read | ||||
| Voltage, Positive Sequence (Short) | Read | ||||
| Voltage U1 L1-N (Short) | V | Read | |||
| Voltage U2 L2-N (Short) | V | Read | |||
| Voltage U3 L3-N (Short) | V | Read | |||
| Voltage U1 L1-L2 (Short) | V | Read | |||
| Voltage U2 L2-L3 (Short) | V | Read | |||
| Voltage U3 L3-L1 (Short) | V | Read | |||
| Fundamental Power Factor, Cos Phi, UL1-N I1 (Short) | Read | ||||
| Fundamental Power Factor, Cos Phi, UL2-N I2 (Short) | Read | ||||
| Fundamental Power Factor, Cos Phi, UL3-N I3 (Short) | Read | ||||
| Fundamental Power Factor Total (Short) | Read | ||||
| Power Factor, UL1-N I1 (Short) | Read | ||||
| Power Factor, UL2-N I2 (Short) | Read | ||||
| Power Factor, UL3-N I3 (Short) | Read | ||||
| Power Factor Total (Short) | Read | ||||
| THD, U L1-N (Short) | % | Read | |||
| THD, U L2-N (Short) | % | Read | |||
| THD, U L3-N (Short) | % | Read | |||
| THD, U L1-L2 (Short) | % | Read | |||
| THD, U L2-L3 (Short) | % | Read | |||
| THD, U L3-L1 (Short) | % | Read | |||
| Voltage, Real Part U L1-N (Short) | V | Read | |||
| Voltage, Real Part U L2-N (Short) | V | Read | |||
| Voltage, Real Part U L3-N (Short) | V | Read | |||
| Voltage, Imaginary Part U L1-N (Short) | V | Read | |||
| Voltage, Imaginary Part U L2-N (Short) | V | Read | |||
| Voltage, Imaginary Part U L3-N (Short) | V | Read | |||
| Current I L1 (Short) | A | Read | |||
| Current I L2 (Short) | A | Read | |||
| Current I L3 (Short) | A | Read | |||
| Neutral Current Vector Sum (Short) | A | Read | |||
| Real Power P L1-N (Short) | W | Read | |||
| Real Power P L2-N (Short) | W | Read | |||
| Real Power P L3-N (Short) | W | Read | |||
| Real Power Total (Short) | W | Read | |||
| Fundamental Reactive Power Q L1-N (Short) | var | Read | |||
| Fundamental Reactive Power Q L2-N (Short) | var | Read | |||
| Fundamental Reactive Power Q L3-N (Short) | var | Read | |||
| Fundamental Reactive Power Total (Short) | var | Read | |||
| Apparent Power S L1-N (Short) | VA | Read | |||
| Apparent Power S L2-N (Short) | VA | Read | |||
| Apparent Power S L3-N (Short) | VA | Read | |||
| Apparent Power Total (Short) | VA | Read | |||
| Fundamental Real Power P0 L1-N (Short) | W | Read | |||
| Fundamental Real Power P0 L2-N (Short) | W | Read | |||
| Fundamental Real Power P0 L3-N (Short) | W | Read | |||
| Fundamental Power Factor Total (Short, W) | Read | ||||
| Harmonic Distortion Power D L1-N (Short) | var | Read | |||
| Harmonic Distortion Power D L2-N (Short) | var | Read | |||
| Harmonic Distortion Power D L3-N (Short) | var | Read | |||
| Distortion Power Total (Short) | var | Read | |||
| THD, I1 (Short) | % | Read | |||
| THD, I2 (Short) | % | Read | |||
| THD, I3 (Short) | % | Read | |||
| TDD I1 (Short) | % | Read | |||
| TDD I2 (Short) | % | Read | |||
| TDD I3 (Short) | % | Read | |||
| Current, Zero Sequence (Short) | A | Read | |||
| Current, Negative Sequence (Short) | A | Read | |||
| Current, Positive Sequence (Short) | A | Read | |||
| Current, Real Part I L1 (Short) | A | Read | |||
| Current, Real Part I L2 (Short) | A | Read | |||
| Current, Real Part I L3 (Short) | A | Read | |||
| Current, Imaginary Part I L1 (Short) | A | Read | |||
| Current, Imaginary Part I L2 (Short) | A | Read | |||
| Current, Imaginary Part I L3 (Short) | A | Read | |||
| Rotation Field (Short) | Read | ||||
| Frequency 200 Ms, Integer (Short) | Hz | Read | |||
| Real Energy, L1 | Wh | Read and write | |||
| Real Energy, L1, Tariff 1 | Wh | Read and write | |||
| Real Energy, L1, Tariff 2 | Wh | Read and write | |||
| Real Energy, L1, Tariff 3 | Wh | Read and write | |||
| Real Energy, L1, Tariff 4 | Wh | Read and write | |||
| Real Energy, L1, Tariff 5 | Wh | Read and write | |||
| Real Energy, L1, Tariff 6 | Wh | Read and write | |||
| Real Energy, L1, Tariff 7 | Wh | Read and write | |||
| Real Energy, L1, Consumed | Wh | Read and write | |||
| Real Energy, L1, Consumed, Tariff 1 | Wh | Read and write | |||
| Real Energy, L1, Consumed, Tariff 2 | Wh | Read and write | |||
| Real Energy, L1, Consumed, Tariff 3 | Wh | Read and write | |||
| Real Energy, L1, Consumed, Tariff 4 | Wh | Read and write | |||
| Real Energy, L1, Consumed, Tariff 5 | Wh | Read and write | |||
| Real Energy, L1, Consumed, Tariff 6 | Wh | Read and write | |||
| Real Energy, L1, Consumed, Tariff 7 | Wh | Read and write | |||
| Real Energy, L1, Delivered | Wh | Read and write | |||
| Real Energy, L1, Delivered, Tariff 1 | Wh | Read and write | |||
| Real Energy, L1, Delivered, Tariff 2 | Wh | Read and write | |||
| Real Energy, L1, Delivered, Tariff 3 | Wh | Read and write | |||
| Real Energy, L1, Delivered, Tariff 4 | Wh | Read and write | |||
| Real Energy, L1, Delivered, Tariff 5 | Wh | Read and write | |||
| Real Energy, L1, Delivered, Tariff 6 | Wh | Read and write | |||
| Real Energy, L1, Delivered, Tariff 7 | Wh | Read and write | |||
| Fundamental Reactive Energy, L1 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind. | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap. | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 7 | varh | Read and write | |||
| Apparent Energy, L1 | VAh | Read and write | |||
| Apparent Energy, L1, Tariff 1 | VAh | Read and write | |||
| Apparent Energy, L1, Tariff 2 | VAh | Read and write | |||
| Apparent Energy, L1, Tariff 3 | VAh | Read and write | |||
| Apparent Energy, L1, Tariff 4 | VAh | Read and write | |||
| Apparent Energy, L1, Tariff 5 | VAh | Read and write | |||
| Apparent Energy, L1, Tariff 6 | VAh | Read and write | |||
| Apparent Energy, L1, Tariff 7 | VAh | Read and write | |||
| Real Energy, L2 | Wh | Read and write | |||
| Real Energy, L2, Tariff 1 | Wh | Read and write | |||
| Real Energy, L2, Tariff 2 | Wh | Read and write | |||
| Real Energy, L2, Tariff 3 | Wh | Read and write | |||
