Eastron Eastron SDM630 Series Modbus RTU template

Eastron SDM630 Series

Reads three-phase energy metering data from Eastron SDM630 meters.

This ModbusCloud template reads three-phase electrical measurements from the Eastron SDM630 multifunctional energy meter family (V1, V2, and V3) over Modbus RTU at 9600 baud. All fifteen registers are read only float32 values covering per-phase voltage and current, per-phase and total active, reactive, and apparent power, import and export energy totals, and line frequency.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
15, read only
Brand
Eastron
Key readings
Voltage L1 to L3 · Current L1 to L3 · Power L1 to L3 · Total active/apparent/reactive Power · Total Energy Import/Export · Frequency
Compatible models
SDM630 · SDM630 V1 · SDM630 V2 · SDM630 V3
Last updated

Registers (15)

15 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Voltage L1VRead
Voltage L2VRead
Voltage L3VRead
Current L1ARead
Current L2ARead
Current L3ARead
Power L1WRead
Power L2WRead
Power L3WRead
Total active PowerWRead
FrequencyHzRead
Total Energy ImportkWhRead
Total Energy ExportkWhRead
Total apparent PowerVARead
Total reactive PowervarRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Track total building consumption, per-phase load, and solar export on a live ModbusCloud dashboard.
  • Alert the installer when any phase current exceeds a safe threshold for more than a minute to catch overloads early.
  • Log import and export energy separately for net-billing compliance reports.
  • Compare measured consumption against invoiced kWh from the utility to spot metering or billing discrepancies.
  • Feed per-phase power into an automation rule that throttles an EV charger when building peak demand is approached.

Installation

  1. Wire the SDM630 A and B terminals to the RS485 channel of your ModbusCloud gateway using twisted pair cable, keeping a common ground where possible.

  2. Verify the meter settings in the front panel menu: address 1, baudrate 9600, 1 stop bit, no parity. Change only if you have multiple meters on the bus.

  3. In ModbusCloud, add a new Modbus RTU device with the same address and baudrate, then import the Eastron SDM630 template.

  4. Confirm voltage and current readings match the meter display. If numbers look swapped or scaled wrong, enable byte order swap in device settings.

Things to watch for

Voltages read correctly but currents are zero. What is wrong?

This is almost always a missing CT connection on the meter. Check that the current transformers are clamped in the right orientation and wired to the correct meter terminals. The SDM630 shows live currents on its display, which is the fastest way to verify hardware before suspecting Modbus.

I see wildly wrong numbers like 3.4e38. Byte order problem?

Yes. Float32 registers can be decoded ABCD, CDAB, BADC, or DCBA depending on the converter. Swap the byte order in ModbusCloud device settings. For a direct RS485 connection on ModbusCloud gateways, ABCD is the correct default.

Can I daisy chain multiple SDM630 meters on one RS485 bus?

Yes. Give each meter a unique Modbus address (2, 3, 4, ...) through the front panel menu, then create one device per meter in ModbusCloud and import this template on each. The bus can handle up to 32 meters in practice.