ONOKOM AIR HS-VRF-MB-B
Controls Hisense VRF air conditioners via the ONOKOM HS-VRF-MB-B gateway over Modbus RTU.
This template connects Hisense VRF air conditioners to ModbusCloud via the ONOKOM HS-VRF-MB-B gateway over Modbus RTU. It provides per-unit temperature readings, on/off control, mode selection, fan speed, target temperature, and vane positioning for up to 64 indoor units.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 513, read and write
- Brand
- Onokom
- Key readings
- Indoor air temperature · Indoor unit online status · Horizontal vanes status
- Available commands
- Active on/off · Target temperature · Smart fan speed · Vanes swing
- Compatible models
- ONOKOM HS-VRF-MB-B
- Last updated
Registers (513)
192 read, 385 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Modbus address (Service) | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write | ||||
| Indoor air temperature | °C | Read | |||
| Indoor unit is on the line (Status) | Read | ||||
| Horizontal vanes (Status) | Read and write | ||||
| Active (Control) | Write | ||||
| Loxone modes (Control) | Write | ||||
| Smart fan speed | Write | ||||
| Target temperature | °C | Write | |||
| Vanes swing | Write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Monitor indoor air temperatures across all Hisense VRF zones on a single cloud dashboard.
- Control target temperature setpoints remotely for each indoor unit without visiting the site.
- Create an alert when an indoor unit goes offline or stops reporting its online status.
- Adjust fan speed and vane swing settings for individual zones based on occupancy schedules.
- Log historical temperature data per zone to identify comfort issues or inefficient operation.
- Verify that all connected VRF units are running in the correct operating mode after commissioning.
Installation
Connect the ONOKOM HS-VRF-MB-B gateway to the Hisense VRF communication bus following the ONOKOM wiring instructions.
Wire the Modbus RTU (RS-485) output of the ONOKOM gateway to the RS-485 port on your ModbusCloud Gateway, connecting A, B, and GND.
Set the baud rate on the ONOKOM gateway to 9600 and configure the Modbus slave address to match the template settings.
In the ModbusCloud platform, import the ONOKOM AIR HS-VRF-MB-B template and assign it to the correct gateway port.
Verify that register blocks align with your indoor unit numbering (unit 0 at 10001, unit 1 at 10101, etc.) and adjust offsets if needed.
Confirm live data appears on the dashboard by checking indoor temperature readings and toggling an indoor unit on and off.
Things to watch for
Why do I see no data even though the RS-485 wiring looks correct?
Confirm the baud rate is set to 9600 on both the ONOKOM gateway and the ModbusCloud gateway. Also verify that the A and B lines are not swapped and that a GND connection is present.
How do I address a specific indoor unit in the register map?
Registers are arranged in blocks of 100 per unit. Unit 0 starts at register 10001, unit 1 at 10101, unit 2 at 10201, and so on. Adjust the offset in the template to target the correct unit.
Can I control more than 64 indoor units with one ONOKOM gateway?
No. The ONOKOM HS-VRF-MB-B supports a maximum of 64 indoor units. For larger installations, a second gateway and a separate Modbus address are required.
The indoor unit online status shows offline but the unit is running. What should I check?
Ensure the Hisense VRF bus cable between the indoor unit and the ONOKOM gateway is properly connected. Also check that the unit is correctly registered on the Hisense VRF network.