| Real Energy, L2, Tariff 4 | Wh | Read and write | |||
| Real Energy, L2, Tariff 5 | Wh | Read and write | |||
| Real Energy, L2, Tariff 6 | Wh | Read and write | |||
| Real Energy, L2, Tariff 7 | Wh | Read and write | |||
| Real Energy, L2, Consumed | Wh | Read and write | |||
| Real Energy, L2, Consumed, Tariff 1 | Wh | Read and write | |||
| Real Energy, L2, Consumed, Tariff 2 | Wh | Read and write | |||
| Real Energy, L2, Consumed, Tariff 3 | Wh | Read and write | |||
| Real Energy, L2, Consumed, Tariff 4 | Wh | Read and write | |||
| Real Energy, L2, Consumed, Tariff 5 | Wh | Read and write | |||
| Real Energy, L2, Consumed, Tariff 6 | Wh | Read and write | |||
| Real Energy, L2, Consumed, Tariff 7 | Wh | Read and write | |||
| Real Energy, L2, Delivered | Wh | Read and write | |||
| Real Energy, L2, Delivered, Tariff 1 | Wh | Read and write | |||
| Real Energy, L2, Delivered, Tariff 2 | Wh | Read and write | |||
| Real Energy, L2, Delivered, Tariff 3 | Wh | Read and write | |||
| Real Energy, L2, Delivered, Tariff 4 | Wh | Read and write | |||
| Real Energy, L2, Delivered, Tariff 5 | Wh | Read and write | |||
| Real Energy, L2, Delivered, Tariff 6 | Wh | Read and write | |||
| Real Energy, L2, Delivered, Tariff 7 | Wh | Read and write | |||
| Fundamental Reactive Energy, L2 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind. | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap. | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 7 | varh | Read and write | |||
| Apparent Energy, L2 | VAh | Read and write | |||
| Apparent Energy, L2, Tariff 1 | VAh | Read and write | |||
| Apparent Energy, L2, Tariff 2 | VAh | Read and write | |||
| Apparent Energy, L2, Tariff 3 | VAh | Read and write | |||
| Apparent Energy, L2, Tariff 4 | VAh | Read and write | |||
| Apparent Energy, L2, Tariff 5 | VAh | Read and write | |||
| Apparent Energy, L2, Tariff 6 | VAh | Read and write | |||
| Apparent Energy, L2, Tariff 7 | VAh | Read and write | |||
| Real Energy, L3 | Wh | Read and write | |||
| Real Energy, L3, Tariff 1 | Wh | Read and write | |||
| Real Energy, L3, Tariff 2 | Wh | Read and write | |||
| Real Energy, L3, Tariff 3 | Wh | Read and write | |||
| Real Energy, L3, Tariff 4 | Wh | Read and write | |||
| Real Energy, L3, Tariff 5 | Wh | Read and write | |||
| Real Energy, L3, Tariff 6 | Wh | Read and write | |||
| Real Energy, L3, Tariff 7 | Wh | Read and write | |||
| Real Energy, L3, Consumed | Wh | Read and write | |||
| Real Energy, L3, Consumed, Tariff 1 | Wh | Read and write | |||
| Real Energy, L3, Consumed, Tariff 2 | Wh | Read and write | |||
| Real Energy, L3, Consumed, Tariff 3 | Wh | Read and write | |||
| Real Energy, L3, Consumed, Tariff 4 | Wh | Read and write | |||
| Real Energy, L3, Consumed, Tariff 5 | Wh | Read and write | |||
| Real Energy, L3, Consumed, Tariff 6 | Wh | Read and write | |||
| Real Energy, L3, Consumed, Tariff 7 | Wh | Read and write | |||
| Real Energy, L3, Delivered | Wh | Read and write | |||
| Real Energy, L3, Delivered, Tariff 1 | Wh | Read and write | |||
| Real Energy, L3, Delivered, Tariff 2 | Wh | Read and write | |||
| Real Energy, L3, Delivered, Tariff 3 | Wh | Read and write | |||
| Real Energy, L3, Delivered, Tariff 4 | Wh | Read and write | |||
| Real Energy, L3, Delivered, Tariff 5 | Wh | Read and write | |||
| Real Energy, L3, Delivered, Tariff 6 | Wh | Read and write | |||
| Real Energy, L3, Delivered, Tariff 7 | Wh | Read and write | |||
| Fundamental Reactive Energy, L3 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind. | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap. | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 7 | varh | Read and write | |||
| Apparent Energy, L3 | VAh | Read and write | |||
| Apparent Energy, L3, Tariff 1 | VAh | Read and write | |||
| Apparent Energy, L3, Tariff 2 | VAh | Read and write | |||
| Apparent Energy, L3, Tariff 3 | VAh | Read and write | |||
| Apparent Energy, L3, Tariff 4 | VAh | Read and write | |||
| Apparent Energy, L3, Tariff 5 | VAh | Read and write | |||
| Apparent Energy, L3, Tariff 6 | VAh | Read and write | |||
| Apparent Energy, L3, Tariff 7 | VAh | Read and write | |||
| Real Energy, Sum L1-L3 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Tariff 1 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Tariff 2 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Tariff 3 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Tariff 4 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Tariff 5 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Tariff 6 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Tariff 7 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 1 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 2 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 3 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 4 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 5 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 6 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 7 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 1 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 2 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 3 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 4 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 5 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 6 | Wh | Read and write | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 7 | Wh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind. | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 7 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap. | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 1 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 2 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 3 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 4 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 5 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 6 | varh | Read and write | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 7 | varh | Read and write | |||
| Apparent Energy, Sum L1-L3 | VAh | Read and write | |||
| Apparent Energy, Sum L1-L3, Tariff 1 | VAh | Read and write | |||
| Apparent Energy, Sum L1-L3, Tariff 2 | VAh | Read and write | |||
| Apparent Energy, Sum L1-L3, Tariff 3 | VAh | Read and write | |||
| Apparent Energy, Sum L1-L3, Tariff 4 | VAh | Read and write | |||
| Apparent Energy, Sum L1-L3, Tariff 5 | VAh | Read and write | |||
| Apparent Energy, Sum L1-L3, Tariff 6 | VAh | Read and write | |||
| Apparent Energy, Sum L1-L3, Tariff 7 | VAh | Read and write | |||
| Real Energy, L1 (Int) | Wh | Read | |||
| Real Energy, L1, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L1, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L1, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L1, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L1, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L1, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L1, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, L1, Consumed (Int) | Wh | Read | |||
| Real Energy, L1, Consumed, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L1, Consumed, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L1, Consumed, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L1, Consumed, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L1, Consumed, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L1, Consumed, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L1, Consumed, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, L1, Delivered (Int) | Wh | Read | |||
| Real Energy, L1, Delivered, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L1, Delivered, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L1, Delivered, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L1, Delivered, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L1, Delivered, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L1, Delivered, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L1, Delivered, Tariff 7 (Int) | Wh | Read | |||
| Fundamental Reactive Energy, L1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind. (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Ind., Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap. (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L1, Cap., Tariff 7 (Int) | varh | Read | |||
| Apparent Energy, L1 (Int) | VAh | Read | |||
| Apparent Energy, L1, Tariff 1 (Int) | VAh | Read | |||
| Apparent Energy, L1, Tariff 2 (Int) | VAh | Read | |||
| Apparent Energy, L1, Tariff 3 (Int) | VAh | Read | |||
| Apparent Energy, L1, Tariff 4 (Int) | VAh | Read | |||
| Apparent Energy, L1, Tariff 5 (Int) | VAh | Read | |||
| Apparent Energy, L1, Tariff 6 (Int) | VAh | Read | |||
| Apparent Energy, L1, Tariff 7 (Int) | VAh | Read | |||
| Real Energy, L2 (Int) | Wh | Read | |||
| Real Energy, L2, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L2, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L2, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L2, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L2, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L2, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L2, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, L2, Consumed (Int) | Wh | Read | |||
| Real Energy, L2, Consumed, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L2, Consumed, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L2, Consumed, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L2, Consumed, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L2, Consumed, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L2, Consumed, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L2, Consumed, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, L2, Delivered (Int) | Wh | Read | |||
| Real Energy, L2, Delivered, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L2, Delivered, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L2, Delivered, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L2, Delivered, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L2, Delivered, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L2, Delivered, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L2, Delivered, Tariff 7 (Int) | Wh | Read | |||
| Fundamental Reactive Energy, L2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind. (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Ind., Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap. (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L2, Cap., Tariff 7 (Int) | varh | Read | |||
| Apparent Energy, L2 (Int) | VAh | Read | |||
| Apparent Energy, L2, Tariff 1 (Int) | VAh | Read | |||
| Apparent Energy, L2, Tariff 2 (Int) | VAh | Read | |||
| Apparent Energy, L2, Tariff 3 (Int) | VAh | Read | |||
| Apparent Energy, L2, Tariff 4 (Int) | VAh | Read | |||
| Apparent Energy, L2, Tariff 5 (Int) | VAh | Read | |||
| Apparent Energy, L2, Tariff 6 (Int) | VAh | Read | |||
| Apparent Energy, L2, Tariff 7 (Int) | VAh | Read | |||
| Real Energy, L3 (Int) | Wh | Read | |||
| Real Energy, L3, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L3, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L3, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L3, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L3, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L3, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L3, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, L3, Consumed (Int) | Wh | Read | |||
| Real Energy, L3, Consumed, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L3, Consumed, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L3, Consumed, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L3, Consumed, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L3, Consumed, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L3, Consumed, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L3, Consumed, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, L3, Delivered (Int) | Wh | Read | |||
| Real Energy, L3, Delivered, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, L3, Delivered, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, L3, Delivered, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, L3, Delivered, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, L3, Delivered, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, L3, Delivered, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, L3, Delivered, Tariff 7 (Int) | Wh | Read | |||
| Fundamental Reactive Energy, L3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind. (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Ind., Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap. (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, L3, Cap., Tariff 7 (Int) | varh | Read | |||
| Apparent Energy, L3 (Int) | VAh | Read | |||
| Apparent Energy, L3, Tariff 1 (Int) | VAh | Read | |||
| Apparent Energy, L3, Tariff 2 (Int) | VAh | Read | |||
| Apparent Energy, L3, Tariff 3 (Int) | VAh | Read | |||
| Apparent Energy, L3, Tariff 4 (Int) | VAh | Read | |||
| Apparent Energy, L3, Tariff 5 (Int) | VAh | Read | |||
| Apparent Energy, L3, Tariff 6 (Int) | VAh | Read | |||
| Apparent Energy, L3, Tariff 7 (Int) | VAh | Read | |||
| Real Energy, Sum L1-L3 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Consumed, Tariff 7 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 1 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 2 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 3 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 4 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 5 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 6 (Int) | Wh | Read | |||
| Real Energy, Sum L1-L3, Delivered, Tariff 7 (Int) | Wh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind. (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Ind., Tariff 7 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap. (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 1 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 2 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 3 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 4 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 5 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 6 (Int) | varh | Read | |||
| Fundamental Reactive Energy, Sum L1-L3, Cap., Tariff 7 (Int) | varh | Read | |||
| Apparent Energy, Sum L1-L3 (Int) | VAh | Read | |||
| Apparent Energy, Sum L1-L3, Tariff 1 (Int) | VAh | Read | |||
| Apparent Energy, Sum L1-L3, Tariff 2 (Int) | VAh | Read | |||
| Apparent Energy, Sum L1-L3, Tariff 3 (Int) | VAh | Read | |||
| Apparent Energy, Sum L1-L3, Tariff 4 (Int) | VAh | Read | |||
| Apparent Energy, Sum L1-L3, Tariff 5 (Int) | VAh | Read | |||
| Apparent Energy, Sum L1-L3, Tariff 6 (Int) | VAh | Read | |||
| Apparent Energy, Sum L1-L3, Tariff 7 (Int) | VAh | Read | |||
| Operation Hours Meter (Int) | s | Read | |||
| Comparator Running Time 1 | s | Read | |||
| Comparator Running Time 2 | s | Read | |||
| Comparator Running Time 3 | s | Read | |||
| Comparator Running Time 4 | s | Read | |||
| Comparator Running Time 5 | s | Read | |||
| Comparator Running Time 6 | s | Read | |||
| Mean Measured Frequency 10sec | Hz | Read | |||
| Mean Voltage, Zero Sequence | V | Read | |||
| Mean Voltage, Negative Sequence | V | Read | |||
| Mean Voltage, Positive Sequence | V | Read | |||
| Mean Voltage L1-N | V | Read | |||
| Mean Voltage L2-N | V | Read | |||
| Mean Voltage L3-N | V | Read | |||
| Mean Voltage L1-L2 | V | Read | |||
| Mean Voltage L2-L3 | V | Read | |||
| Mean Voltage L3-L1 | V | Read | |||
| Mean Fundamental Power Factor, Cos Phi, UL1-N I1 | Read | ||||
| Mean Fundamental Power Factor, Cos Phi, UL2-N I2 | Read | ||||
| Mean Fundamental Power Factor, Cos Phi, UL3-N I3 | Read | ||||
| Mean Fundamental Power Factor Total | Read | ||||
| Mean Power Factor, UL1-N I1 | Read | ||||
| Mean Power Factor, UL2-N I2 | Read | ||||
| Mean Power Factor, UL3-N I3 | Read | ||||
| Mean Power Factor Total | Read | ||||
| Mean THD, U L1-N | % | Read | |||
| Mean THD, U L2-N | % | Read | |||
| Mean THD, U L3-N | % | Read | |||
| Mean THD, U L1-L2 | % | Read | |||
| Mean THD, U L2-L3 | % | Read | |||
| Mean THD, U L3-L1 | % | Read | |||
| Mean Voltage, Real Part U L1-N | V | Read | |||
| Mean Voltage, Real Part U L2-N | V | Read | |||
| Mean Voltage, Real Part U L3-N | V | Read | |||
| Mean Voltage, Imaginary Part U L1-N | V | Read | |||
| Mean Voltage, Imaginary Part U L2-N | V | Read | |||
| Mean Voltage, Imaginary Part U L3-N | V | Read | |||
| Mean Current I1 | A | Read | |||
| Mean Current I2 | A | Read | |||
| Mean Current I3 | A | Read | |||
| Mean Neutral Current Vector Sum | A | Read | |||
| Mean Real Power P L1-N | W | Read | |||
| Mean Real Power P L2-N | W | Read | |||
| Mean Real Power P L3-N | W | Read | |||
| Mean Real Power Total | W | Read | |||
| Mean Fundamental Reactive Power Q L1-N | var | Read | |||
| Mean Fundamental Reactive Power Q L2-N | var | Read | |||
| Mean Fundamental Reactive Power Q L3-N | var | Read | |||
| Mean Fundamental Reactive Power Total | var | Read | |||
| Mean Apparent Power S L1-N | VA | Read | |||
| Mean Apparent Power S L2-N | VA | Read | |||
| Mean Apparent Power S L3-N | VA | Read | |||
| Mean Apparent Power Total | VA | Read | |||
| Mean Fundamental Real Power P0 L1-N | W | Read | |||
| Mean Fundamental Real Power P0 L2-N | W | Read | |||
| Mean Fundamental Real Power P0 L3-N | W | Read | |||
| Mean Fundamental Real Power Total | W | Read | |||
| Mean Harmonic Distortion Power D L1-N | var | Read | |||
| Mean Harmonic Distortion Power D L2-N | var | Read | |||
| Mean Harmonic Distortion Power D L3-N | var | Read | |||
| Mean Distortion Power Total | var | Read | |||
| Mean THD I1 | % | Read | |||
| Mean THD I2 | % | Read | |||
| Mean THD I3 | % | Read | |||
| Mean TDD I1 | % | Read | |||
| Mean TDD I2 | % | Read | |||
| Mean TDD I3 | % | Read | |||
| Mean Current, Zero Sequence | A | Read | |||
| Mean Current, Negative Sequence | A | Read | |||
| Mean Current, Positive Sequence | A | Read | |||
| Mean Current, Real Part I L1 | A | Read | |||
| Mean Current, Real Part I L2 | A | Read | |||
| Mean Current, Real Part I L3 | A | Read | |||
| Mean Current, Imaginary Part I1 | A | Read | |||
| Mean Current, Imaginary Part I2 | A | Read | |||
| Mean Current, Imaginary Part I3 | A | Read | |||
| Average Frequency 200 Ms | Hz | Read | |||
| Mean Crest Factor, U L1 | Read | ||||
| Mean Crest Factor, U L2 | Read | ||||
| Mean Crest Factor, U L3 | Read | ||||
| Mean Crest Factor, I L1 | Read | ||||
| Mean Crest Factor, I L2 | Read | ||||
| Mean Crest Factor, I L3 | Read | ||||
| Mean Measured Frequency 10sec (Short) | Hz | Read | |||
| Mean Voltage, Zero Sequence (Short) | Read | ||||
| Mean Voltage, Negative Sequence (Short) | Read | ||||
| Mean Voltage, Positive Sequence (Short) | Read | ||||
| Mean Voltage L1-N (Short) | V | Read | |||
| Mean Voltage L2-N (Short) | V | Read | |||
| Mean Voltage L3-N (Short) | V | Read | |||
| Mean Voltage L1-L2 (Short) | V | Read | |||
| Mean Voltage L2-L3 (Short) | V | Read | |||
| Mean Voltage L3-L1 (Short) | V | Read | |||
| Mean Fundamental Power Factor, Cos Phi, UL1-N I1 (Short) | Read | ||||
| Mean Fundamental Power Factor, Cos Phi, UL2-N I2 (Short) | Read | ||||
| Mean Fundamental Power Factor, Cos Phi, UL3-N I3 (Short) | Read | ||||
| Mean Fundamental Power Factor Total (Short) | Read | ||||
| Mean Power Factor, UL1-N I1 (Short) | Read | ||||
| Mean Power Factor, UL2-N I2 (Short) | Read | ||||
| Mean Power Factor, UL3-N I3 (Short) | Read | ||||
| Mean Power Factor Total (Short) | Read | ||||
| Mean THD U L1-N (Short) | % | Read | |||
| Mean THD U L2-N (Short) | % | Read | |||
| Mean THD U L3-N (Short) | % | Read | |||
| Mean THD U L1-L2 (Short) | % | Read | |||
| Mean THD U L2-L3 (Short) | % | Read | |||
| Mean THD U L3-L1 (Short) | % | Read | |||
| Mean Real Part U L1-N (Short) | V | Read | |||
| Mean Real Part U L2-N (Short) | V | Read | |||
| Mean Real Part U L3-N (Short) | V | Read | |||
| Mean Imaginary Part U L1-N (Short) | V | Read | |||
| Mean Imaginary Part U L2-N (Short) | V | Read | |||
| Mean Imaginary Part U L3-N (Short) | V | Read | |||
| Mean Current I1 (Short) | A | Read | |||
| Mean Current I2 (Short) | A | Read | |||
| Mean Current I3 (Short) | A | Read | |||
| Mean Neutral Current Vector Sum (Short) | A | Read | |||
| Mean Real Power P L1-N (Short) | W | Read | |||
| Mean Real Power P L2-N (Short) | W | Read | |||
| Mean Real Power P L3-N (Short) | W | Read | |||
| Mean Real Power Total (Short) | W | Read | |||
| Mean Fundamental Reactive Power Q L1-N (Short) | var | Read | |||
| Mean Fundamental Reactive Power Q L2-N (Short) | var | Read | |||
| Mean Fundamental Reactive Power Q L3-N (Short) | var | Read | |||
| Mean Fundamental Reactive Power Total (Short) | var | Read | |||
| Mean Apparent Power S L1-N (Short) | VA | Read | |||
| Mean Apparent Power S L2-N (Short) | VA | Read | |||
| Mean Apparent Power S L3-N (Short) | VA | Read | |||
| Mean Apparent Power Total (Short) | VA | Read | |||
| Mean Fundamental Real Power P0 L1-N (Short) | W | Read | |||
| Mean Fundamental Real Power P0 L2-N (Short) | W | Read | |||
| Mean Fundamental Real Power P0 L3-N (Short) | W | Read | |||
| Mean Fundamental Power Factor Total (Short, W) | Read | ||||
| Mean Harmonic Distortion Power D L1-N (Short) | var | Read | |||
| Mean Harmonic Distortion Power D L2-N (Short) | var | Read | |||
| Mean Harmonic Distortion Power D L3-N (Short) | var | Read | |||
| Mean Distortion Power Total (Short) | var | Read | |||
| Mean THD I1 (Short) | % | Read | |||
| Mean THD I2 (Short) | % | Read | |||
| Mean THD I3 (Short) | % | Read | |||
| Mean TDD I1 (Short) | % | Read | |||
| Mean TDD I2 (Short) | % | Read | |||
| Mean TDD I3 (Short) | % | Read | |||
| Mean Current, Zero Sequence (Short) | A | Read | |||
| Mean Current, Negative Sequence (Short) | A | Read | |||
| Mean Current, Positive Sequence (Short) | A | Read | |||
| Mean Current, Real Part I L1 (Short) | A | Read | |||
| Mean Current, Real Part I L2 (Short) | A | Read | |||
| Mean Current, Real Part I L3 (Short) | A | Read | |||
| Mean Current, Imaginary Part I L1 (Short) | A | Read | |||
| Mean Current, Imaginary Part I L2 (Short) | A | Read | |||
| Mean Current, Imaginary Part I L3 (Short) | A | Read | |||
| Average Frequency 200 Ms, Integer (Short) | Hz | Read | |||
| Max Mean Current I1 | A | Read | |||
| Max Mean Current I2 | A | Read | |||
| Max Mean Current I3 | A | Read | |||
| Max Mean Neutral Current Vector Sum | A | Read | |||
| Max Mean Real Power P L1-N | W | Read | |||
| Max Mean Real Power P L2-N | W | Read | |||
| Max Mean Real Power P L3-N | W | Read | |||
| Max Mean Real Power Total | W | Read | |||
| Max Mean Current I1 (Short) | A | Read | |||
| Max Mean Current I2 (Short) | A | Read | |||
| Max Mean Current I3 (Short) | A | Read | |||
| Max Mean Neutral Current Vector Sum (Short) | A | Read | |||
| Max Mean Real Power P L1-N (Short) | W | Read | |||
| Max Mean Real Power P L2-N (Short) | W | Read | |||
| Max Mean Real Power P L3-N (Short) | W | Read | |||
| Max Mean Real Power Total (Short) | W | Read | |||
| Min Measured Frequency 10sec | Hz | Read | |||
| Min Voltage, Zero Sequence | V | Read | |||
| Min Voltage, Negative Sequence | V | Read | |||
| Min Voltage, Positive Sequence | V | Read | |||
| Min Voltage L1-N | V | Read | |||
| Min Voltage L2-N | V | Read | |||
| Min Voltage L3-N | V | Read | |||
| Min Voltage L1-L2 | V | Read | |||
| Min Voltage L2-L3 | V | Read | |||
| Min Voltage L3-L1 | V | Read | |||
| Min Fundamental Power Factor, Cos Phi, UL1-N I1 | Read | ||||
| Min Fundamental Power Factor, Cos Phi, UL2-N I2 | Read | ||||
| Min Fundamental Power Factor, Cos Phi, UL3-N I3 | Read | ||||
| Min Fundamental Power Factor Total | Read | ||||
| Min Power Factor, UL1-N I1 | Read | ||||
| Min Power Factor, UL2-N I2 | Read | ||||
| Min Power Factor, UL3-N I3 | Read | ||||
| Min Power Factor Total | Read | ||||
| Min THD U L1-N | % | Read | |||
| Min THD U L2-N | % | Read | |||
| Min THD U L3-N | % | Read | |||
| Min THD U L1-L2 | % | Read | |||
| Min THD U L2-L3 | % | Read | |||
| Min THD U L3-L1 | % | Read | |||
| Min Voltage, Real Part U L1-N | V | Read | |||
| Min Voltage, Real Part U L2-N | V | Read | |||
| Min Voltage, Real Part U L3-N | V | Read | |||
| Min Voltage, Imaginary Part U L1-N | V | Read | |||
| Min Voltage, Imaginary Part U L2-N | V | Read | |||
| Min Voltage, Imaginary Part U L3-N | V | Read | |||
| Min Frequency 200 Ms | Hz | Read | |||
| Min Measured Frequency 10sec (Short) | Hz | Read | |||
| Min Voltage, Zero Sequence (Short) | Read | ||||
| Min Voltage, Negative Sequence (Short) | Read | ||||
| Min Voltage, Positive Sequence (Short) | Read | ||||
| Min Voltage L1-N (Short) | V | Read | |||
| Min Voltage L2-N (Short) | V | Read | |||
| Min Voltage L3-N (Short) | V | Read | |||
| Min Voltage L1-L2 (Short) | V | Read | |||
| Min Voltage L2-L3 (Short) | V | Read | |||
| Min Voltage L3-L1 (Short) | V | Read | |||
| Min Fundamental Power Factor, Cos Phi, UL1-N I1 (Short) | Read | ||||
| Min Fundamental Power Factor, Cos Phi, UL2-N I2 (Short) | Read | ||||
| Min Fundamental Power Factor, Cos Phi, UL3-N I3 (Short) | Read | ||||
| Min Fundamental Power Factor Total (Short) | Read | ||||
| Min Power Factor, UL1-N I1 (Short) | Read | ||||
| Min Power Factor, UL2-N I2 (Short) | Read | ||||
| Min Power Factor, UL3-N I3 (Short) | Read | ||||
| Min Power Factor Total (Short) | Read | ||||
| Min THD U L1-N (Short) | % | Read | |||
| Min THD U L2-N (Short) | % | Read | |||
| Min THD U L3-N (Short) | % | Read | |||
| Min THD U L1-L2 (Short) | % | Read | |||
| Min THD U L2-L3 (Short) | % | Read | |||
| Min THD U L3-L1 (Short) | % | Read | |||
| Min Voltage, Real Part U L1-N (Short) | V | Read | |||
| Min Voltage, Real Part U L2-N (Short) | V | Read | |||
| Min Voltage, Real Part U L3-N (Short) | V | Read | |||
| Min Voltage, Imaginary Part U L1-N (Short) | V | Read | |||
| Min Voltage, Imaginary Part U L2-N (Short) | V | Read | |||
| Min Voltage, Imaginary Part U L3-N (Short) | V | Read | |||
| Min Frequency 200 Ms, Integer (Short) | Hz | Read | |||
| Max Measured Frequency 10sec | Hz | Read | |||
| Max Voltage, Zero Sequence | V | Read | |||
| Max Voltage, Negative Sequence | V | Read | |||
| Max Voltage, Positive Sequence | V | Read | |||
| Max Voltage L1-N | V | Read | |||
| Max Voltage L2-N | V | Read | |||
| Max Voltage L3-N | V | Read | |||
| Max Voltage L1-L2 | V | Read | |||
| Max Voltage L2-L3 | V | Read | |||
| Max Voltage L3-L1 | V | Read | |||
| Max Fundamental Power Factor, Cos Phi, UL1-N I1 | Read | ||||
| Max Fundamental Power Factor, Cos Phi, UL2-N I2 | Read | ||||
| Max Fundamental Power Factor, Cos Phi, UL3-N I3 | Read | ||||
| Max Fundamental Power Factor Total | Read | ||||
| Max Power Factor, UL1-N I1 | Read | ||||
| Max Power Factor, UL2-N I2 | Read | ||||
| Max Power Factor, UL3-N I3 | Read | ||||
| Max Sum, Power Factor Sum | Read | ||||
| Max THD, U L1-N | % | Read | |||
| Max THD, U L2-N | % | Read | |||
| Max THD, U L3-N | % | Read | |||
| Max THD, U L1-L2 | % | Read | |||
| Max THD, U L2-L3 | % | Read | |||
| Max THD, U L3-L1 | % | Read | |||
| Max Voltage, Real Part U L1-N | V | Read | |||
| Max Voltage, Real Part U L2-N | V | Read | |||
| Max Voltage, Real Part U L3-N | V | Read | |||
| Max Voltage, Imaginary Part U L1-N | V | Read | |||
| Max Voltage, Imaginary Part U L2-N | V | Read | |||
| Max Voltage, Imaginary Part U L3-N | V | Read | |||
| Max Current I L1 | A | Read | |||
| Max Current I L2 | A | Read | |||
| Max Current I L3 | A | Read | |||
| Max Neutral Current Vector Sum | A | Read | |||
| Max Real Power P L1-N | W | Read | |||
| Max Real Power P L2-N | W | Read | |||
| Max Real Power P L3-N | W | Read | |||
| Max Real Power Total | W | Read | |||
| Max Fundamental Reactive Power Q L1-N | var | Read | |||
| Max Fundamental Reactive Power Q L2-N | var | Read | |||
| Max Fundamental Reactive Power Q L3-N | var | Read | |||
| Max Fundamental Reactive Power Total | var | Read | |||
| Max Apparent Power S L1-N | VA | Read | |||
| Max Apparent Power S L2-N | VA | Read | |||
| Max Apparent Power S L3-N | VA | Read | |||
| Max Apparent Power Total | VA | Read | |||
| Max Fundamental Real Power P0 L1-N | W | Read | |||
| Max Fundamental Real Power P0 L2-N | W | Read | |||
| Max Fundamental Real Power P0 L3-N | W | Read | |||
| Max Fundamental Real Power Total | W | Read | |||
| Max Harmonic Distortion Power D L1-N | var | Read | |||
| Max Harmonic Distortion Power D L2-N | var | Read | |||
| Max Harmonic Distortion Power D L3-N | var | Read | |||
| Max Distortion Power Total | var | Read | |||
| Max THD I1 | % | Read | |||
| Max THD I2 | % | Read | |||
| Max THD I3 | % | Read | |||
| Max TDD I1 | % | Read | |||
| Max TDD I2 | % | Read | |||
| Max TDD I3 | % | Read | |||
| Max Current, Zero Sequence | A | Read | |||
| Max Current, Negative Sequence | A | Read | |||
| Max Positive Sequence | A | Read | |||
| Max Real Part I L1 | A | Read | |||
| Max Real Part I L2 | A | Read | |||
| Max Real Part I L3 | A | Read | |||
| Max Imaginary Part I L1 | A | Read | |||
| Max Imaginary Part I L2 | A | Read | |||
| Max Imaginary Part I L3 | A | Read | |||
| Max Frequency 200 Ms | Hz | Read | |||
| Max Measured Frequency 10sec (Short) | Hz | Read | |||
| Max Voltage, Zero Sequence (Short) | Read | ||||
| Max Voltage, Negative Sequence (Short) | Read | ||||
| Max Voltage, Positive Sequence (Short) | Read | ||||
| Max Voltage L1-N (Short) | V | Read | |||
| Max Voltage L2-N (Short) | V | Read | |||
| Max Voltage L3-N (Short) | V | Read | |||
| Max Voltage L1-L2 (Short) | V | Read | |||
| Max Voltage L2-L3 (Short) | V | Read | |||
| Max Voltage L3-L1 (Short) | V | Read | |||
| Max Fundamental Power Factor, Cos Phi, UL1-N I1 (Short) | Read | ||||
| Max Fundamental Power Factor, Cos Phi, UL2-N I2 (Short) | Read | ||||
| Max Fundamental Power Factor, Cos Phi, UL3-N I3 (Short) | Read | ||||
| Max Fundamental Power Factor Total (Short) | Read | ||||
| Max Power Factor, UL1-N I1 (Short) | Read | ||||
| Max Power Factor, UL2-N I2 (Short) | Read | ||||
| Max Power Factor, UL3-N I3 (Short) | Read | ||||
| Max Power Factor Total (Short) | Read | ||||
| Max THD U L1-N (Short) | % | Read | |||
| Max THD U L2-N (Short) | % | Read | |||
| Max THD U L3-N (Short) | % | Read | |||
| Max THD U L1-L2 (Short) | % | Read | |||
| Max THD U L2-L3 (Short) | % | Read | |||
| Max THD U L3-L1 (Short) | % | Read | |||
| Max Real Part U L1-N (Short) | V | Read | |||
| Max Real Part U L2-N (Short) | V | Read | |||
| Max Real Part U L3-N (Short) | V | Read | |||
| Max Imaginary Part U L1-N (Short) | V | Read | |||
| Max Imaginary Part U L2-N (Short) | V | Read | |||
| Max Imaginary Part U L3-N (Short) | V | Read | |||
| Max Current I L1 (Short) | A | Read | |||
| Max Current I L2 (Short) | A | Read | |||
| Max Current I L3 (Short) | A | Read | |||
| Max Neutral Current Vector Sum (Short) | A | Read | |||
| Max Real Power P L1-N (Short) | W | Read | |||
| Max Real Power P L2-N (Short) | W | Read | |||
| Max Real Power P L3-N (Short) | W | Read | |||
| Max Real Power Total (Short) | W | Read | |||
| Max Fundamental Reactive Power Q L1-N (Short) | var | Read | |||
| Max Fundamental Reactive Power Q L2-N (Short) | var | Read | |||
| Max Fundamental Reactive Power Q L3-N (Short) | var | Read | |||
| Max Fundamental Reactive Power Total (Short) | var | Read | |||
| Max Apparent Power S L1-N (Short) | VA | Read | |||
| Max Apparent Power S L2-N (Short) | VA | Read | |||
| Max Apparent Power S L3-N (Short) | VA | Read | |||
| Max Apparent Power Total (Short) | VA | Read | |||
| Max Fundamental Real Power P0 L1-N (Short) | W | Read | |||
| Max Fundamental Real Power P0 L2-N (Short) | W | Read | |||
| Max Fundamental Real Power P0 L3-N (Short) | W | Read | |||
| Max Fundamental Real Power Total (Short) | W | Read | |||
| Max Harmonic Distortion Power D L1-N (Short) | var | Read | |||
| Max Harmonic Distortion Power D L2-N (Short) | var | Read | |||
| Max Harmonic Distortion Power D L3-N (Short) | var | Read | |||
| Max Distortion Power Total (Short) | var | Read | |||
| Max THD I1 (Short) | % | Read | |||
| Max THD I2 (Short) | % | Read | |||
| Max THD I3 (Short) | % | Read | |||
| Max TDD I1 (Short) | % | Read | |||
| Max TDD I2 (Short) | % | Read | |||
| Max TDD I3 (Short) | % | Read | |||
| Max Current, Zero Sequence (Short) | A | Read | |||
| Max Current, Negative Sequence (Short) | A | Read | |||
| Max Current, Positive Sequence (Short) | A | Read | |||
| Max Current, Real Part I1 (Short) | A | Read | |||
| Max Current, Real Part I2 (Short) | A | Read | |||
| Max Current, Real Part I3 (Short) | A | Read | |||
| Max Current, Imaginary Part I L1 (Short) | A | Read | |||
| Max Current, Imaginary Part I L2 (Short) | A | Read | |||
| Max Current, Imaginary Part I L3 (Short) | A | Read | |||
| Max Frequency 200 Ms, Integer (Short) | Hz | Read | |||
| Current Transformer I1, Primary | A | Read and write | |||
| Current Transformer I1, Sec | A | Read and write | |||
| Voltage Transformer V1, Primary | V | Read and write | |||
| Voltage Transformer V1, Sec. | V | Read and write | |||
| Current Transformer I2, Primary | A | Read and write | |||
| Current Transformer I2, Sec | A | Read and write | |||
| Voltage Transformer V2, Primary | V | Read and write | |||
| Voltage Transformer V2, Sec. | V | Read and write | |||
| Current Transformer I3, Primary | A | Read and write | |||
| Current Transformer I3, Sec | A | Read and write | |||
| Voltage Transformer V3, Primary | V | Read and write | |||
| Voltage Transformer V3, Sec. | V | Read and write | |||
| Frequency Determination | Hz | Read and write | |||
| Display Contrast | Read and write | ||||
| Background Lighting | Read and write | ||||
| Display Profile | Read and write | ||||
| Display Change Profile | Read and write | ||||
| Changeover Time for Measured Value Displays | s | Read and write | |||
| Averaging Time, I | Read and write | ||||
| Averaging Time, P | Read and write | ||||
| Averaging Time, U | Read and write | ||||
| Nominal Current TDD | A | Read and write | |||
| Minimum Response Current | mA | Read and write | |||
| Password | Read and write | ||||
| Results of the Comparator Group 1 Combine A, B, C | Read and write | ||||
| Comparator 1A, Limit | Read and write | ||||
| Comparator 1A, Address of Measurement Value | Read and write | ||||
| Comparator 1A, Min. on Time | s | Read and write | |||
| Comparator 1A, Lead Time | s | Read and write | |||
| Comparator 1A, Operator | Read and write | ||||
| Comparator 1B, Limit | Read and write | ||||
| Comparator 1B, Address of Measurement Value | Read and write | ||||
| Comparator 1B, Min. on Time | s | Read and write | |||
| Comparator 1B, Lead Time | s | Read and write | |||
| Comparator 1B, Operator | Read and write | ||||
| Comparator 1C, Limit | Read and write | ||||
| Comparator 1C, Address of Measurement Value | Read and write | ||||
| Comparator 1C, Min. on Time | s | Read and write | |||
| Comparator 1C, Lead Time | s | Read and write | |||
| Comparator 1C, Operator | Read and write | ||||
| Results of the Comparator Group 2 Combine A, B, C | Read and write | ||||
| Comparator 2A, Limit | Read and write | ||||
| Comparator 2A, Address of Measurement Value | Read and write | ||||
| Comparator 2A, Min. on Time | s | Read and write | |||
| Comparator 2A, Lead Time | s | Read and write | |||
| Comparator 2A, Operator | Read and write | ||||
| Comparator 2B, Limit | Read and write | ||||
| Comparator 2B, Address of Measurement Value | Read and write | ||||
| Comparator 2B, Min. on Time | s | Read and write | |||
| Comparator 2B, Lead Time | s | Read and write | |||
| Comparator 2B, Operator | Read and write | ||||
| Comparator 2C, Limit | Read and write | ||||
| Comparator 2C, Address of Measurement Value | Read and write | ||||
| Comparator 2C, Min. on Time | s | Read and write | |||
| Comparator 2C, Lead Time | s | Read and write | |||
| Comparator 2C, Operator | Read and write | ||||
| Connection Configuration, I L1 | Read and write | ||||
| Connection Configuration, I L2 | Read and write | ||||
| Connection Configuration, I L3 | Read and write | ||||
| Connection Configuration, U L1 | Read and write | ||||
| Connection Configuration, U L2 | Read and write | ||||
| Connection Configuration, U L3 | Read and write | ||||
| Delete Min. and Maximum Values | Read and write | ||||
| Delete Energy Values | Read and write | ||||
| Write in EEPROM | Read and write | ||||
| Connection Diagram Voltage | Read and write | ||||
| Connection Diagram Current | Read and write | ||||
| Voltages Used for THD and Harmonics on the Display | Read and write | ||||
| Overrange | Read | ||||
| Comparator 1 Output A | Read | ||||
| Comparator 1 Output B | Read | ||||
| Comparator 1 Output C | Read | ||||
| Comparator 2 Output A | Read | ||||
| Comparator 2 Output B | Read | ||||
| Comparator 2 Output C | Read | ||||
| Linkage Result of Comparator Group 1 | Read | ||||
| Linkage Result of Comparator Group 2 | Read | ||||
| Tariff Settings, Real Energy | Read and write | ||||
| Tariff Settings, Real Energy Consumed | Read and write | ||||
| Tariff Settings, Real Energy Delivered | Read and write | ||||
| Tariff Settings, Fundamental Reactive Energy | Read and write | ||||
| Tariff Settings, Fundamental Reactive Energy Ind. | Read and write | ||||
| Tariff Settings, Fundamental Reactive Energy Cap. | Read and write | ||||
| Tariff Settings, Apparent Energy | Read and write | ||||
| Firmware Release, Major Version | Read | ||||
| Firmware Release, Minor Version | Read | ||||
| Firmware Release, Patch Version | Read | ||||
| Period After Which the Device Switches to Standby | s | Read and write | |||
| Background Lighting in Standby Mode | Read and write | ||||
| Serial Number | Read | ||||
| Production Number | Read | ||||
| MQTT Connection Status | Read | ||||
| Error Code of Last MQTT Error | Read | ||||
| Device Name | Read and write | ||||
| Device Description | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Build a dashboard per distribution board with voltage, current and power per phase.
- Get an alarm when a phase voltage drops below a limit, so a blown fuse is noticed quickly.
- Compare the currents of L1, L2 and L3 to find an unbalanced board.
- Report monthly consumption and feed-in per board from the energy counters.
- Track THD per phase to see the effect of drives, chargers and LED drivers.
- Check the highest mean power of a board before you add a new load.
Installation
Connect the RJ45 port of the meter to the network of the ModbusCloud Gateway, or directly to its LAN port.
Give the meter a fixed IP address or a DHCP reservation, and set the current and voltage transformer ratios on the device.
In ModbusCloud, add a Modbus TCP device with that IP address, port 502 and unit ID 1, and import this template.
Check that the phase voltages show the mains voltage and the frequency is about 50 Hz.
Things to watch for
The UMG 96-EL does not answer. What should I check?
Check that the meter and the ModbusCloud Gateway are in the same network and that you can reach the IP address of the meter. Use port 502. If the meter gets its address by DHCP, it may have a new address after a restart; give it a fixed address or a DHCP reservation.
Why do the 16-bit values differ from the float values?
The 16-bit values do not include the current and voltage transformer ratio, the float values do. With transformers, use the float values or multiply the 16-bit value by the ratio yourself. Also set the transformer ratios correctly on the device.
Some values stay at zero. Is the template wrong?
Tariff counters stay at zero until a tariff is active, and minimum and maximum values start again after they are deleted. Below the minimum response current the meter shows zero current. Check the connection diagram settings if one phase stays at zero.
Can I write the energy counters and settings?
Yes. The float energy counters, transformer ratios, tariffs and comparators can be written. A write changes the meter right away and cannot be undone, so read the current value first and only write when you are sure. Wrong transformer ratios make every reading wrong.
Want to see how it works?